[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-021":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-021","fire-113-1-water-chemical-021",113,1,21,"密閉式撒水頭之標示溫度，下列何者適用於最高周圍溫度在 39℃以上 64℃未滿之場所？",{"A":16,"B":17,"C":18,"D":19},"57℃","68℃","93℃","141℃","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第四十八條密閉式撒水頭標示溫度與裝置場所平時最高周圍溫度的對照表。\n【正解理由】第四十八條明定密閉式撒水頭應就裝置場所平時最高周圍溫度依表選擇一定標示溫度之撒水頭，表列「三十九度以上六十四度未滿」該列對應之標示溫度為「七十五度以上一百二十一度未滿」。四個選項中只有九十三度落在七十五度以上一百二十一度未滿的區間內，故選 C。\n【逐項排除】\n(A) 五十七度未達七十五度，屬表列標示溫度「七十五度未滿」該列，適用於最高周圍溫度三十九度未滿之場所。\n(B) 六十八度同樣未達七十五度，仍落在標示溫度七十五度未滿該列，不適用本題所問之場所。\n(C) 九十三度在七十五度以上一百二十一度未滿之範圍內，正對應最高周圍溫度三十九度以上六十四度未滿之場所，即應選項。\n(D) 一百四十一度落在標示溫度一百二十一度以上一百六十二度未滿該列，對應之最高周圍溫度為六十四度以上一百零六度未滿之場所。\n【記憶點】第四十八條表四列成組：未滿三十九配未滿七十五、三十九到六十四配七十五到一百二十一、六十四到一百零六配一百二十一到一百六十二、一百零六以上配一百六十二以上。","第四十八條的表共四列，完整對照是：最高周圍溫度三十九度未滿者，用標示溫度七十五度未滿；三十九度以上六十四度未滿者，用七十五度以上一百二十一度未滿；六十四度以上一百零六度未滿者，用一百二十一度以上一百六十二度未滿；一百零六度以上者，用一百六十二度以上。四列的分界一路往上推，用意是讓標示溫度與環境溫度保持足夠落差，避免撒水頭因廚房、鍋爐、屋頂層日照、烘乾設備等日常熱源誤動作而造成水損，同時又不致遲滯到火勢已擴大才動作。記憶時可抓住三十九與七十五這組起算值，往上每一級的環境溫度上限就是下一級的下限。\n容易與此混用的是第五十二條的感知撒水頭：開放式自動撒水設備之自動啟動裝置採感知撒水頭者，應使用標示溫度在七十九度以下者，且每二十平方公尺設置一個，並設在裝置面距樓地板面高度五公尺以下且能有效探測火災之處；採探測器者，使用定溫式一種或二種，依第一百二十條規定設置，每一放水區域至少一個。第一百二十條又另定具有定溫式性能之探測器，應裝設在平時之最高周圍溫度比補償式局限型探測器之標稱定溫點或其他具有定溫式性能探測器之標稱動作溫度低攝氏二十度以上處；具二種以上標稱動作溫度者，應設在平時之最高周圍溫度比最低標稱動作溫度低攝氏二十度以上處。撒水頭看「標示溫度」、探測器看「標稱動作溫度」，兩套規定分屬滅火設備與警報設備，不可互換。\n與撒水頭同條系的其他常考數值還有第四十七條的位置規定：撒水頭軸心與裝置面成垂直裝置；迴水板下方四十五公分內及水平方向三十公分內應保持淨空間；密閉式撒水頭迴水板與裝置面之間距在三十公分以下；裝置於樑下時，迴水板與樑底之間距在十公分以下，且與樓板或天花板之間距在五十公分以下。驗證面則看《消防安全設備及必要檢修項目檢修基準》自動撒水設備之綜合檢查，密閉式撒水設備末端查驗管之放水壓力應在每平方公分一公斤以上十公斤以下。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-020","有關水道連結型自動撒水設備，下列敘述何者錯誤？",20,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-022","下列場所何者得設置水霧滅火設備？",22,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-019","關於水帶試驗，下列敘述何者錯誤？",19,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-023","有關停車空間泡沫瞄子綜合試驗，下列敘述何者正確？",23,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-018","有關泡沫滅火設備泡沫放射試驗判定要領，下列何者與消防安全設備測試報告書規定不同？",18,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-024","若同一樓層設 2 個泡沫消防栓箱時，消防幫浦出水量應在每分鐘多少公升以上？",24,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-021",112,"某一場所設置有滅火藥劑為 IG-01 之惰性氣體滅火設備，依據消防安全設備測試報告書測試方法及判定要領，針對儲存容器進行外觀試驗，則在室溫 35℃時，充填壓力應在多少 kgf\u002Fcm2 以下？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-021",111,"下列有關乾粉滅火設備設置之規定，何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-021",110,"依各類場所消防安全設備設置標準，應就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇設置之場所，下列場所何者得使用預動式自動撒水設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-021",109,"室內消防栓中之減水警報裝置，應於水量減至多少時發出警報？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-021",108,"某鍋爐房樓地板面積為 20 m×15 m，依法其所需之滅火效能值為何？",1785129971648]