[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-114-1-water-chemical-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":53,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-114-1-水與化學系統消防安全設備概要-004","fire-114-1-water-chemical-004",114,1,4,"依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",{"A":16,"B":17,"C":18,"D":19},"3.5","4.5","5.5","6.5","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》對鹵化烴滅火設備儲存容器加壓規定，分別為蓄壓式的氮氣加壓壓力與加壓式的壓力調整裝置壓力，並要求求兩者之和。\n【正解理由】依《各類場所消防安全設備設置標準》關於鹵化烴滅火設備儲存容器之規定，蓄壓式儲存容器儲存HFC-227ea、FK-5-1-12者，應於溫度攝氏21度時以氮氣加壓至2.5百萬帕斯卡以上，故X=2.5；加壓式儲存容器則應設置能調整壓力至2.0百萬帕斯卡之壓力調整裝置，故Y=2.0。兩者相加得2.5＋2.0＝4.5，故選B。\n【演算步驟】\n蓄壓式氮氣加壓壓力：X = 2.5 MPa。\n加壓式壓力調整裝置壓力：Y = 2.0 MPa。\n合計：X + Y = 2.5 MPa + 2.0 MPa = 4.5 MPa。\n【逐項排除】\n(A) 3.5須由1.5加2.0或2.5加1.0組成，其中1.5與1.0均非條文所定之加壓或調壓數值，數值來源不成立。\n(B) 4.5恰為蓄壓式2.5與加壓式2.0之和，兩個組成值均與條文一致，正確。\n(C) 5.5須由3.5加2.0或2.5加3.0組成，3.5與3.0皆非本條所列壓力級距，屬憑印象加碼的誘答。\n(D) 6.5多由誤把蓄壓式壓力記成另一較高加壓級距4.2再湊整而來，與本題所問藥劑之2.5規定不符。\n【記憶點】鹵化烴「蓄壓2.5、加壓調2.0」，相加就是4.5。","鹵化烴滅火設備是海龍滅火設備的替代體系。海龍藥劑滅火效率極高，靠溴自由基捕捉燃燒連鎖反應中的活性基而中斷燃燒，但因破壞臭氧層而依蒙特婁議定書逐步禁用，各國轉而採用不含溴的氫氟碳化物與氟化酮類藥劑，我國法制也隨之在設置標準中新增鹵化烴滅火設備專節，HFC-23、HFC-227ea、FK-5-1-12即是常見的替代藥劑。理解這段沿革，就能理解為何條文會逐藥劑分別訂定儲存壓力：不同藥劑的飽和蒸氣壓與充填比不同，加壓氮氣的量自然要分開規範。\n儲存容器的加壓方式分為蓄壓式與加壓式兩種，這是本題的辨識核心。蓄壓式是在容器內預先以氮氣加壓，藥劑與推進氣體同處一室，開放閥門即藉本身壓力放射，構造簡單、動作快，但需長期承壓並定期檢查壓力表；加壓式則另設加壓用氣體容器，動作時先將氣體導入儲存容器把藥劑推出，因為來源壓力較高，中間必須設置壓力調整裝置把壓力降到設計值，本題的2.0百萬帕斯卡即是這個調整後的目標壓力。兩者的差異也反映在檢修上：蓄壓式重點在壓力表指示與容器閥氣密，加壓式重點在加壓用氣體容器壓力與壓力調整裝置作動。\n單位換算是這一節的常見陷阱。1百萬帕斯卡約等於10.2公斤重每平方公分，也約等於102公尺水頭，故2.5百萬帕斯卡約相當於25.5公斤重每平方公分。條文一律以百萬帕斯卡表述，但教科書與現場壓力表常見公斤重每平方公分，換算關係必須熟練，否則遇到跨單位的敘述題容易誤判。\n延伸考點包括：全區放射方式的藥劑放射時間規定、防護區劃開口部與自動關閉裝置、儲存容器設置場所應避免陽光直射與高溫、以及與二氧化碳滅火設備在對人體危害性上的差異——二氧化碳以窒息為主要滅火機制而有致命風險，故對常時有人場所限制嚴格，鹵化烴則以抑制連鎖反應為主、設計濃度下對人相對安全，這組對照幾乎年年入題，宜與本條數值一併整理。",true,[28,33,37,41,45,49],{"webId":29,"stem":30,"number":31,"year":32,"session":12},"fire-113-1-water-chemical-040","有關射水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",40,113,{"webId":34,"stem":35,"number":12,"year":36,"session":12},"fire-106-1-water-chemical-001","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列何者錯誤？",106,{"webId":38,"stem":39,"number":40,"year":32,"session":12},"fire-113-1-water-chemical-039","某一工廠儲存鹼金屬過氧化物，滅火藥劑適用下列何者？",39,{"webId":42,"stem":43,"number":44,"year":36,"session":12},"fire-106-1-water-chemical-002","依各類場所消防安全設備設置標準，下列何種場所不需設置滅火器？",2,{"webId":46,"stem":47,"number":48,"year":32,"session":12},"fire-113-1-water-chemical-038","依各類場所消防安全設備設置標準之規定，下列何場所得免設滅火器？",38,{"webId":50,"stem":51,"number":52,"year":36,"session":12},"fire-106-1-water-chemical-003","有關滅火器設置間距之規定，下列何者錯誤？",3,[54,57,61,65,69],{"webId":55,"year":32,"stem":56,"number":13},"fire-113-1-water-chemical-004","有關連結送水管設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-water-chemical-004",112,"依水道連結型自動撒水設備設置基準之規定，採民生水箱共用式，其配管、配件及閥類之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-water-chemical-004",111,"裝置於舞臺之開放式自動撒水設備，依規定下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-water-chemical-004",110,"下列有關室內消防栓設備之規定，何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-water-chemical-004",109,"供集會堂使用之舞臺，應設置何種自動撒水設備？",1785129971304]