[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-028","fire-113-1-water-chemical-028",113,1,28,"下列場所之消防安全設備設置何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"屋頂直昇機停機場（坪）設置乾粉滅火系統","飛機修理廠設置二氧化碳滅火設備","發電機室設置二氧化碳滅火設備","電信機械室設置乾粉滅火系統","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第十八條的應設場所表——哪些場所應就水霧、泡沫、二氧化碳或惰性氣體、鹵化烴、乾粉滅火設備選擇設置。\n【正解理由】依《各類場所消防安全設備設置標準》第十八條之表，項目二為「飛機修理廠、飛機庫樓地板面積在二百平方公尺以上者」，該列標記於泡沫、乾粉二欄，二氧化碳或惰性氣體欄未標記，故飛機修理廠不得就二氧化碳滅火設備選擇設置。本題要挑出設置錯誤者，故選 B。\n【逐項排除】\n(A) 屋頂直昇機停機場（坪）為表列項目一，該列標記於泡沫、乾粉二欄，得選擇設置乾粉滅火設備，敘述正確。\n(B) 飛機修理廠所屬之項目二，二氧化碳或惰性氣體欄未標記，設置二氧化碳滅火設備於法無據，本項錯誤。\n(C) 發電機室屬項目五「發電機室、變壓器室及其他類似之電器設備場所，樓地板面積在二百平方公尺以上者」，該列標記於水霧、二氧化碳或惰性氣體、鹵化烴、乾粉四欄，得設二氧化碳滅火設備。\n(D) 電信機械室屬項目七「電信機械室、電腦室或總機室及其他類似場所，樓地板面積在二百平方公尺以上者」，該列標記於二氧化碳或惰性氣體、鹵化烴、乾粉三欄，得設乾粉滅火設備。\n【記憶點】第十八條表七項：停機坪、飛機修理廠標泡沫與乾粉；汽車修理廠、室內停車空間、昇降機械式停車場五欄全標（含二氧化碳）；發電機室標水霧與三種氣體系統欄；鍋爐房、廚房、電信機械室標二氧化碳或惰性氣體、鹵化烴、乾粉。","第十八條位於《設置標準》第二編【消防設計】，讀法有兩層：先看場所落在表列哪一個項目，再看該列在哪些欄位標有記號，標記的欄位就是得選擇設置的種類，欄位為水霧、泡沫、二氧化碳或惰性氣體、鹵化烴、乾粉五種。表列共七個項目，規模門檻並不一致：項目一屋頂直昇機停機場（坪）沒有規模門檻；項目四昇降機械式停車場的門檻是「可容納十輛以上者」，用的是車輛數而不是樓地板面積；項目二飛機修理廠、飛機庫，項目五發電機室、變壓器室及其他類似之電器設備場所，項目六鍋爐房、廚房等大量使用火源之場所，項目七電信機械室、電腦室或總機室及其他類似場所，這四項的門檻都寫樓地板面積在二百平方公尺以上者；項目三汽車修理廠、室內停車空間則分三段：在第一層樓地板面積五百平方公尺以上者，在地下層或第二層以上樓地板面積在二百平方公尺以上者，在屋頂設有停車場樓地板面積在三百平方公尺以上者。\n本文但書與表後附註同樣是考點所在。但書規定，外牆開口面積（常時開放部分）達該層樓地板面積百分之十五以上者，上列除惰性氣體及鹵化烴外之滅火設備得採移動式設置。表後五則附註為：一、大量使用火源場所，指最大消費熱量合計在每小時三十萬千卡以上者；二、廚房如設有自動撒水設備，且排油煙管及煙罩設簡易自動滅火裝置時，得不受本表限制；三、停車空間內車輛採一列停放，並能同時通往室外者，得不受本表限制；四、本表項目三及項目四所列應設場所得設置自動撒水設備，項目七所列應設場所得設置預動式自動撒水設備，不受本表限制；五、平時有特定或不特定人員使用之中央管理室、防災中心等類似處所，不得設置二氧化碳滅火設備。\n附註第五點與本題的「不得設置」來源不同：附註第五點是對有人使用處所的明文禁止，本題項目二則是該列沒把二氧化碳列為得選擇設置之種類，兩種來源要分清楚。本條另有第二項，就樓地板面積在三百平方公尺以上之餐廳，及第十二條第一款第六目所定榮譽國民之家、長期照顧服務機構、老人福利機構、護理機構、身心障礙福利機構等使用之場所且樓地板面積合計在五百平方公尺以上者，定其廚房排油煙管及煙罩應設簡易自動滅火設備；但已依前項規定設有滅火設備者，得免設。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-027","公共危險物品等場所設置之室內消防栓設備，應符合下列何者規定？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-029","有關流水檢知裝置之構造，依據流水檢知裝置認可基準規定，下列敘述何者錯誤？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-026","設於外浮頂式儲槽之泡沫放出口為？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-030","鹵化烴滅火設備全區放射綜合檢查時，檢查方法、判定方法及注意事項，下列何者錯誤？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-025","有一建築物樓高 40 m，總樓地板面積 30000 m2，其消防專用蓄水池之有效水量規定要多少立方公尺以上？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-031","依各類場所消防安全設備設置標準規定，二氧化碳滅火設備使用氣體啟動者，下列敘述何者錯誤？",31,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-028",112,"有關水霧滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-028",111,"依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-028",110,"消防專用蓄水池規定之有效水量，指蓄水池深度在基地地面下多少公尺範圍內之水量，但採機械方式引水時，不在此限？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-028",109,"水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-028",108,"依法令規定在應設水霧、泡沫、乾粉、二氧化碳滅火設備之場所，但外牆開口面積（常時開放部分）達該層樓地板面積百分之多少以上者，上列滅火設備得採移動式設置？",1785129971693]