[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-114-1-fire-law-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-114-1-消防法規概要-015","fire-114-1-fire-law-015",114,1,15,"依消防安全設備及必要檢修項目檢修基準規定，有關連結送水管性能，水帶箱水帶的檢查及判定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"以目視及手操作確認有無損傷、腐蝕及是否容易接合、分開","製造年份超過 5 年或無法辨識製造年份之水帶，應經水壓試驗合格，始得繼續使用","水帶箱水帶經水壓試驗合格未達 3 年期間，得免進行水壓試驗","判定方法：應無損傷、顯著腐蝕等，且接合、分開應能容易進行，水帶應無破裂、漏水或與消防水帶用接頭脫落之情形","B",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》連結送水管性能檢查中，水帶箱水帶之檢查方法與判定方法。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》連結送水管之性能檢查，水帶及瞄子之檢查方法明定：製造年份超過十年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，並利用相關器具夾住兩末端處，經確認快速接頭已確實連接及水帶內無殘留之空氣後，施以 7kgf\u002Fcm2 以上水壓試驗五分鐘合格，始得繼續使用。題目寫成製造年份超過 5 年，與原文之十年不符，故選 B 為錯誤敘述。\n【逐項排除】\n(A) 「以目視及手操作確認有無損傷、腐蝕及是否容易接合、分開」即該項檢查方法所定之作法，敘述正確。\n(B) 年限應為製造年份超過十年，非 5 年，故為錯誤敘述。\n(C) 該項但書明定「已經水壓試驗合格未達 3 年者，不在此限」，敘述正確。\n(D) 判定方法明定「應無損傷、顯著腐蝕等」及「接合、分開應能容易進行，水帶應無破裂、漏水或與消防水帶用接頭脫落之情形」，敘述正確。\n【記憶點】製造年份超過十年或無法辨識者才做水壓試驗，已試驗合格未達三年期間免再試。","消防水帶的水壓試驗規定散在《消防安全設備及必要檢修項目檢修基準》多個設備章節，體例高度一致，把它們並列起來記最有效率。連結送水管之性能檢查、室內消防栓設備第一種消防栓之性能檢查、泡沫滅火設備泡沫消防栓箱等之性能檢查，三者皆定製造年份超過十年或無法辨識製造年份之水帶，須施以 7kgf\u002Fcm2 以上水壓試驗五分鐘合格始得繼續使用；室外消防栓設備與射水設備之室外消防栓箱等，同樣是製造年份超過十年或無法辨識者，試驗壓力則為 6kgf\u002Fcm2 以上、時間同為五分鐘。這五處的但書寫法相同：已經水壓試驗合格未達三年者，不在此限。「超過十年或無法辨識才試、三年內免再試」這組條件在這五處通用，換的是試驗壓力值。\n試驗手法的細節也常被拿來改字命題。原文要求將消防水帶兩端之快速接頭連接於耐水壓試驗機，並利用相關器具夾住消防水帶兩末端處，且須先確認快速接頭已確實連接、快速接頭至被器具夾住處之部分水帶內無殘留之空氣，才能施壓。這段程序文字本身就是必背內容，命題常從「幾年、幾 kgf\u002Fcm2、幾分鐘」與「施壓前要確認什麼」下手。\n再來要分清外觀檢查與性能檢查的分工。連結送水管之外觀檢查就水帶箱等所定者，是以目視及開關操作確認水帶箱有無變形、損傷及箱門能否確實開關，周圍有無檢查上及使用上之障礙、「水帶箱」標示設置是否適當，以及水帶及瞄子有無變形、損傷並依所需之數量設置於規定位置；至於是否容易接合分開、有無破裂漏水、要不要做水壓試驗，則落在性能檢查。本題四個選項寫的都是性能檢查的內容。\n判定方法的用字同樣要精讀。連結送水管性能檢查對水帶及瞄子的判定方法寫的是「應無損傷、顯著腐蝕等」，多了「顯著」二字；接合、分開應能容易進行，水帶應無破裂、漏水或與消防水帶用接頭脫落之情形。範圍上要記住：連結送水管的性能檢查列有送水口、水帶箱等、電動機之控制裝置、啟動裝置、呼水裝置、中繼水箱等、配管七個項目，「出水口之開關閥」不是獨立項目，而是「水帶箱等」項下與水帶及瞄子並列的第二個子項，其檢查方法為以手操作確認是否容易開、關，判定方法為開、關操作應能容易進行。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-114-1-fire-law-014","依消防安全設備檢修及申報辦法規定，檢修人員或檢修機構完成消防安全設備檢修後，附加檢修完成標示，下列敘述何者錯誤？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-114-1-fire-law-016","依消防安全設備及必要檢修項目檢修基準規定，有關火警自動警報設備綜合檢查，下列敘述何者錯誤？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-114-1-fire-law-013","消防設備人員執行消防安全設備之設計、監造、測試及檢修業務，由消防安全設備設計人員依滅火設備、警報設備、避難逃生設備、消防搶救上之必要設備及其他經中央主管機關認定之消防安全設備等依序繪製，標示記號，並依消防或建築等圖示範例註記，上述製作之文書為下列何者？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-114-1-fire-law-017","依消防安全設備及必要檢修項目檢修基準規定，針對性能檢查完成後之滅火器應張貼標示，下列敘述何者錯誤？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-114-1-fire-law-012","消防設備人員辦理各項業務，應遵守誠信原則，違反下列何項行為，可予以警告、申誡、停止執行業務 2 個月以上 2 年以下或廢止執業執照之懲戒處分：",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-114-1-fire-law-018","依各類場所消防安全設備設置標準規定，下列何者為有效開口之必要條件？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-fire-law-015",113,"依消防法施行細則規定，施工中消防防護計畫不包括下列那一事項？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-015",112,"依防火牆及防火水幕設置基準之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-015",111,"某一百貨商場為地上八層、地下三層，總樓地板面積 3 千平方公尺。其火警自動警報設備之鳴動方式何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-015",110,"某自助洗衣店使用液化石油氣作為動力來源，其容器串接使用量為 100 公斤，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定之安全設施，下列何者應設置？①滅火器 ②氣體漏氣警報器 ③自動緊急遮斷裝置 ④標示板標示緊急聯絡人姓名及電話",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-015",109,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法，有關販賣場所之規定，下列敘述何者正確？",1785129968593]