[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-029","fire-113-1-water-chemical-029",113,1,29,"有關流水檢知裝置之構造，依據流水檢知裝置認可基準規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"開關等電氣組件，應作防蝕處理","用於啟動加壓送水裝置者，應裝配逆止閥","不得有堆積物致妨礙其性能之構造","本體及其他零件應能容易檢查換修","A",null,[],false,"本題考點：流水檢知裝置的構造要求，依據是中央主管機關公告的《流水檢知裝置認可基準》，屬認可基準層級的產品規範，與《各類場所消防安全設備設置標準》的設置規定分屬兩套文件。\n【正解理由】依《流水檢知裝置認可基準》關於構造之規定，本體及其他零件應能容易檢查換修、不得有堆積物致妨礙其性能之構造，用於啟動加壓送水裝置者並應裝配逆止閥；至於開關等電氣組件，該基準所要求的處理方式並非防蝕處理，因此本題四項敘述中，與該認可基準不符者為電氣組件應作防蝕處理這一項，故選 A。\n【逐項排除】\n(A) 開關等電氣組件應作防蝕處理一語，與該認可基準對電氣組件所定之處理要求不符，為本題應挑出的錯誤敘述。\n(B) 用於啟動加壓送水裝置者應裝配逆止閥，是該認可基準構造規定所列的項目，敘述正確。\n(C) 不得有堆積物致妨礙其性能之構造，屬該認可基準對構造的要求，避免異物堆積影響閥的動作，敘述正確。\n(D) 本體及其他零件應能容易檢查換修，是產品認可基準對可維修性的一貫要求，敘述正確。\n【記憶點】流水檢知裝置的構造三要件記「好檢修、不積物、啟動加壓送水裝置要有逆止閥」；電氣組件的處理要求不是防蝕。","流水檢知裝置是自動撒水設備的心臟閥件，負責偵知二次側配管的水流並發出訊號、啟動警報與加壓送水裝置，依動作型式分為濕式、乾式與預動式三類。它在法制上有兩層規範：產品面由中央主管機關公告的《流水檢知裝置認可基準》管，內容是構造、材質、性能與試驗方法，體例採壹貳參與章節而無條號；設置與檢修面則分別由《設置標準》與《消防安全設備及必要檢修項目檢修基準》規範。本題題幹逐字寫明「依據流水檢知裝置認可基準規定」，就是要考生辨識依據來自認可基準而非設置標準，其逐字文字以中央主管機關公告之該認可基準內容為準。\n與流水檢知裝置有關的設置規定散在《設置標準》數條：第四十四條規定密閉乾式或預動式之流水檢知裝置二次側配管，應施予鍍鋅等防腐蝕處理（一齊開放閥二次側配管亦同），並為有效排水而定支管每十公尺傾斜四公分、主管每十公尺傾斜二公分，且於明顯易見處設排水閥並標明排水閥字樣；第五十六條規定使用密閉式撒水頭之自動撒水設備末端查驗閥，管徑在二十五毫米以上，依各流水檢知裝置配管系統配置，並接裝在建築物各層放水壓力最低之最遠支管末端，一次側設壓力表、二次側設有與撒水頭同等放水性能之限流孔，距離地板面高度在二點一公尺以下並附排水管裝置。\n檢修面則見於《消防安全設備及必要檢修項目檢修基準》自動撒水設備之外觀檢查，把自動警報逆止閥及流水檢知裝置拆成閥本體、延遲裝置、壓力開關三個檢查對象：閥本體要以目視確認本體、附屬閥類、配管及壓力表有無漏水、變形，確認壓力表指示值是否正常，並確認「常時開」或「常時關」之標示及開關位置是否正常；延遲裝置與壓力開關則確認有無變形、損傷、顯著腐蝕。把認可基準（產品要怎麼做）、設置標準（現場要怎麼裝）、檢修基準（平時要怎麼查）三層分開記，是這一類題目最不容易被混淆的讀法。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-028","下列場所之消防安全設備設置何者錯誤？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-030","鹵化烴滅火設備全區放射綜合檢查時，檢查方法、判定方法及注意事項，下列何者錯誤？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-027","公共危險物品等場所設置之室內消防栓設備，應符合下列何者規定？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-031","依各類場所消防安全設備設置標準規定，二氧化碳滅火設備使用氣體啟動者，下列敘述何者錯誤？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-026","設於外浮頂式儲槽之泡沫放出口為？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-032","某電信機房使用二氧化碳滅火系統，其配管規定，下列敘述何者錯誤？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-029",112,"有關泡沫滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-029",111,"變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-029",110,"公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-029",109,"泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-029",108,"有一室內停車空間，其防護區為 25 m × 16 m × 4 m，未設自動關閉裝置之開口部面積為 10 m2，擬設置全區放射式乾粉滅火設備，試問所需法定滅火藥劑量最少為多少公斤？",1785129971701]