[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-035":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-035","fire-113-1-water-chemical-035",113,1,35,"惰性氣體進行高壓式全區放射綜合檢查，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"IG-55 氣體滅火藥劑每公斤核算空氣量或氮氣量為 100 公升","二氧化碳氣體滅火藥劑每公斤核算空氣量或氮氣量為 55 公升","IG-541 氣體滅火藥劑每公斤核算空氣量或氮氣量為 100 公升","氮氣滅火藥劑每公斤核算空氣量或氮氣量為 55 公升","D",null,[],false,"本題考點：惰性氣體滅火設備高壓式全區放射方式綜合檢查時，各滅火藥劑每公斤所核算的空氣量或氮氣量。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》惰性氣體滅火設備之綜合檢查，高壓式者以空氣或氮氣進行放射試驗，所需空氣量或氮氣量應就放射區域應設滅火藥劑量之百分之十核算，每公斤依表所列公升數之比例核算：二氧化碳五十五公升、氮氣一百公升、IG-55 一百公升、IG-541 一百公升，每次試驗最多放出五支。題目把氮氣寫成每公斤五十五公升，與該表不符，故選 D。\n【逐項排除】\n(A) IG-55 每公斤核算之空氣量或氮氣量為一百公升，與表列一致，敘述正確。\n(B) 二氧化碳每公斤核算之空氣量或氮氣量為五十五公升，與表列一致，敘述正確。\n(C) IG-541 每公斤核算之空氣量或氮氣量為一百公升，與表列一致，敘述正確。\n(D) 氮氣每公斤核算之空氣量或氮氣量為一百公升，本項寫成五十五公升，為錯誤敘述。\n【記憶點】惰性氣體核算量只有二氧化碳是五十五公升，氮氣與 IG 系列三者一律一百公升。","惰性氣體滅火設備章把二氧化碳與 IG 系列放在同一章，因此綜合檢查的核算表同時列出四種藥劑，而四個數字裡只有二氧化碳與眾不同，這正是命題者換數字的著力點。之所以只有一個異數，可由藥劑本身理解：二氧化碳以液化狀態儲存，單位重量所佔的氣體體積與氮氣、IG-55、IG-541 這些以高壓氣態儲存的惰性氣體不同，因此換算比例自成一格。\n綜合檢查的整體程序與鹵化烴章同一個骨架。先將電源切換為緊急電源狀態，再依系統數量抽樣：抽樣分配表以設置套數對應第一年至第十年的抽測套數，設置數量超過二十一套者依其比例類推分配；抽測之系統放射區域在二區以上時，應至少擇一放射區域實施放射試驗，並於滅火藥劑儲存容器標示放射日期。高壓式的檢查方法即本題所考的替代氣體核算，並附三項注意事項：充填空氣或氮氣之試驗用氣體容器壓力，應與該滅火設備儲存容器之充填壓力大約相等；使用啟動用氣體容器之設備者，應準備與設置數量相同之氣體容器數；應準備必要數量供塞住集合管部或容器閥部及操作管部之帽蓋或塞子。檢查前的準備包括暫時切斷控制盤等電源設備、將自儲存容器取下之容器閥開放裝置及操作管連接裝設在試驗用氣體容器上、取下連接管並用帽蓋等塞住集合管、塞住放射用以外之操作管、確認其餘部分處於平時設置狀況、控制盤等設備電源置於開的位置。啟動操作則二擇一：手動式者操作手動啟動裝置使其啟動，自動式者將自動、手動切換裝置切換至自動位置，使探測器動作或使受信機、控制盤探測器回路之端子短路而啟動。\n低壓式另有一套：應進行放射試驗，其放射試驗所需之藥劑量為該放射區域所設滅火藥劑量之百分之十以上，或使用四十公升氮氣五瓶以上作為替代藥劑放射。至於防護區域本身的把關，《設置標準》第九十六條之一規定惰性氣體滅火設備之防護區域竣工時應做防護區域完整性測試，十分鐘內之氣體洩漏量使滅火藥劑維持在設計濃度百分之八十五以上者為合格。竣工測試看密閉性、綜合檢查看系統動作，兩者時機與目的不同，答題時先看題幹問的是竣工還是定期檢修。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-034","蓄壓式鹵化烴滅火藥劑儲存容器使用水平液面計之方法進行滅火藥劑量性能檢查，下列敘述何者錯誤？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-036","有關室外消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-033","某加油站附設加氣站，其滅火器設置應符合之規定，下列敘述何者錯誤？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-037","加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至多少 Mpa 以下？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-032","某電信機房使用二氧化碳滅火系統，其配管規定，下列敘述何者錯誤？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-038","依各類場所消防安全設備設置標準之規定，下列何場所得免設滅火器？",38,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-035",112,"二氧化碳滅火設備之滅火藥劑儲存容器，其設置規定下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-035",111,"二氧化碳滅火設備採全區放射，其噴頭設置規定下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-035",110,"依消防安全設備及必要檢修項目檢修基準，製造日期超過 10 年或無法辨識製造日期之何種滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-035",109,"廚房等大量使用火源之處所，多少樓地板面積需有一滅火效能值？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-035",108,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備呼水裝置之減水警報裝置，當水量減少至多少前應發出警報？",1785129971738]