[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-114-1-fire-law-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-114-1-消防法規概要-019","fire-114-1-fire-law-019",114,1,19,"依各類場所消防安全設備設置標準規定，下列何者應就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇設置？",{"A":16,"B":17,"C":18,"D":19},"昇降機械式停車場有停放電動車","室內停車空間在第 1 層樓地板面積 150 平方公尺以上","飛機庫樓地板面積 150 平方公尺以上","發電機室樓地板面積 200 平方公尺以上","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第十八條應設場所表，考的是各項場所的種類與樓地板面積門檻。\n【正解理由】依第十八條所列之應設場所表，該表項目五為「發電機室、變壓器室及其他類似之電器設備場所，樓地板面積在二百平方公尺以上者」，此類場所應就水霧、泡沫、二氧化碳或惰性氣體、鹵化烴或乾粉滅火設備等選擇設置。題目所述發電機室樓地板面積二百平方公尺以上，場所種類與面積門檻均與項目五相符，故選 D。\n【逐項排除】\n(A) 該表項目四所列為「昇降機械式停車場可容納十輛以上者」，門檻是可容納車輛數，表內並未以是否停放電動車為要件。\n(B) 該表項目三對室內停車空間定為「在第一層樓地板面積五百平方公尺以上者」，本項寫一百五十平方公尺，與表列數值不符。\n(C) 該表項目二為「飛機修理廠、飛機庫樓地板面積在二百平方公尺以上者」，本項寫一百五十平方公尺，未達表列門檻。\n(D) 場所種類與二百平方公尺之面積門檻均與項目五相符，本項正確。\n【記憶點】第十八條表：飛機庫、發電機室、鍋爐房廚房、電信機械室都是二百平方公尺；室內停車空間第一層是五百平方公尺；昇降機械式停車場看的是十輛。","第十八條的體例是一張表加本文與附註。本文明定表列場所應就水霧、泡沫、二氧化碳、惰性氣體、鹵化烴或乾粉滅火設備等選擇設置之，但外牆開口面積（常時開放部分）達該層樓地板面積百分之十五以上者，上列除惰性氣體及鹵化烴外之滅火設備得採移動式設置。表格右側依水霧、泡沫、二氧化碳或惰性氣體、鹵化烴、乾粉分欄，各場所以圈記標示得選設之設備，因此同一場所可選的設備種類並不相同。\n表後附註共五點，常單獨命題：一、大量使用火源場所，指最大消費熱量合計在每小時三十萬千卡以上者。二、廚房如設有自動撒水設備，且排油煙管及煙罩設簡易自動滅火裝置時，得不受本表限制。三、停車空間內車輛採一列停放，並能同時通往室外者，得不受本表限制。四、本表項目三及項目四所列應設場所得設置自動撒水設備；項目七所列應設場所得設置預動式自動撒水設備。五、平時有特定或不特定人員使用之中央管理室、防災中心等類似處所，不得設置二氧化碳滅火設備。\n面積門檻最容易混淆的是停車類與飛機類：飛機修理廠、飛機庫為二百平方公尺；汽車修理廠、室內停車空間則分三段，第一層五百平方公尺、地下層或第二層以上二百平方公尺、屋頂設有停車場者三百平方公尺；昇降機械式停車場改以可容納十輛以上計。\n延伸考點方面，第十七條第二項明定應設自動撒水設備之場所，設有水霧、泡沫、二氧化碳、惰性氣體、鹵化烴或乾粉等滅火設備者，在該有效範圍內得免設自動撒水設備；第一百零一條另定供室內停車空間使用之滅火藥劑，以第三種乾粉為限。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-114-1-fire-law-018","依各類場所消防安全設備設置標準規定，下列何者為有效開口之必要條件？",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-114-1-fire-law-020","依建築技術規則建築設計施工編規定，下列敘述何者錯誤？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-114-1-fire-law-017","依消防安全設備及必要檢修項目檢修基準規定，針對性能檢查完成後之滅火器應張貼標示，下列敘述何者錯誤？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-114-1-fire-law-021","某工廠現有建築物及儲存場所之中度危險工作場所樓地板面積合計 2,000 平方公尺，該工廠將擴廠增建一棟一樓層之低度危險工作場所，該增建場所之建築物及儲存場所樓地板面積合計在多少平方公尺以上時，應設置室外消防栓設備？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-114-1-fire-law-016","依消防安全設備及必要檢修項目檢修基準規定，有關火警自動警報設備綜合檢查，下列敘述何者錯誤？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-114-1-fire-law-022","消防設備人員依消防安全設備及必要檢修項目檢修基準規定，執行室內消防栓設備檢修之綜合檢查。下列檢查方法及判定方法，何者錯誤？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-law-019",113,"已領有消防設備人員證書並具有 2 年以上消防實務經驗者，應向主管機關提出申請登記及核發執業執照，始得執行業務。有關消防實務經驗，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-019",112,"依各類場所消防安全設備設置標準之規定，各類場所於增建、改建或變更用途時，下列何項消防安全設備適用增建、改建或變更用途前之標準？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-019",111,"依各類場所消防安全設備設置標準第 12 條之場所用途分類，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-019",110,"有一棟建築物高度超過 60 公尺，其連結送水管採用濕式設計，並設中繼幫浦，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-019",109,"依可燃性高壓氣體儲存場所防爆牆設置基準之規定，防爆牆長度應超過設置方位儲存場所建築物牆面長度，其牆腳與儲存場所建築物之距離不得少於多少公尺？",1785129968614]