[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-027","fire-113-1-water-chemical-027",113,1,27,"公共危險物品等場所設置之室內消防栓設備，應符合下列何者規定？",{"A":16,"B":17,"C":18,"D":19},"放水壓力 1.7 kgf\u002Fcm2 以上，放水量 130 L\u002Fmin 以上","放水壓力 2.5 kgf\u002Fcm2 以上，放水量 350 L\u002Fmin 以上","放水壓力 2.5 kgf\u002Fcm2 以上，放水量 60 L\u002Fmin 以上","放水壓力 3.5 kgf\u002Fcm2 以上，放水量 260 L\u002Fmin 以上","D",null,[],false,"本題考點：公共危險物品等場所之室內消防栓設備，其放水壓力與放水量由《各類場所消防安全設備設置標準》第四編另設專條，數值與一般場所不同。\n【正解理由】依《各類場所消防安全設備設置標準》第二百零九條第四款，任一樓層內全部室內消防栓同時使用時，各消防栓瞄子放水壓力在每平方公分三點五公斤以上或0.35MPa以上；放水量在每分鐘二百六十公升以上；但全部消防栓數量超過五支時，以同時使用五支計算之。四個選項中與本款逐字相符的是「三點五公斤搭配二百六十公升」，故選 D。\n【逐項排除】\n(A) 每平方公分一點七公斤、每分鐘一百三十公升，出自第三十四條第一項第一款第二目所定一般場所第一種消防栓，不是第四編公共危險物品等場所的規格。\n(B) 每平方公分二點五公斤、每分鐘三百五十公升，出自第四十條第二款所定一般場所室外消防栓之出水壓力與出水量，連設備別都不同。\n(C) 每平方公分二點五公斤、每分鐘六十公升，出自第五十七條第三項第二款補助撒水栓之放水壓力與放水量，屬自動撒水設備的一環，不是室內消防栓。\n(D) 放水壓力三點五公斤以上、放水量二百六十公升以上，與第二百零九條第四款一致，為正確敘述。\n【記憶點】公危場所室內消防栓記四個數：壓力三點五、水量二六○、水源三十分鐘、緊急電源四十五分鐘。","《設置標準》分為五編，第四編【公共危險物品等場所消防設計及消防安全設備】自第一百九十三條起至第二百三十三條止，替公共危險物品與可燃性高壓氣體場所另立整套規格，第二百零九條即室內消防栓設備專條，第一項有五款，另有第二項就緊急電源另作規定。第一項第二款以準用方式處理：配管、試壓、室內消防栓箱、有效水量及加壓送水裝置之設置，準用第三十二條（配管、配件及屋頂水箱）、第三十三條（竣工加壓試驗）、第三十四條第一項第一款第三目、第三十四條第二項、第三十五條、第三十六條第二項、第三項及第三十七條，被準用的這幾條都落在第三編【消防安全設計】；第二項的緊急電源寫成「除準用第三十八條規定外」，也是一處準用。\n第一、三、四、五款則由第四編直接定其內容：第一款指定設置第一種消防栓，而第三十四條對一般場所的體例是除第十二條第二款第十一目或第四款之場所應設第一種外，其他場所就二種消防栓選擇設置之；第三款定各層任一點至消防栓接頭之水平距離在二十五公尺以下，且各層之出入口附近設置一支以上；第四款定放水壓力與放水量；第五款定水源容量為裝置室內消防栓最多樓層之全部消防栓繼續放水三十分鐘之水量以上，同以五支為計算上限。第二項在準用第三十八條之外，另定供電容量應供其有效動作四十五分鐘以上，而第三十八條本身所定為三十分鐘。\n同編第二百一十條室外消防栓為口徑六十三毫米以上、與防護對象外圍或外牆各部分之水平距離在四十公尺以下且設置二支以上，全部同時使用時各瞄子出水壓力在每平方公分三點五公斤以上，放水量在每分鐘四百五十公升以上，超過四支時以四支計算。一般場所方面，第三十四條第一種消防栓為一點七公斤、一百三十公升，第二種為一點七公斤、八十公升；第四十條室外消防栓為二點五公斤、三百五十公升。\n檢修面可對讀《消防安全設備及必要檢修項目檢修基準》室內消防栓設備之綜合檢查：放水壓力應在 1.7kgf\u002Fcm2 以上 7kgf\u002Fcm2 以下，但公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之消防栓，其放水壓力應在 3.5kgf\u002Fcm2 以上 7kgf\u002Fcm2 以下、放水量應在 260 l\u002Fmin 以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-026","設於外浮頂式儲槽之泡沫放出口為？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-028","下列場所之消防安全設備設置何者錯誤？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-025","有一建築物樓高 40 m，總樓地板面積 30000 m2，其消防專用蓄水池之有效水量規定要多少立方公尺以上？",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-029","有關流水檢知裝置之構造，依據流水檢知裝置認可基準規定，下列敘述何者錯誤？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-024","若同一樓層設 2 個泡沫消防栓箱時，消防幫浦出水量應在每分鐘多少公升以上？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-030","鹵化烴滅火設備全區放射綜合檢查時，檢查方法、判定方法及注意事項，下列何者錯誤？",30,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-027",112,"有關自動撒水設備設置流水檢知裝置規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-027",111,"自動撒水採用密閉乾式或預動式自動撒水設備，撒水頭動作後，流水檢知裝置應在幾分鐘內，使撒水頭放水？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-027",110,"二氧化碳滅火設備之全區放射或局部放射方式防護區域，對放射之滅火藥劑之排放規定，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-027",109,"中央消防主管機關認定儲存大量可燃物之場所天花板高度超過 6 公尺，或其他場所天花板高度超過 10 公尺者，應採用何種撒水頭？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-027",108,"依各類場所消防安全設備設置標準之規定，室外消防栓於其 I 公尺範圍內附設水帶箱，在 J 公尺以內，保持空曠，不得堆放物品或種植花木。下列 I，J 何者正確？",1785129971689]