[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-023":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-023","fire-113-1-water-chemical-023",113,1,23,"有關停車空間泡沫瞄子綜合試驗，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"放射量 100 L\u002Fmin 以上","6%型稀釋容量濃度應在 3-4%","水成膜泡沫 25%還原時間 30 秒以上","合成介面活性劑泡沫 25%還原時間 20 秒以上","A",null,[],false,"本題考點：《消防安全設備測試報告書測試方法及判定要領》移動式泡沫滅火設備綜合試驗中，泡沫瞄子放射量與泡沫品質的判定值。\n【正解理由】依該要領泡沫滅火設備綜合試驗（使用低發泡者）移動式部分，泡沫瞄子放射量之判定要領為「設置在供汽車修理、停車空間等部分應為每分鐘一百公升以上；設置在其他防護對象物部分應為每分鐘二百公升以上」。題幹問的是停車空間，門檻即每分鐘一百公升以上，故選 A。\n【逐項排除】\n(A) 停車空間之泡沫瞄子放射量為每分鐘一百公升以上，與判定要領相符，並與《各類場所消防安全設備設置標準》第八十條第一款移動式泡沫滅火設備各泡沫瞄子放射量每分鐘一百公升以上一致，即應選項。\n(B) 稀釋容量濃度判定為三％型者應在三至四％、六％型者應在六至八％，本項把六％型寫成三至四％，與判定要領不符。\n(C) 水成膜泡沫滅火藥劑之二十五％還原時間應為六十秒以上，本項寫三十秒，與判定要領不符。\n(D) 合成界面活性劑泡沫滅火藥劑之二十五％還原時間應為三十秒以上，本項寫二十秒，與判定要領不符。\n【記憶點】移動式泡沫記「停車空間一百公升、其他防護對象二百公升」，泡沫品質記「六％型六到八，蛋白與水成膜六十秒、合成界面活性劑三十秒」。","《各類場所消防安全設備設置標準》第八十條把移動式泡沫滅火設備的規定寫成四款，是本題的上游依據。第一款：同一樓層各泡沫瞄子放射量應在每分鐘一百公升以上，但全部泡沫消防栓箱數量超過二個時，以同時使用二支泡沫瞄子計算之。第二款：泡沫瞄子放射壓力應在每平方公分三點五公斤以上或 0.35 MPa 以上。第三款：移動式泡沫滅火設備之泡沫原液應使用低發泡。第四款：在水帶接頭三公尺範圍內設置泡沫消防栓箱，箱內配置長二十公尺以上水帶及泡沫瞄子乙具，箱面表面積應在零點八平方公尺以上，且標明移動式泡沫滅火設備字樣，並在泡沫消防栓箱上方設置紅色幫浦啟動表示燈。\n水源與幫浦則分列兩條：第七十六條第一項第三款定移動式泡沫滅火設備之水源容量，在二具泡沫瞄子同時放水十五分鐘之水量以上，同條第二項另要求加算充滿配管所需之泡沫水溶液量，且加算總泡沫水溶液量之百分之二十。第七十七條第三項定其幫浦出水量，同一樓層設一個泡沫消防栓箱時每分鐘一百三十公升以上、設二個以上時每分鐘二百六十公升以上，出水壓力核算最末端一個泡沫消防栓放射壓力能達每平方公分三點五公斤以上。\n檢修面在《消防安全設備及必要檢修項目檢修基準》泡沫滅火設備綜合檢查的移動式部分：由任一泡沫消防栓進行放射試驗，依附表測其發泡倍率及二十五％還原時間，並以糖度計法或比色計法測混合比率，判定要求發泡倍率應在五倍以上，混合比率應為設計時之稀釋容量濃度。\n易混淆對照要注意編別：公共危險物品場所的移動式泡沫滅火設備走第二百十九條，泡沫瞄子放射壓力同為每平方公分三點五公斤以上，但水源容量改依第二百二十條第二款，以四具瞄子同時放水三十分鐘計算，設於室內者放水量每分鐘二百公升以上、設於室外者每分鐘四百公升以上。另外第一百零一條定供室內停車空間使用之滅火藥劑，以第三種乾粉為限，也是停車空間常一併命題的規定。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-022","下列場所何者得設置水霧滅火設備？",22,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-024","若同一樓層設 2 個泡沫消防栓箱時，消防幫浦出水量應在每分鐘多少公升以上？",24,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-021","密閉式撒水頭之標示溫度，下列何者適用於最高周圍溫度在 39℃以上 64℃未滿之場所？",21,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-025","有一建築物樓高 40 m，總樓地板面積 30000 m2，其消防專用蓄水池之有效水量規定要多少立方公尺以上？",25,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-020","有關水道連結型自動撒水設備，下列敘述何者錯誤？",20,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-026","設於外浮頂式儲槽之泡沫放出口為？",26,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-023",112,"依各類場所消防安全設備設置標準規定，下列何種場所不需設置室內消防栓設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-023",111,"簡易自動滅火設備進行性能檢查時，蓄壓式滅火藥劑儲存容器滅火藥劑量應與標示差異不超過多少？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-023",110,"下列場所何者可選擇第二種室內消防栓選擇設置之？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-023",109,"下列有關室內消防栓箱之敘述，何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-023",108,"依各類場所消防安全設備設置標準之規定，有關應設置室外消防栓設備之場所，下列敘述何者正確？",1785129971662]