[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-115-1-water-chemical-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":71},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-115-1-水與化學系統消防安全設備概要-029","fire-115-1-water-chemical-029",115,1,29,"鹵化烴滅火設備使用氣體啟動者，有關設置之規定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"啟動用氣體容器能耐每平方公分二百五十公斤之壓力","啟動用氣體容器之內容積應有一公升以上，其所儲存之二氧化碳重量在零點四公斤以上，且其充填比在一點三五以上","啟動用氣體容器之安全裝置及容器閥符合 CNS 四六二六規定，或經中央主管機關認可具同等性能以上者","啟動用氣體容器可兼供防護區域之自動關閉裝置使用","A",null,[],false,"",[26,31,34,38,42,46],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-107-1-water-chemical-027","有關二氧化碳滅火設備放射時間之敘述，下列何者正確？",27,107,{"webId":32,"stem":33,"number":13,"year":30,"session":12},"fire-107-1-water-chemical-029","全區放射二氧化碳滅火設備進行綜合檢查時，如為高壓式儲存系統，在放射試驗時需放射多少藥劑量？",{"webId":35,"stem":36,"number":37,"year":30,"session":12},"fire-107-1-water-chemical-026","室內消防栓設備之消防立管管系竣工時，應做加壓試驗，試驗壓力不得小於加壓送水裝置全閉揚程 A 倍以上之水壓。試驗壓力以繼續維持 B 小時無漏水現象為合格，A、B 分別為：",26,{"webId":39,"stem":40,"number":41,"year":30,"session":12},"fire-107-1-water-chemical-030","實施二氧化碳滅火設備檢修，於進行性能檢查時，皮管連接部應無鬆動，皮管損傷、老化等情形，且皮管長度應在幾公尺以上？",30,{"webId":43,"stem":44,"number":45,"year":30,"session":12},"fire-107-1-water-chemical-025","泡沫滅火設備進行綜合檢查時，有關泡沫滅火藥劑 25%還原時間標準值敘述，下列何者正確？",25,{"webId":47,"stem":48,"number":49,"year":30,"session":12},"fire-107-1-water-chemical-031","惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",31,[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-113-1-water-chemical-029",113,"有關流水檢知裝置之構造，依據流水檢知裝置認可基準規定，下列敘述何者錯誤？",{"webId":56,"year":57,"stem":58,"number":13},"fire-112-1-water-chemical-029",112,"有關泡沫滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":60,"year":61,"stem":62,"number":13},"fire-111-1-water-chemical-029",111,"變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",{"webId":64,"year":65,"stem":66,"number":13},"fire-110-1-water-chemical-029",110,"公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",{"webId":68,"year":69,"stem":70,"number":13},"fire-109-1-water-chemical-029",109,"泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",true,1785129971216]