[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-013":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-013","fire-113-1-water-chemical-013",113,1,13,"水道連結型自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"於建築物各層放水壓力最低之最遠支管末端，打開末端查驗閥或連結之水龍頭等日常生活用水設施，確認系統性能是否正常及壓力表之指示值","末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在每平方公分 0.25 公斤以上每平方公分 6 公斤以下","設有增壓供水裝置者，於打開末端查驗閥或連結之水龍頭等日常生活用水設施降低配管內的壓力後，該增壓供水裝置應開始動作","設置末端查驗閥者，應設有與撒水頭同等放水性能之限流孔","B",null,[],false,"本題考點：水道連結型自動撒水設備綜合檢查之放水壓力判定值。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》水道連結型自動撒水設備之綜合檢查，判定方法明定末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在 0.5kgf\u002Fcm2 以上 10kgf\u002Fcm2 以下。題敘寫成 0.25kgf\u002Fcm2 以上 6kgf\u002Fcm2 以下，上下限均與規定不符，故選 B。\n【逐項排除】\n(A) 正確。檢查方法明定於建築物各層放水壓力最低之最遠支管末端，打開末端查驗閥或連結之水龍頭等日常生活用水設施，確認系統性能是否正常及壓力表之指示值。\n(B) 錯誤。放水壓力應在 0.5kgf\u002Fcm2 以上 10kgf\u002Fcm2 以下，即本題所指之錯誤敘述。\n(C) 正確。同一檢查方法明定，設有增壓供水裝置者，於打開末端查驗閥或連結之水龍頭等日常生活用水設施降低配管內壓力後，該增壓供水裝置應開始動作。\n(D) 正確。設置末端查驗閥者，應設有與撒水頭同等放水性能之限流孔，與《各類場所消防安全設備設置標準》第五十六條第三款所定相同。\n【記憶點】水道連結型放水壓力 0.5 至 10kgf\u002Fcm2，末端可用日常生活用水設施代替查驗閥。","水道連結型自動撒水設備是《各類場所消防安全設備設置標準》第十七條第一項第九款與第三項的產物：榮譽國民之家、機構住宿式與社區式長期照顧服務機構、老人福利機構、護理機構、身心障礙福利機構等場所應設自動撒水設備，但其樓地板面積合計未達一千平方公尺者，得設置水道連結型自動撒水設備或與現行法令同等以上效能之滅火設備，或採用中央主管機關公告之措施，其設置基準由中央主管機關定之。同條第二項另定，應設自動撒水設備之場所依本標準設有水霧、泡沫、二氧化碳、惰性氣體、鹵化烴或乾粉等滅火設備者，在該有效範圍內得免設自動撒水設備。\n系統特徵直接反映在查驗項目上。《消防安全設備測試報告書測試方法及判定要領》水道連結型自動撒水設備外觀試驗明定：民生水箱共用式應配接防止水滯留之管接頭，配管末端連結水龍頭或馬桶水箱等日常生活用水設施，俾使配管內水源流動不滯留，並配置壓力表；屋外或潮濕場所露出之金屬配管須施以防銹塗裝等防蝕措施，配管材質採不銹鋼鋼管者不在此限。採獨立水箱式而設末端查驗閥者，應設置在放水壓力預測為最低之配管部分，一次側應設壓力表、二次側應設有與撒水頭同等放水性能之限流孔，並在附近明顯易見之處所標示末端查驗閥字樣。\n對照組是一般密閉式自動撒水設備：末端查驗閥依第五十六條設於各層放水壓力最低之最遠支管末端、管徑二十五毫米以上、距地板面高度二點一公尺以下並附排水管裝置；撒水頭放水量依第五十條每分鐘八十公升以上、放水壓力每平方公分一公斤以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-012","自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",12,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-014","依據消防安全設備及必要檢修項目檢修基準，於檢查類似醫院之場所時，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查，下列消防安全設備何者不適用此一規定？",14,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-011","室內消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",11,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-015","有關滅火藥劑每公斤核算空氣量或氮氣量，依據惰性氣體與鹵化烴滅火設備之綜合檢查，下列何者與消防安全設備及必要檢修項目檢修基準規定不同？",15,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-010","有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",10,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-016","有關自動撒水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",16,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-013",112,"依據各類場所消防安全設備設置標準規定，加氣站之滅火器設置，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-013",111,"有關自動撒水設備末端查驗閥之敘述，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-013",110,"使用主成分為碳酸氫鈉之移動放射方式乾粉滅火設備，每一具噴射瞄子之每分鐘藥劑放射量應為下列何者？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-013",109,"乾粉滅火設備設置啟動用氣體容器時，其容器之內容積應有多少以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-013",108,"依各類場所消防安全設備設置標準之規定，乾粉滅火設備配管及閥類，下列設置規定何者錯誤？",1785129971601]