[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-014":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-014","fire-113-1-water-chemical-014",113,1,14,"依據消防安全設備及必要檢修項目檢修基準，於檢查類似醫院之場所時，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查，下列消防安全設備何者不適用此一規定？",{"A":16,"B":17,"C":18,"D":19},"連結送水管","移動式泡沫滅火設備","乾粉滅火設備","水霧滅火設備","C",null,[],false,"本題考點：檢修基準綜合檢查之注意事項，也就是類似醫院之場所得改用常用電源檢查，究竟適用於哪些設備。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》，室內消防栓、室外消防栓、自動撒水（密閉式與開放式）、水霧、泡沫（固定式與移動式）、連結送水管，共八處綜合檢查之注意事項均載明：於檢查類似醫院之場所，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查。乾粉滅火設備之綜合檢查則無此注意事項，其全區及局部放射方式之綜合檢查開頭明定「將電源切換為緊急電源狀態，依下列各點進行檢查。當放射區域在二區以上，於每次檢查時，避免選擇同一區域內重複檢查，應依序進行檢查」，故選 C。\n【逐項排除】\n(A) 正確。連結送水管綜合檢查之注意事項明定，檢查醫院等場所因切換成緊急電源可能會造成困擾時，得使用常用電源進行檢查。\n(B) 正確。移動式泡沫滅火設備綜合檢查之注意事項亦載，於檢查類似醫院之場所因切換緊急電源可能造成困擾時，得使用常用電源檢查。\n(C) 錯誤，即本題所指不適用者。乾粉滅火設備之綜合檢查未有得改用常用電源之規定。\n(D) 正確。水霧滅火設備綜合檢查之注意事項同樣載明，於檢查類似醫院之場所時得使用常用電源檢查。\n【記憶點】寫「得」的是室內外消防栓、自動撒水、水霧、泡沫五章加連結送水管；排煙寫的是「應」；乾粉沒有這一條。","檢修基準把綜合檢查的電源狀態分寫在各章，體例有三種，應逐一分辨。第一種是水系統與連結送水管：室內消防栓、室外消防栓、自動撒水（密閉式與開放式）、水霧、泡沫（固定式與移動式）、連結送水管，共八處注意事項都是同一句型——於檢查類似醫院之場所，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查，用字是「得」。第二種是排煙設備，第二十二章綜合檢查之注意事項寫的是「醫院等切換成緊急電源進行檢查有困難之場所，應使用常用電源進行檢查」，用字是「應」，與前八處體例不同，作答時勿混為一談。第三種是藥劑放射型設備，各章開頭一律要求將電源切換為緊急電源狀態，未附任何改用常用電源之注意事項。\n乾粉滅火設備第八章綜合檢查的開頭為「將電源切換為緊急電源狀態，依下列各點進行檢查。當放射區域在二區以上，於每次檢查時，避免選擇同一區域內重複檢查，應依序進行檢查」。其放射試驗所需試驗用氣體量，加壓式為該放射區域應設加壓用氣體之百分之十以上，蓄壓式為該放射區域應設蓄壓用氣體量之百分之十以上，小數點以下有尾數時進一；移動式則為每五支噴射瞄子內以該設備一具加壓用氣體容器量或清洗用氣體容器量為之。\n須特別分辨的是抽樣分配表：它只出現在海龍、惰性氣體、鹵化烴三章，乾粉章全章沒有這張表，而且三章的適用範圍並不相同。第十章海龍滅火設備全區及局部放射方式均應依設置之系統數量進行抽樣檢查，表 10-1 之表名即為海龍滅火設備全區及局部放射方式之綜合檢查抽樣分配表；第十一章惰性氣體（表 11-1）與第十二章鹵化烴（表 12-1）則僅限全區放射方式。三張表都以設置套數對應第一年至第十年，備註均載明系統設置數量超過二十一套者依其比例類推分配；抽測之系統放射區域在二區以上時，應至少擇一放射區域實施放射試驗，並應於滅火藥劑儲存容器標示放射日期。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-013","水道連結型自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",13,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-015","有關滅火藥劑每公斤核算空氣量或氮氣量，依據惰性氣體與鹵化烴滅火設備之綜合檢查，下列何者與消防安全設備及必要檢修項目檢修基準規定不同？",15,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-012","自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",12,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-016","有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",16,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-011","室內消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",11,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-017","有關冷卻撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",17,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-014",112,"有關二氧化碳滅火設備相關規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-014",111,"開放式自動撒水設備之自動啟動裝置，感知撒水頭應設在裝置面距樓地板面高度多少公尺以下，且能有效探測火災處？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-014",110,"高壓電器設備其電壓在 7000 伏特以下時，水霧噴頭及配管與高壓電器設備應保持多少公分之標準離開距離？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-014",109,"測量室內消防栓瞄子直線放水之壓力時，應將壓力表之進水口，放置於瞄子前端多少距離處，讀取壓力表的指示值？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-014",108,"依各類場所消防安全設備設置標準之規定，加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至若干 MPa 以下？",1785129971606]