[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-018":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-018","fire-113-1-water-chemical-018",113,1,18,"有關泡沫滅火設備泡沫放射試驗判定要領，下列何者與消防安全設備測試報告書規定不同？",{"A":16,"B":17,"C":18,"D":19},"泡沫滅火藥劑之稀釋濃度，如為 3%型者，應在 3%至 4%之範圍內；如為 6%型者，應在 6% 至 8%之範圍內","蛋白泡沫滅火藥劑，25%還原時間應為 60 秒以上","水成膜泡沫滅火藥劑，25%還原時間應為 60 秒以上","合成界面活性劑泡沫滅火藥劑，25%還原時間應為 20 秒以上","D",null,[],false,"本題考點：《消防安全設備測試報告書測試方法及判定要領》泡沫滅火設備泡沫放射試驗的稀釋容量濃度與二十五％還原時間判定值。\n【正解理由】依該要領泡沫滅火設備之綜合試驗，二十五％還原時間判定要領明定「如為蛋白泡沫滅火藥劑及水成膜泡沫滅火藥劑，應為六十秒以上；如為合成界面活性劑泡沫滅火藥劑，則應為三十秒以上」。合成界面活性劑泡沫的門檻是三十秒，題目寫二十秒，是四個選項中唯一與規定不同者，故選 D。\n【逐項排除】\n(A) 稀釋容量濃度判定要領載明三％型者應在三至四％之範圍內、六％型者應在六至八％之範圍內，本項逐字相符。\n(B) 蛋白泡沫滅火藥劑與水成膜泡沫滅火藥劑同列，二十五％還原時間為六十秒以上，本項相符。\n(C) 水成膜泡沫滅火藥劑之二十五％還原時間同為六十秒以上，本項相符。\n(D) 合成界面活性劑泡沫滅火藥劑之二十五％還原時間應為三十秒以上，本項寫二十秒與判定要領不同，即應選項。\n【記憶點】二十五％還原時間記「蛋白與水成膜六十秒，合成界面活性劑三十秒」；濃度記「三％型三到四，六％型六到八」。","二十五％還原時間的定義與測法，寫在《消防安全設備及必要檢修項目檢修基準》第七章泡沫滅火設備綜合檢查所附的「泡沫滅火設備發泡倍率及二十五％還原時間測定方法」附表：指自所採集之泡沫消泡為泡水溶液，還原至全部泡沫水溶液量之二十五％止所需之時間，因其特別著重水之保持能力及泡沫之流性，故另訂測法。該附表是兩套並列，適用藥劑不同，器具與算式也不同。\n第一套的適用範圍原文為「本測定方法適用於使用蛋白泡沫滅火藥劑或合成界面活性劑中之低發泡者」：器具為一千四百毫升容量之泡沫試料容器二個、泡沫試料採集器一個、量秤一個，還原時間另備碼表二個、泡沫試料容器台一個、一百毫升容量之透明容器四個；發泡倍率＝一千四百毫升÷扣除容器重量後之淨量（公克）。還原時間係將試料容器置於容器台上，在一定時間內以一百毫升透明容器承接還原於容器底部之水溶液。附表舉例：泡沫試料淨重一百八十公克者，二十五％容量值為四十五毫升，經過二分鐘還原四十毫升、二點五分鐘還原五十毫升，內插得二點二五分鐘。\n第二套的適用範圍原文為「本測定方法適用於使用水成膜泡沫滅火藥劑發泡者」：器具改為內容積一千毫升具刻度之量筒二個、泡沫試料採集器一個、一千公克計量器一個，還原時間用碼表一個與同款量筒二個；發泡倍率＝一千毫升÷減掉量筒重量之泡沫重量（公克）。還原時間係將量筒置於平面上，利用量筒上之刻度觀察還原至二十五％所需之時間。其舉例為淨重二百公克、一公克換算一毫升，二十五％容量值五十毫升，二分鐘還原四十毫升、三分鐘還原六十毫升，內插得二點五分鐘。本題選項含水成膜泡沫藥劑，套用測定方法前務必先看藥劑種類。\n稀釋濃度的上游依據是《各類場所消防安全設備設置標準》第七十九條：蛋白質泡沫液百分之三或百分之六、合成界面活性泡沫液百分之一或百分之三、水成膜泡沫液百分之三或百分之六。發泡倍率則不分藥劑種類，測試要領與檢修基準都定在五倍以上。另有第七十二條泡沫頭放射量：泡水噴頭每分鐘七十五公升以上；泡沫噴頭按泡沫原液種類，蛋白質泡沫液每平方公尺每分鐘六點五公升以上、合成界面活性泡沫液八公升以上、水成膜泡沫液三點七公升以上。兩張表的分組方式不同，作答時要分別記。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-017","有關冷卻撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",17,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-019","關於水帶試驗，下列敘述何者錯誤？",19,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-016","有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",16,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-020","有關水道連結型自動撒水設備，下列敘述何者錯誤？",20,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-015","有關滅火藥劑每公斤核算空氣量或氮氣量，依據惰性氣體與鹵化烴滅火設備之綜合檢查，下列何者與消防安全設備及必要檢修項目檢修基準規定不同？",15,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-021","密閉式撒水頭之標示溫度，下列何者適用於最高周圍溫度在 39℃以上 64℃未滿之場所？",21,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-018",112,"乾粉滅火設備使用蓄壓用氣體容器，若氣體使用氮氣時，在溫度 35℃，大氣壓力（表壓力） 0 kg\u002Fcm2 狀態下，除加算清洗配管所需要量外，每一公斤乾粉藥劑需氮氣之量為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-018",111,"依各類場所消防安全設備設置標準規定，總樓地板面積 100 平方公尺之何種場所應設置滅火器？ ①咖啡廳 ②幼兒園 ③陳列館 ④商場",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-018",110,"有關滅火器設置規定，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-018",109,"移動式泡沫滅火設備進行綜合檢查作業時，發泡倍率應在幾倍以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-018",108,"依各類場所消防安全設備檢修及申報作業基準，固定式泡沫滅火設備（低發泡）綜合檢查，設置泡沫頭者，每次選擇全部放射區域數之若干%以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力？",1785129971637]