[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-114-1-fire-law-035":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-114-1-消防法規概要-035","fire-114-1-fire-law-035",114,1,35,"消防法第 15 條之 5 第 4 項所規定儲存液體公共危險物品之儲槽達中央主管機關公告一定規模者，其管理權人於開始使用後，應委託專業機構實施定期檢查，作成紀錄，並至少保存 5 年。有關一定規模係指容量達多少公秉以上之室外儲槽？",{"A":16,"B":17,"C":18,"D":19},"1千","1萬","5萬","10 萬","B",null,[],false,"本題考點：《消防法》第 15-5 條第四項所稱「一定規模」的儲槽，其數字寫在哪裡、又是多少。\n【正解理由】《消防法》第 15-5 條第四項明定：「前項儲槽達中央主管機關公告一定規模者，其管理權人於開始使用後，應委託前項之專業機構實施定期檢查，作成紀錄，並至少保存五年；公告生效前已設置之儲槽，應自公告生效之日起五年內完成初次定期檢查。」條文只寫「一定規模」四個字，具體數值並不在法條裡，而是由中央主管機關（內政部）另以公告訂定；依該公告，一定規模指容量達一萬公秉以上之室外儲槽，故選 B。\n【逐項排除】\n(A) 一千公秉：尚未達公告所定之一萬公秉，此一規模之室外儲槽不因第四項而負委託專業機構定期檢查之義務。\n(B) 一萬公秉：與公告所定之規模相符，即本題所問之數值。\n(C) 五萬公秉：高於公告所定之規模；以此為界，容量一萬公秉以上、未達五萬公秉之室外儲槽會被漏在門檻外。\n(D) 十萬公秉：同樣高於公告所定之規模，漏在門檻外的範圍比 (C) 更大。\n【記憶點】法條只給「一定規模」，數字在內政部公告裡：容量達一萬公秉以上之室外儲槽，檢查紀錄至少保存五年。","《消防法》第 15-5 條共七項，是一條把公共危險物品場所從開工前一路管到使用中的時間軸條文。第一項是開工前：第 15 條第一項所定場所之起造人，應將該場所之位置、構造及設備圖說，送請場所所在地主管機關審查完成後，始得向主管建築機關申報開工。第二項是完工時：依建築法規定申請使用執照時，主管建築機關應會同前項辦理審查之主管機關檢查其位置、構造及設備合格後，始得發給使用執照。第三項是儲槽的加強規定：儲存液體公共危險物品之儲槽起造人，依前項規定申請使用執照前，應經中央主管機關許可之專業機構完成檢查，並出具合格證明文件。第四項才進入使用中的定期檢查，也就是本題所問；第五項、第六項分別授權訂定儲槽檢查辦法與專業機構許可辦法；第七項規定第四項之儲槽，中央目的事業主管機關另有定期檢查規定者，依其規定辦理。\n這一條要分清「數字寫在法條裡」與「數字寫在公告裡」兩種題型。法條出現「一定規模」「由中央主管機關公告」這類文字時，門檻是另以公告訂定的，翻遍條文都找不到數字；本題的一萬公秉即屬此類，它是公告的內容，不是第 15-5 條的文字。記住授權依據在第四項，數值以公告為準。\n第四項還藏了兩個「五年」，命題最愛互換：一個是檢查紀錄至少保存五年，另一個是公告生效前已設置之儲槽，應自公告生效之日起五年內完成初次定期檢查。違反的效果在《消防法》第 42-3 條第一項第二款：管理權人違反第十五條之五第四項規定，未委託中央主管機關許可之專業機構實施儲槽定期檢查、未依規定期限完成初次定期檢查，或儲槽定期檢查紀錄未至少保存五年者，處新臺幣二萬元以上十萬元以下罰鍰，並通知限期改善，屆期未改善者，得按次處罰。\n最後分清「規模」的層次。《公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法》第 6 條把公共危險物品儲存場所分為室外儲存、室內儲存、室內儲槽、室外儲槽、地下儲槽五種，其中室外儲槽場所指在建築物外地面上設置容量超過六百公升且不可移動之儲槽儲存六類物品之場所——六百公升是「成為列管場所」的門檻；本題的一萬公秉則是已列管之室外儲槽再升一級、必須實施定期檢查的門檻。兩者層次不同，不可互相套用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-114-1-fire-law-034","依消防法施行細則規定，下列何者非屬消防防災計畫應包括事項？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-114-1-fire-law-036","消防設備人員執行消防安全設備之測試業務，製作測試報告書是由消防安全設備測試人員依滅火設備、警報設備、避難逃生設備、消防搶救上之必要設備及其他經中央主管機關認定之消防安全設備等依序製表，並確認各項消防安全設備之試驗符合規定。下列何者非屬應實施之試驗？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-114-1-fire-law-033","依六類公共危險物品製造儲存及處理場所標示板規格及設置要點規定，下列敘述何者正確？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-114-1-fire-law-037","依建築技術規則建築設計施工編規定，下列敘述何者正確？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-114-1-fire-law-032","依可燃性高壓氣體場所標示板規格及設置要點規定，下列敘述何者錯誤？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-114-1-fire-law-038","依消防法規定，下列敘述何者錯誤？",38,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-law-035",113,"液化石油氣販賣場所經營者應每 6 個月向販賣場所及供應設備所在地之消防機關申報資料，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-035",112,"下列何者非屬高層建築物消防安全設備竣工查驗時應檢附之資料？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-035",111,"某合法 KTV 視聽歌唱場所經當地消防機關會勘通過依法取得室內裝修許可，依照消防安全設備檢修及申報辦法規定，自該室內裝修許可核發之日期起算，距申報期限在多少個月以內，免辦理當次檢修及申報備查？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-035",110,"某幼兒園經當地消防機關會勘通過依法取得使用執照，依消防安全設備檢修及申報辦法規定，自該使用執照證明文件核發之日期起算，距申報期限在幾個月內，免辦理當次檢修及申報備查？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-035",109,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，裝設消防撒水幫浦，設計水量為 600 公升\u002F分，其設計揚程為 50 公尺；當揚水量在 900 公升\u002F分時，其揚程需調校在下列何標準值以上，方能判定合格？",1785129968725]