[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-114-1-fire-law-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-114-1-消防法規概要-028","fire-114-1-fire-law-028",114,1,28,"依各類場所消防安全設備設置標準規定，二氧化碳滅火設備全區及局部放射方式之緊急電源，應採用自用發電設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",{"A":16,"B":17,"C":18,"D":19},"20 分鐘","30 分鐘","1 小時","2 小時","C",null,[],false,"本題考點：二氧化碳滅火設備全區放射方式與局部放射方式之緊急電源，其電源種類與容量時間。\n【正解理由】依《各類場所消防安全設備設置標準》第 95 條，全區及局部放射方式之緊急電源，應採用自用發電設備或蓄電池設備，其容量應能使該設備有效動作一小時以上。條文把電源種類寫成自用發電設備、蓄電池設備二者，容量則逐字寫明「一小時以上」，故選 C。\n【逐項排除】\n(A) 20 分鐘：第 95 條所定為一小時；二十分鐘是同標準第 155 條出口標示燈及避難方向指示燈緊急電源蓄電池設備之容量，該條並定設於所列場所主要避難路徑者為六十分鐘以上。\n(B) 30 分鐘：三十分鐘是同標準第 38 條室內消防栓設備緊急電源、第 177 條緊急照明設備蓄電池設備之供電容量，不是第 95 條對全區及局部放射方式所定之值。\n(C) 1 小時：與第 95 條「其容量應能使該設備有效動作一小時以上」相符，為本題正解。\n(D) 2 小時：二小時是第 192-1 條第二項防災監控系統綜合操作裝置緊急電源之供電容量，與二氧化碳滅火設備之緊急電源分屬不同條文。\n【記憶點】第 95 條一句話兩個重點：電源為自用發電設備或蓄電池設備，容量為有效動作一小時以上。","《各類場所消防安全設備設置標準》第 95 條的原文是「全區及局部放射方式之緊急電源，應採用自用發電設備或蓄電池設備，其容量應能使該設備有效動作一小時以上」，句中並未出現任何藥劑名稱。它與第 82 條以下規範二氧化碳及惰性氣體滅火設備的各條同段，條文未限定藥劑種類，惰性氣體滅火設備之緊急電源即依本條辦理；同段的第 93 條第二項另定惰性氣體滅火設備之安全裝置，第 97 條則寫明「二氧化碳及惰性氣體滅火設備使用之各種標示規格」由中央主管機關另定。鹵化烴滅火設備另有第 97-8 條「鹵化烴滅火設備之緊急電源，準用第九十五條之規定設置」；乾粉滅火設備依第 98 條，其放射方式、通風換氣裝置、防護區域之開口部、選擇閥、啟動裝置、音響警報裝置、安全裝置、緊急電源及各種標示規格，準用第八十二條、第八十五條、第八十六條、第九十條至第九十三條、第九十五條及第九十七條規定設置。\n把同一部標準各設備的緊急電源並列起來看，數值分布會清楚許多。室內消防栓設備依第 38 條為三十分鐘以上，且供第十二條第四款使用之場所，得使用具有相同效果之引擎動力系統；火警自動警報設備依第 128 條應使用蓄電池設備，容量為十分鐘以上；緊急照明設備依第 177 條應使用蓄電池設備，持續動作三十分鐘以上，但採蓄電池設備與緊急發電機併設方式時，容量分別為十分鐘及三十分鐘以上；排煙設備依第 188 條第九款為三十分鐘以上；特別安全梯或緊急昇降機間排煙室之排煙口、進風口、排煙機及進風機，依第 189 條第二款第六目亦為三十分鐘以上；無線電通信輔助設備設增輻器時，依第 192 條第五款為三十分鐘以上；防災監控系統綜合操作裝置依第 192-1 條第二項，緊急電源準用第 38 條規定，供電容量則為二小時以上。背的時候要連條號一起背。\n鄰近條次的考點也常一起命題。第 93 條第一項就二氧化碳滅火設備全區放射方式之安全裝置，定有啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有二十秒以上之遲延裝置、採手動啟動時應採取在前款延遲時間內滅火藥劑不得放射之措施，以及於防護區域出入口等易於辨認處所設置放射表示燈。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-114-1-fire-law-027","依各類場所消防安全設備設置標準，針對滅火設備水源容量之規定，下列敘述何者錯誤？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-114-1-fire-law-029","依各類場所消防安全設備設置標準規定，下列何處所得免設排煙設備？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-114-1-fire-law-026","依據消防法、公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法，有關公共危險物品管制量規定，下列敘述何者錯誤？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-114-1-fire-law-030","下列何者非屬各類場所消防安全設備設置標準之警報設備？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-114-1-fire-law-025","依消防設備人員法規定，有關消防設備人員的業務及責任，下列敘述何者錯誤？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-114-1-fire-law-031","依消防法相關規定，下列敘述何者正確？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-law-028",113,"直轄市、縣（市）有登記執業之消防設備師或消防設備士達多少人以上者，得組織消防設備師公會或消防設備士公會？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-028",112,"經濟部輔導未登記工廠申請補辦臨時工廠登記，若該場所消防安全設備業依消防機關辦理建築物消防安全設備審查及查驗作業基準之規定完成測試，且經查驗合格，多久時間免辦理消防安全設備檢修結果申報？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-028",111,"可燃性高壓氣體儲存場所防爆牆，其鋼筋混凝土經過 28 日養生後之抗壓強度（kgf\u002Fcm2），應為多少以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-028",110,"依各類場所消防安全設備設置標準規定，下列場所何者屬於乙類場所？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-028",109,"依各類場所消防安全設備設置標準，有關裝設瓦斯漏氣火警自動警報設備之規定，下列敘述何者錯誤？",1785129968679]