[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-114-1-water-chemical-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":71},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-114-1-水與化學系統消防安全設備概要-011","fire-114-1-water-chemical-011",114,1,11,"依滅火器認可基準規定，某種滅火器滅火效能值標示 B-20，該滅火器實施滅火效能值之第二種滅火試驗方式，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"可以滅火之油盤表面積為 4 平方公尺","滅火動作應於油盤點火 2 分鐘後開始","B-20 以上可於室外進行試驗，但應在風速 3.0 m\u002Fsec 以下之環境狀態進行","滅火藥劑噴射完畢後 1 分鐘以內不再復燃者，可判定已完全熄滅","B",null,[],false,"",[26,31,34,38,42,46],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-106-1-water-chemical-009","如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",9,106,{"webId":32,"stem":33,"number":13,"year":30,"session":12},"fire-106-1-water-chemical-011","鹵化烴滅火設備進行性能檢查時，控制裝置之遲延裝置檢查項目，於操作啟動按鈕後至容器閥開放裝置動作，其所需時間應為：",{"webId":35,"stem":36,"number":37,"year":30,"session":12},"fire-106-1-water-chemical-008","乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",8,{"webId":39,"stem":40,"number":41,"year":30,"session":12},"fire-106-1-water-chemical-012","簡易自動滅火設備進行性能檢查時，其蓄壓式滅火藥劑量應與標示重量差異在何範圍以內？",12,{"webId":43,"stem":44,"number":45,"year":30,"session":12},"fire-106-1-water-chemical-007","依各類場所消防安全設備設置標準，二氧化碳滅火設備之藥劑放射時間，下列何者正確？",7,{"webId":47,"stem":48,"number":49,"year":30,"session":12},"fire-106-1-water-chemical-013","有關室內消防栓之放水壓力，下列何者錯誤？",13,[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-113-1-water-chemical-011",113,"室內消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"webId":56,"year":57,"stem":58,"number":13},"fire-112-1-water-chemical-011",112,"建築物高度在 X 公尺以下時，其連結送水管得與室內消防栓共用立管，其管徑在 Y 毫米以上，支管管徑在 Z 毫米以上。其中 X、Y 與 Z 分別為多少？",{"webId":60,"year":61,"stem":62,"number":13},"fire-111-1-water-chemical-011",111,"依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",{"webId":64,"year":65,"stem":66,"number":13},"fire-110-1-water-chemical-011",110,"室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",{"webId":68,"year":69,"stem":70,"number":13},"fire-109-1-water-chemical-011",109,"乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",true,1785129971346]