[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-034","fire-113-1-water-chemical-034",113,1,34,"蓄壓式鹵化烴滅火藥劑儲存容器使用水平液面計之方法進行滅火藥劑量性能檢查，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"插入水平液面計電源開關，檢查其電壓值","使容器維持平常之狀態，將容器置於液面計探針與放射源之間","緩緩使液面計檢出部左右方向移動，當發現儀表指針振動差異較大時，由該位置即可求出自容器底部起之藥劑存量高度","液面高度與藥劑量之換算，應使用專用之換算尺為之","C",null,[],false,"本題考點：蓄壓式鹵化烴滅火藥劑儲存容器以水平液面計進行滅火藥劑量性能檢查時的操作步驟。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》鹵化烴滅火設備之性能檢查，使用水平液面計之方法載明：插入水平液面計電源開關並檢查其電壓值；使容器維持平常之狀態，將容器置於液面計探針與放射源之間；緩緩使液面計檢出部上下方向移動，當發現儀表指針振動差異較大時，由該位置即可求出自容器底部起之藥劑存量高度；液面高度與藥劑量之換算，應使用專用之換算尺為之。題目把檢出部的移動方向寫成左右方向，與檢查方法不符，故選 C。\n【逐項排除】\n(A) 插入水平液面計電源開關並檢查其電壓值，是該檢查方法的第一個步驟，敘述正確。\n(B) 使容器維持平常之狀態、將容器置於液面計探針與放射源之間，與檢查方法一致，敘述正確。\n(C) 檢出部應為上下方向移動，本項寫成左右方向移動，為錯誤敘述。\n(D) 液面高度與藥劑量之換算應使用專用之換算尺，與檢查方法一致，敘述正確。\n【記憶點】水平液面計四步驟：先看電壓、容器夾在探針與放射源之間、檢出部上下移動找指針振動、再用專用換算尺換算。","水平液面計的原理是以放射源（鈷六十）發出的射線穿透容器，液面上下兩側對射線的衰減程度不同，因此當檢出部移動到液面高度時，儀表指針的振動會出現明顯差異，該位置即為自容器底部起的藥劑存量高度；由於容器直徑固定，高度再經專用換算尺即可換為藥劑重量。理解了這個原理，就能記住檢出部必須沿容器軸向上下移動——左右移動只會在同一高度掃過，找不到液面。\n《檢修基準》對蓄壓式鹵化烴滅火藥劑儲存容器的藥劑量檢查給了四種方法。一是使用台秤測定計：將裝設在容器閥之容器閥開放裝置、連接管、操作管及容器固定器具取下，把容器置於台秤上測定其重量至小數點第一位，藥劑量為測定值扣除容器閥及容器重量後所得之值。二是本題的水平液面計法。三是使用鋼瓶液面計：打開保護蓋緩慢抽出表尺，當表尺被鋼瓶內浮球之磁性吸引而停頓時讀取表尺刻度，再對照各廠商提供之專用換算表讀取藥劑重量，並需考慮溫度變化造成之影響。四是以其他原廠技術手冊規範之方式檢測藥劑量。\n判定方法只有一句但很關鍵：將藥劑量之測定結果與重量表、圖面明細表或原廠技術手冊規範核對，其差值應在充填值百分之十以下。注意事項分兩組。以水平液面計測定時：不得任意卸取放射線源（鈷六十），萬一有異常時應即時連絡專業處理單位；鈷六十有效使用年限約為三年，如已超過時應即時連絡專業單位處理或更換；使用壓力表者，應先確認容器內壓為規定之壓力值。共同事項則包括：因容器重量頗重（約一百五十公斤），傾倒或操作時應加以注意；測量後應將容器號碼、充填量記載於檢查表上；當滅火藥劑量或容器內壓減少時，應迅即進行調查並採取必要之措施；使用具放射源者，應取得主管機關之許可登記。\n本題型的命題手法很固定：把檢查方法的某一個動作換掉一個字（上下改左右、探針與放射源之間改成其他相對位置），或把判定方法的百分之十改成別的數字。準備時逐步驟默背動作順序，比記憶結論更有效。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-033","某加油站附設加氣站，其滅火器設置應符合之規定，下列敘述何者錯誤？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-035","惰性氣體進行高壓式全區放射綜合檢查，下列敘述何者錯誤？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-032","某電信機房使用二氧化碳滅火系統，其配管規定，下列敘述何者錯誤？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-036","有關室外消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-031","依各類場所消防安全設備設置標準規定，二氧化碳滅火設備使用氣體啟動者，下列敘述何者錯誤？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-037","加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至多少 Mpa 以下？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-034",112,"有關自動撒水設備免設撒水頭處所得設置補助撒水栓之規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-034",111,"第五種滅火設備除滅火器外之其他設備，有關滅火效能值核算之規定，下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-034",110,"依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-034",109,"乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-034",108,"依各類場所消防安全設備設置標準之規定，水霧滅火設備之加壓送水裝置使用消防幫浦時，用於防護電氣設備者，每一個水霧噴頭壓力依規定均應達到多少以上？",1785129971734]