[{"data":1,"prerenderedAt":74},["ShallowReactive",2],{"q-fire-113-1-water-chemical-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":53,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-038","fire-113-1-water-chemical-038",113,1,38,"依各類場所消防安全設備設置標準之規定，下列何場所得免設滅火器？",{"A":16,"B":17,"C":18,"D":19},"早期療育機構樓地板面積 80 m2","日間型精神復健機構樓地板面積 80 m2","資訊休閒場所 180 m2","老人文康機構 180 m2","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 14 條應設滅火器之場所，關鍵在第 12 條甲類與乙類場所的目次歸屬。\n【正解理由】第 14 條第一款所列之甲類場所、地下建築物、幼兒園，條文未附任何面積條件；第二款則以「總樓地板面積在一百五十平方公尺以上之乙、丙、丁類場所」為門檻。日間型精神復健機構列於第 12 條第二款第六目，屬乙類場所，題示八十平方公尺未達一百五十平方公尺，不落入第 14 條第二款，故選 B。\n【逐項排除】\n(A) 早期療育機構列於第 12 條第一款第六目之「兒童及少年福利機構（限托嬰中心、早期療育機構、有收容未滿二歲兒童之安置及教養機構）」，屬甲類場所，依第 14 條第一款無面積下限，八十平方公尺仍應設。\n(B) 屬乙類場所且未達一百五十平方公尺，不在第 14 條第二款之列，為本題答案。\n(C) 資訊休閒場所列於第 12 條第一款第二目，屬甲類場所，同樣依第一款應設，與一百八十平方公尺無關。\n(D) 老人文康機構列於第 12 條第二款第六目，屬乙類場所，一百八十平方公尺已達第二款之一百五十平方公尺門檻，應設。\n【記憶點】第 14 條第一款的甲類場所不附面積條件，第二款的乙、丙、丁類場所以一百五十平方公尺起算，第三款以下另就地下層、無開口樓層、電氣設備及火源處所各定條件。","第 14 條共五款：第一款甲類場所、地下建築物、幼兒園；第二款總樓地板面積在一百五十平方公尺以上之乙、丙、丁類場所；第三款設於地下層或無開口樓層，且樓地板面積在五十平方公尺以上之各類場所；第四款設有放映室或變壓器、配電盤及其他類似電氣設備之各類場所；第五款設有鍋爐房、廚房等大量使用火源之各類場所。\n真正的難點在第 12 條的目次歸屬。第一款第六目（甲類）收的是醫院、療養院、榮譽國民之家、長期照顧服務機構（限機構住宿式、社區式之建築物使用類組非屬 H-2 之日間照顧、團體家屋及小規模多機能）、老人福利機構（限長期照護型、養護型、失智照顧型之長期照顧機構、安養機構）、兒童及少年福利機構（限托嬰中心、早期療育機構、有收容未滿二歲兒童之安置及教養機構）、護理機構（限一般護理之家、精神護理之家、產後護理機構）、身心障礙福利機構（限供住宿養護、日間服務、臨時及短期照顧者）、身心障礙者職業訓練機構（限提供住宿或使用特殊機具者）、啟明、啟智、啟聰等特殊學校。第二款第六目（乙類）收的則是辦公室、靶場、診所、長期照顧服務機構（限社區式之建築物使用類組屬 H-2 之日間照顧、團體家屋及小規模多機能）、日間型精神復健機構、兒童及少年心理輔導或家庭諮詢機構、身心障礙者就業服務機構、老人文康機構，以及前款第六目以外之老人福利機構及身心障礙福利機構。\n兩個第六目的機構名稱高度重疊，分界依據就寫在括號裡：長期照顧服務機構看是機構住宿式，還是社區式而建築物使用類組屬不屬於 H-2；兒童及少年福利機構看是不是托嬰中心、早期療育機構或收容未滿二歲兒童之安置及教養機構；身心障礙福利機構看有沒有供住宿養護、日間服務、臨時及短期照顧；身心障礙者職業訓練機構看有沒有提供住宿或使用特殊機具。括號一旦漏讀，甲乙兩類就分不開。\n數量核算另看第 31 條：供第 12 條第一款及第五款使用之場所，各層樓地板面積每一百平方公尺（含未滿）有一滅火效能值；供第二款至第四款使用之場所每二百平方公尺（含未滿）有一滅火效能值；鍋爐房、廚房等大量使用火源之處所每二十五平方公尺（含未滿）有一滅火效能值。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-037","加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至多少 Mpa 以下？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-039","某一工廠儲存鹼金屬過氧化物，滅火藥劑適用下列何者？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-036","有關室外消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-040","有關射水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-035","惰性氣體進行高壓式全區放射綜合檢查，下列敘述何者錯誤？",35,{"webId":49,"stem":50,"number":51,"year":52,"session":12},"fire-114-1-water-chemical-004","依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",4,114,[54,58,62,66,70],{"webId":55,"year":56,"stem":57,"number":13},"fire-112-1-water-chemical-038",112,"依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",{"webId":59,"year":60,"stem":61,"number":13},"fire-111-1-water-chemical-038",111,"一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",{"webId":63,"year":64,"stem":65,"number":13},"fire-110-1-water-chemical-038",110,"依消防安全設備及必要檢修項目檢修基準，海龍滅火設備全區放射方式檢查方法，若以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之多少%核算？",{"webId":67,"year":68,"stem":69,"number":13},"fire-109-1-water-chemical-038",109,"消防專用蓄水池之設置規定，下列何者正確？",{"webId":71,"year":72,"stem":73,"number":13},"fire-108-1-water-chemical-038",108,"依各類場所消防安全設備檢修及申報作業基準，有關乾粉滅火藥劑判定方法，乾粉藥劑不得有雜質、變質、固化等情形，且以手輕握搓揉，並自地面上高度多少公分處使其落下，應呈粉狀？",1785129971754]