[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-019","fire-113-1-water-chemical-019",113,1,19,"關於水帶試驗，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"製造年份超過 10 年者應做","無法辨識製造年份者應做","施加壓力 7 kgf\u002Fcm2 時間 5 分鐘","經測試合格未達 5 年者可不做","D",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》對消防水帶耐水壓試驗的實施對象、試驗壓力、時間與免試期間。\n【正解理由】依該基準室內消防栓設備之性能檢查「消防栓箱等」一項，製造年份超過十年或無法辨識製造年份之水帶，應將兩端快速接頭連接於耐水壓試驗機，並以相關器具夾住水帶兩末端，確認接頭確實連接且水帶內無殘留空氣後，施以每平方公分七公斤以上水壓試驗五分鐘合格始得繼續使用，但書為「已經水壓試驗合格未達三年者，不在此限」。免試期間是三年，題目寫五年，故選 D。\n【逐項排除】\n(A) 製造年份超過十年之水帶正是應實施耐水壓試驗的對象，敘述無誤。\n(B) 無法辨識製造年份之水帶與超過十年者並列為應實施對象，敘述無誤。\n(C) 第一種室內消防栓、連結送水管水帶箱及泡沫消防栓箱之水帶，試驗壓力為每平方公分七公斤以上、時間五分鐘，敘述無誤；室外消防栓箱與射水設備之水帶則為每平方公分六公斤以上，時間同為五分鐘。\n(D) 經水壓試驗合格未達三年者才得免試，本項寫五年與基準不符，即應選項。\n【記憶點】水帶試驗記「十年或年份不明就要試，七公斤五分鐘，合格未達三年免再試」。","《消防安全設備及必要檢修項目檢修基準》的體例是外觀檢查、性能檢查、綜合檢查三段，水帶耐水壓試驗落在性能檢查的消防栓箱等項目。同一段文字散見於多個設備章節，實施對象與時間完全一致，只有試驗壓力隨設備而異：室內消防栓設備第一種消防栓、連結送水管之水帶箱、泡沫滅火設備之泡沫消防栓箱三處寫每平方公分七公斤以上；室外消防栓設備與射水設備之室外消防栓箱兩處寫每平方公分六公斤以上；時間一律五分鐘，免試門檻一律為經水壓試驗合格未達三年者。第二種消防栓箱內配置的是口徑二十五毫米消防栓連同管盤長三十公尺之皮管或消防用保形水帶，檢查方法只以目視確認腐蝕、損傷及瞄子開閉裝置是否容易操作，不做耐水壓試驗，這是常被忽略的一格。\n「試驗」二字在本科有三個層次，數值各不相同，先分清題幹問的是哪一層再答。第一層是竣工時的加壓試驗：《各類場所消防安全設備設置標準》第三十三條定室內消防栓設備之消防立管管系試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓，並以繼續維持二小時無漏水現象為合格；第四十五條定自動撒水設備準用之，密閉乾式管系應併行空氣壓試驗，空氣壓力達每平方公分二點八公斤，壓力持續二十四小時，漏氣減壓量在每平方公分零點一公斤以下為合格。第二層是定期檢修的性能檢查，即本題的水帶耐水壓試驗。第三層是驗收階段的《消防安全設備測試報告書測試方法及判定要領》，體例為外觀試驗、性能試驗、綜合試驗。\n另一個與水帶有關而常被混淆的規定是配置本身：第三十四條第一項第一款第三目定第一種消防栓箱內配置口徑三十八毫米或五十毫米、長十五公尺並附快式接頭之水帶二條，但消防栓接頭至建築物任一點之水平距離在十五公尺以下時，水帶部分得設十公尺水帶二條。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-018","有關泡沫滅火設備泡沫放射試驗判定要領，下列何者與消防安全設備測試報告書規定不同？",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-020","有關水道連結型自動撒水設備，下列敘述何者錯誤？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-017","有關冷卻撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-021","密閉式撒水頭之標示溫度，下列何者適用於最高周圍溫度在 39℃以上 64℃未滿之場所？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-016","有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-022","下列場所何者得設置水霧滅火設備？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-019",112,"依各類場所消防安全設備設置標準規定，樓地板面積在 X 平方公尺以上之餐廳或供失智照顧型之長期照顧機構使用之場所且樓地板面積合計在 Y 平方公尺以上者，其廚房排油煙管及煙罩應設簡易自動滅火設備。則 X、Y 為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-019",111,"下列有關滅火器性能檢查之敘述，何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-019",110,"依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-019",109,"某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-019",108,"依各類場所消防安全設備檢修及申報作業基準，有關高壓式二氧化碳滅火藥劑儲存容器之滅火藥劑量檢查方法之注意事項中，鈷 60 有效使用年限約為多少年，如已超過時，應即時連絡專業單位處理或更換？",1785129971642]