[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-015","fire-113-1-water-chemical-015",113,1,15,"有關滅火藥劑每公斤核算空氣量或氮氣量，依據惰性氣體與鹵化烴滅火設備之綜合檢查，下列何者與消防安全設備及必要檢修項目檢修基準規定不同？",{"A":16,"B":17,"C":18,"D":19},"滅火藥劑 HFC-227ea 每公斤核算空氣量或氮氣量 14 公升","滅火藥劑 HFC-23 每公斤核算空氣量或氮氣量 100 公升","滅火藥劑 IG-55 每公斤核算空氣量或氮氣量 100 公升","滅火藥劑 IG-541 每公斤核算空氣量或氮氣量 100 公升","B",null,[],false,"本題考點：惰性氣體與鹵化烴滅火設備綜合檢查，放射試驗用空氣量或氮氣量之核算表。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》鹵化烴滅火設備綜合檢查之滅火藥劑每公斤核算空氣量或氮氣量表，HFC-23 為三十四公升、HFC-227ea 為十四公升；惰性氣體滅火設備綜合檢查之對應表則為二氧化碳五十五公升、氮氣一百公升、IG-55 一百公升、IG-541 一百公升。題敘把 HFC-23 寫成一百公升，與表列之三十四公升不同，故選 B。\n【逐項排除】\n(A) 正確。HFC-227ea 每公斤核算空氣量或氮氣量為十四公升，與鹵化烴該表所列相符。\n(B) 錯誤。HFC-23 應為每公斤三十四公升，即本題所指與規定不同者。\n(C) 正確。IG-55 每公斤核算空氣量或氮氣量為一百公升，與惰性氣體該表所列相符。\n(D) 正確。IG-541 每公斤核算空氣量或氮氣量為一百公升，與惰性氣體該表所列相符。\n【記憶點】只有鹵化烴那組不是一百：HFC-23 三十四、HFC-227ea 十四；惰性氣體組除二氧化碳五十五外皆一百。","這兩張表用在綜合檢查的放射試驗：所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之百分之十核算，再依每公斤所列公升數換算，每次試驗最多放出五支。換算比例因藥劑而異，是因為各藥劑的儲存狀態與充填密度不同：HFC-23、HFC-227ea 屬鹵化烴，以液化狀態儲存，單位重量所占容積小；IG-55（氮氣與氬氣）、IG-541（氮氣、氬氣與二氧化碳）屬惰性氣體，本身即以高壓氣態充填，故每公斤換算的試驗氣體量較大。低壓式者另有規定：其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之百分之十以上，或使用四十公升氮氣五瓶以上作為替代藥劑放射。\n設置端可與《各類場所消防安全設備設置標準》互相參照。第八條把滅火設備分為十一種，二氧化碳、惰性氣體、鹵化烴、乾粉分列第七至第十款，這也是檢修基準分章的依據。第九十六條之一明定惰性氣體滅火設備之防護區域竣工時，應做防護區域完整性測試，十分鐘內之氣體洩漏量使滅火藥劑維持在設計濃度百分之八十五以上者為合格。公共危險物品場所則走第四編，第二百二十二條之一明定鹵化烴滅火設備準用第九十七條之一第一項之 HFC-23、HFC-227ea 藥劑及第九十七條之二至第九十七條之十規定，並依表列滅火藥劑之係數核算藥劑量。\n抽樣分配表的讀法也常考：以系統設置數量對應第一年至第十年逐年抽測，設置數量超過二十一套者依其比例類推分配；抽測系統之放射區域在二區以上時，至少擇一放射區域實施放射試驗。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-014","依據消防安全設備及必要檢修項目檢修基準，於檢查類似醫院之場所時，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查，下列消防安全設備何者不適用此一規定？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-016","有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-013","水道連結型自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-017","有關冷卻撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-012","自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-018","有關泡沫滅火設備泡沫放射試驗判定要領，下列何者與消防安全設備測試報告書規定不同？",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-015",112,"有關滅火設備之緊急電源供電容量規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-015",111,"採用移動式放射方式之乾粉滅火設備，藥劑種類為第四種乾粉時，每一具噴射瞄子所需藥劑放射量為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-015",110,"公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-015",109,"公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-015",108,"依各類場所消防安全設備檢修及申報作業基準，對蓄壓式二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過多少%以上或壓力表示值在綠色範圍外時，應予以更新？",1785129971614]