[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-031","fire-113-1-water-chemical-031",113,1,31,"依各類場所消防安全設備設置標準規定，二氧化碳滅火設備使用氣體啟動者，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"啟動用氣體容器能耐每平方公分 250 公斤或 25 MPa 之壓力","啟動用氣體容器之內容積應有 1 公升以上","儲存之二氧化碳重量在 0.5 公斤以上","充填比在 1.5 以上","C",null,[],false,"本題考點：二氧化碳滅火設備使用氣體啟動時，啟動用氣體容器的耐壓、內容積、二氧化碳重量與充填比四項數值。\n【正解理由】依《各類場所消防安全設備設置標準》第八十八條第二款，啟動用氣體容器之內容積應有一公升以上，其所儲存之二氧化碳重量在零點六公斤以上，且其充填比在一點五以上。題目把重量寫成零點五公斤以上，與本款所定之零點六公斤不符，故選 C。\n【逐項排除】\n(A) 第八十八條第一款明定啟動用氣體容器能耐每平方公分二百五十公斤或 25MPa 之壓力，與本項一致，敘述正確。\n(B) 內容積應有一公升以上，是第八十八條第二款前段的文字，敘述正確。\n(C) 所儲存之二氧化碳重量應在零點六公斤以上，本項寫零點五公斤，數值低於條文所定，為錯誤敘述。\n(D) 充填比在一點五以上，是第八十八條第二款後段的文字，敘述正確。\n【記憶點】啟動用氣體容器四個數：耐壓二百五十公斤、內容積一公升、二氧化碳零點六公斤、充填比一點五。","第八十八條全條只有四款，是二氧化碳滅火設備裡最容易整條背下來的條文之一。除本題所考的第一款耐壓與第二款三項數值外，第三款規定啟動用氣體容器之安全裝置及容器閥應符合 CNS 一一一七六規定，第四款規定啟動用氣體容器不得兼供防護區域之自動關閉裝置使用——第四款是常被忽略的申論素材，它把啟動氣源與關閉開口部的氣源分開，避免同一支容器同時擔兩個任務。\n容易與本條混淆的是第八十七條的滅火藥劑儲存容器。第八十七條第一款的充填比為高壓式一點五以上一點九以下、低壓式一點一以上一點四以下，並在該條第二項把充填比定義為「容器內容積（公升）與液化氣體重量（公斤）之比值」；第八十八條第二款的充填比則只寫「在一點五以上」而無上限。兩個一點五分屬不同容器，作答時要先看題幹問的是啟動用氣體容器還是滅火藥劑儲存容器。第八十七條其餘各款也常入題：儲存場所應置於防護區域外、溫度攝氏四十度以下且溫度變化較少處、不得置於有日光曝曬或雨水淋濕之處；低壓式儲存容器應設液面計、壓力表及壓力警報裝置，壓力在每平方公分二十三公斤以上或 2.3MPa 以上、或每平方公分十九公斤以下或 1.9MPa 以下時發出警報，並應設置使容器內部溫度維持於攝氏零下二十度以上、零下十八度以下之自動冷凍機；容器閥使用電磁閥直接開啟時，同時開啟之儲存容器數在七支以上者，該儲存容器應設二個以上之電磁閥。\n啟動的另一半在第九十一條：手動啟動裝置應設於能看清區域內部且操作後能容易退避之防護區域外，每一防護區域或防護對象裝設一套，操作部設在距樓地板面高度零點八公尺以上一點五公尺以下，外殼漆紅色，以電力啟動者裝置電源表示燈，操作開關或拉桿於操作時同時發出警報音響且設有透明塑膠製之有效保護裝置，並在近旁標示所防護區域名稱、操作方法及安全上應注意事項；自動啟動裝置則與火警探測器感應連動啟動。再配合第九十三條全區放射方式之安全裝置——啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟設有二十秒以上之遲延裝置，並於防護區域出入口等易於辨認處所設置放射表示燈——氣體啟動這一串就完整了。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-030","鹵化烴滅火設備全區放射綜合檢查時，檢查方法、判定方法及注意事項，下列何者錯誤？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-032","某電信機房使用二氧化碳滅火系統，其配管規定，下列敘述何者錯誤？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-029","有關流水檢知裝置之構造，依據流水檢知裝置認可基準規定，下列敘述何者錯誤？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-033","某加油站附設加氣站，其滅火器設置應符合之規定，下列敘述何者錯誤？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-028","下列場所之消防安全設備設置何者錯誤？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-034","蓄壓式鹵化烴滅火藥劑儲存容器使用水平液面計之方法進行滅火藥劑量性能檢查，下列敘述何者錯誤？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-031",112,"消防幫浦之性能規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-031",111,"應設置消防專用蓄水池之場所規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-031",110,"公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-031",109,"使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-031",108,"第四種乾粉滅火藥劑儲存容器，有關充填比之規定，下列何者正確？",1785129971709]