[{"data":1,"prerenderedAt":74},["ShallowReactive",2],{"q-fire-113-1-water-chemical-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":53,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-040","fire-113-1-water-chemical-040",113,1,40,"有關射水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"A":16,"B":17,"C":18,"D":19},"緊急電源應為發電機設備或蓄電池設備，其供電容量應供其有效動作 25 分鐘以上","消防栓、射水槍與建築物一樓外牆各部分之水平距離不得超過 40 公尺","呼水裝置應確保 100 公升以上之水量","瞄子前端放水壓力分別應在每平方公分 3.5 公斤以上每平方公分 6 公斤以下，且放水量在每分鐘 450 公升以上","A",null,[],false,"本題考點：射水設備的測試方法及判定要領，四個選項分別對應緊急電源、水平距離、呼水裝置水量與放水壓力放水量。\n【正解理由】依《消防安全設備測試報告書測試方法及判定要領》室外消防栓設備之外觀試驗，緊急電源種類的判定要領為「應為發電機設備或蓄電池設備，其供電容量應供其有效動作三十分鐘以上」；射水設備所用之室外消防栓比照同一體例，且《各類場所消防安全設備設置標準》第 38 條對室內消防栓設備緊急電源也是三十分鐘。選項所寫二十五分鐘與之不同，故選 A。\n【逐項排除】\n(A) 二十五分鐘與判定要領所定之三十分鐘不符，為本題答案。\n(B) 與建築物一樓外牆各部分之水平距離不得超過四十公尺，和《設置標準》第 40 條第一款室外消防栓之四十公尺以下相符。\n(C) 呼水裝置確保一百公升以上之水量，與加壓送水裝置之判定要領所定相同，非本題所指之不同者。\n(D) 放水壓力每平方公分三點五公斤以上、放水量每分鐘四百五十公升以上，與《設置標準》第 231 條第三款及檢修基準射水設備綜合檢查之判定值一致；其每平方公分六公斤之上限亦為判定要領所載。\n【記憶點】射水設備緊急電源記三十分鐘，放水壓力三點五公斤以上、放水量四百五十公升以上。","射水設備的定義在《各類場所消防安全設備設置標準》第 197 條第二項第二款：指固定式射水槍、移動式射水槍或室外消防栓，與冷卻撒水設備同屬可燃性高壓氣體製造場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之防護設備。第 231 條就其設置列四款：室外消防栓應設置於屋外且具備消防水帶箱；箱內配置瞄子、開關把手及口徑六十三毫米、長度二十公尺消防水帶二條；全部射水設備同時使用時，各放水壓力在每平方公分三點五公斤以上或 0.35MPa 以上、放水量在每分鐘四百五十公升以上，但全部數量超過二支時以同時使用二支計算；水源容量在二具射水設備同時放水三十分鐘之水量以上。\n檢修面見《消防安全設備及必要檢修項目檢修基準》射水設備之綜合檢查：切換成緊急電源供電狀態，操作直接操作部及遠隔操作部啟動裝置以確認各項性能；放水試驗以全部射水設備進行，超過二具時選擇最遠最高處之二具；量測時把壓力表之進水口放在瞄子前端瞄子口徑二分之一距離處或射水槍前端口徑二分之一距離處讀值；放水量以 Ｑ＝0.653Ｄ²√Ｐ 計算，其中 Ｑ 為放水量、Ｄ 為口徑、Ｐ 為放水壓力。判定值為放水壓力 3.5kgf／cm² 以上、每具放水量 450l／min 以上，恰與第 231 條第三款相同。\n緊急電源的分鐘數是本題的分水嶺，也是本科最容易記混的一組數字。《消防安全設備測試報告書測試方法及判定要領》室內消防栓設備與室外消防栓設備的外觀試驗，緊急電源種類欄都寫「應為發電機設備或蓄電池設備，其供電容量應供其有效動作三十分鐘以上」，與《設置標準》第 38 條相同。另一組數字出自第四編公共危險物品等場所：第 209 條室內消防栓、第 210 條室外消防栓、第 211 條自動撒水、第 212 條水霧的緊急電源供電容量均為四十五分鐘以上。三十分鐘與四十五分鐘分屬不同編別、不同適用場所，命題時最常拿來互換；另可一併記住第 95 條全區及局部放射方式緊急電源為一小時以上、第 128 條火警自動警報設備為十分鐘以上、第 155 條標示設備為二十分鐘以上。",true,[28,32,37,41,45,49],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-039","某一工廠儲存鹼金屬過氧化物，滅火藥劑適用下列何者？",39,{"webId":33,"stem":34,"number":35,"year":36,"session":12},"fire-114-1-water-chemical-004","依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",4,114,{"webId":38,"stem":39,"number":40,"year":11,"session":12},"fire-113-1-water-chemical-038","依各類場所消防安全設備設置標準之規定，下列何場所得免設滅火器？",38,{"webId":42,"stem":43,"number":12,"year":44,"session":12},"fire-106-1-water-chemical-001","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列何者錯誤？",106,{"webId":46,"stem":47,"number":48,"year":11,"session":12},"fire-113-1-water-chemical-037","加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至多少 Mpa 以下？",37,{"webId":50,"stem":51,"number":52,"year":44,"session":12},"fire-106-1-water-chemical-002","依各類場所消防安全設備設置標準，下列何種場所不需設置滅火器？",2,[54,58,62,66,70],{"webId":55,"year":56,"stem":57,"number":13},"fire-112-1-water-chemical-040",112,"有關公共危險物品場所設置自動撒水設備規定，下列敘述何者正確？",{"webId":59,"year":60,"stem":61,"number":13},"fire-111-1-water-chemical-040",111,"二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",{"webId":63,"year":64,"stem":65,"number":13},"fire-110-1-water-chemical-040",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之供第四類公共危險物品之顯著滅火困難場所之加壓送水裝置，啟動後 X 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 Y 公尺以下，但設有保壓措施者不在此限。X、Y 分別為何？",{"webId":67,"year":68,"stem":69,"number":13},"fire-109-1-water-chemical-040",109,"儲槽規定設置補助泡沫消防栓時，下列敘述何者錯誤？",{"webId":71,"year":72,"stem":73,"number":13},"fire-108-1-water-chemical-040",108,"電動機之使用應符合之相關規定，下列何者錯誤？",1785129971773]