[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-115-1-water-chemical-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":24,"sameNumber":50,"hasEssay":71},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":23,"freq":12,"indexable":22},"fire-115-1-水與化學系統消防安全設備概要-001","fire-115-1-water-chemical-001",115,1,"有關消防幫浦性能試驗，下列敘述何者錯誤？",{"A":15,"B":16,"C":17,"D":18},"消防幫浦出水量在額定出水量時，其性能曲線上之全揚程必須達額定揚程之 100%至 110%之間","消防幫浦出水量在額定出水量之 150%時，其性能曲線上之全揚程必須達額定揚程之 65%以上","全閉揚程應為額定出水量在性能曲線上全揚程之 140%以上","消防幫浦二次測壓力錶所顯示壓力值 1 kg\u002Fcm2 約等於 10 公尺揚程","C",null,[],false,"",[25,30,34,38,42,46],{"webId":26,"stem":27,"number":28,"year":29,"session":12},"fire-106-1-water-chemical-039","泡沫滅火設備使用低發泡水成膜泡沫液，其泡沫 25%還原時間應在多少分鐘以上？",39,106,{"webId":31,"stem":32,"number":12,"year":33,"session":12},"fire-107-1-water-chemical-001","撒水頭之設置位置規定中，撒水頭迴水板下方 A 公分內及水平方向 B 公分內，應保持淨空間，不得有障礙物，其中 A、B 分別為下列何者？",107,{"webId":35,"stem":36,"number":37,"year":29,"session":12},"fire-106-1-water-chemical-038","乾粉全區放射所核算之滅火藥劑量須於幾秒內放射完畢？",38,{"webId":39,"stem":40,"number":41,"year":33,"session":12},"fire-107-1-water-chemical-002","有關連結送水管之送水口設置規定，下列何者錯誤？",2,{"webId":43,"stem":44,"number":45,"year":29,"session":12},"fire-106-1-water-chemical-037","消防幫浦之全閉揚程應為性能曲線上全揚程之百分之多少以下，方符合檢修基準要求？",37,{"webId":47,"stem":48,"number":49,"year":33,"session":12},"fire-107-1-water-chemical-003","水霧滅火設備之水源容量規定，下列何者正確？",3,[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":12},"fire-113-1-water-chemical-001",113,"有關消防安全設備水源容量之放水時間，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",{"webId":56,"year":57,"stem":58,"number":12},"fire-112-1-water-chemical-001",112,"某一新建建築物設有室內消防栓設備，其加壓送水裝置全閉揚程為 60 公尺，今於上午 9 時施作消防立管管系加壓試驗，試驗壓力應大於 X kgf\u002Fcm2 以上之水壓，且須持續維持試驗壓力至 Y 時止均無漏水現象方為合格。其中 X 與 Y 分別為多少？",{"webId":60,"year":61,"stem":62,"number":12},"fire-111-1-water-chemical-001",111,"依各類場所消防安全設備設置標準規定，下列何種場所不需設置室外消防栓設備？",{"webId":64,"year":65,"stem":66,"number":12},"fire-110-1-water-chemical-001",110,"公共危險物品等場所消防設計及消防安全設備，電氣設備使用之處所，每多少平方公尺（含未滿）應設置第五種滅火設備一具以上？",{"webId":68,"year":69,"stem":70,"number":12},"fire-109-1-water-chemical-001",109,"下列場所何者未達依法應設置滅火器之條件？",true,1785129971065]