[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-114-1-fire-law-021":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-114-1-消防法規概要-021","fire-114-1-fire-law-021",114,1,21,"某工廠現有建築物及儲存場所之中度危險工作場所樓地板面積合計 2,000 平方公尺，該工廠將擴廠增建一棟一樓層之低度危險工作場所，該增建場所之建築物及儲存場所樓地板面積合計在多少平方公尺以上時，應設置室外消防栓設備？",{"A":16,"B":17,"C":18,"D":19},"3,000","5,000","6,000","8,000","D","第21題答Ｄ給分",[],false,"本題考點：室外消防栓設備應設場所中，不同危險程度工作場所之比例合計法。\n【正解理由】依《各類場所消防安全設備設置標準》第十六條第一項第四款，不同危險程度工作場所未達前三款標準時，以各款場所之實際面積為分子、各款規定之面積為分母分別計算，其比例之總和大於一者，應設室外消防栓設備；分母即第二款中度危險之五千平方公尺與第三款低度危險之一萬平方公尺。條文要求大於一，恰等於一並不成立，故選 D。\n【逐項排除】\n(A) 3,000 平方公尺：總和為 0.4＋0.3＝0.7，未大於一。\n(B) 5,000 平方公尺：總和為 0.4＋0.5＝0.9，未大於一。\n(C) 6,000 平方公尺：總和為 0.4＋0.6＝1.0，僅等於一，不符「大於一」之要件。\n(D) 8,000 平方公尺：總和為 0.4＋0.8＝1.2，大於一，為選項中最先滿足者。\n【演算步驟】公式：中度面積÷5,000 平方公尺＋低度面積÷10,000 平方公尺＞1。中度＝2,000 平方公尺÷5,000 平方公尺＝0.4；設低度面積為 X 平方公尺，0.4＋X÷10,000 平方公尺＞1，得 X＞6,000 平方公尺；代入 8,000 平方公尺得 0.4＋0.8＝1.2＞1，成立。\n【記憶點】室外消防栓門檻高中低為 3,000／5,000／10,000 平方公尺；混合場所分數相加須大於一，等於一不算。","第十六條第一項共五款。第一款高度危險工作場所為三千平方公尺，第二款中度危險為五千平方公尺，第三款低度危險為一萬平方公尺，均指建築物及儲存場所第一層及第二層樓地板面積合計；本題增建之場所僅一樓層，其樓地板面積即為該場所之計算面積。第四款是本題的比例合計法；第五款另定同一建築基地內有二棟以上木造或其他易燃構造建築物時，建築物間外牆與中心線水平距離第一層在三公尺以下、第二層在五公尺以下，且合計各棟第一層及第二層樓地板面積在三千平方公尺以上者，亦應設置。\n危險程度的定義不在第十六條，而在第四條第一項：高度危險工作場所指儲存一般可燃性固體物質倉庫之高度超過五點五公尺者，或易燃性液體物質之閃火點未超過攝氏六十度、且攝氏三十七點八度時蒸氣壓未超過每平方公分二點八公斤或 0.28MPa 者，或可燃性高壓氣體製造儲存處理場所、石化作業場所、木材加工業作業場所及油漆作業場所等；中度危險工作場所指倉庫高度未超過五點五公尺者，或易燃性液體物質閃火點超過攝氏六十度之作業場所或輕工業場所；低度危險工作場所指有可燃性物質存在，但存量少、延燒範圍小、延燒速度慢，僅形成小型火災者。做題時要先把場所歸到哪一款，分母才不會抓錯。\n計算上最常見的失分點有三個：一是把中度的五千與低度的一萬互換；二是漏看「第一層及第二層樓地板面積合計」，把全棟各層都加進去；三是把「大於一」讀成「達一」，本題的 6,000 平方公尺正是踩在等於一的位置而不成立。\n延伸考點方面，第十六條第二項另定應設室外消防栓設備之場所，依本標準設有自動撒水、水霧、泡沫、二氧化碳、惰性氣體、鹵化烴或乾粉等滅火設備者，在該有效範圍內得免設；水源與加壓送水裝置則見第四十一條（二具室外消防栓同時放水三十分鐘之水量以上）與第四十二條（幫浦出水量一支每分鐘四百公升以上、全揚程加二十五公尺）。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-114-1-fire-law-020","依建築技術規則建築設計施工編規定，下列敘述何者錯誤？",20,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-114-1-fire-law-022","消防設備人員依消防安全設備及必要檢修項目檢修基準規定，執行室內消防栓設備檢修之綜合檢查。下列檢查方法及判定方法，何者錯誤？",22,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-114-1-fire-law-019","依各類場所消防安全設備設置標準規定，下列何者應就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇設置？",19,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-114-1-fire-law-023","依消防設備人員法規定，下列敘述何者錯誤？",23,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-114-1-fire-law-018","依各類場所消防安全設備設置標準規定，下列何者為有效開口之必要條件？",18,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-114-1-fire-law-024","依避難器具支固器具及固定部之結構、強度計算及施工方法規定，有關斜降式救助袋之下部支撐裝置固定在降落面等器具之構造、強度及埋設到降落面之方法，下列敘述何者錯誤？",24,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-law-021",113,"有關消防設備人員執行業務，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-021",112,"依各類場所消防安全設備設置標準，滅火設備之室內消防栓設備、室外消防栓設備、泡沫滅火設備，及防火牆及防火水幕設置基準之防火水幕設備之水源容量規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-021",111,"依建築技術規則建築設計施工編所訂之建築技術用語，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-021",110,"依各類場所消防安全設備設置標準規定，有關應設置自動撒水設備之場所，其撒水頭之位置規定，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-021",109,"依各類場所消防安全設備設置標準，有關使用密閉式撒水頭自動撒水設備末端查驗閥之規定，下列敘述何者正確？",1785129968632]