[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-011","fire-113-1-water-chemical-011",113,1,11,"室內消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"於裝置消防栓最多之最高樓層做放水試驗，以該樓層全部消防栓放水為準，但消防栓超過二支時，以二支同時放水","測量瞄子直線放水之壓力時，將壓力表之進水口放置於瞄子前端瞄子口徑的三分之一距離處，讀取壓力表的指示值","公共危險物品等場所達顯著滅火困難者設置消防栓之數量超過五支時，以五支同時放水","公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之消防栓，其放水壓力應在每平方公分 3.5 公斤以上每平方公分 7 公斤以下","B",null,[],false,"本題考點：室內消防栓綜合檢查中，瞄子直線放水壓力的量測位置。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》室內消防栓設備之綜合檢查，測量瞄子直線放水之壓力時，係將壓力表之進水口放置於瞄子前端瞄子口徑的二分之一距離處，讀取壓力表的指示值；題敘寫成三分之一距離處，與規定不符，故選 B。同一量測位置也見於室外消防栓設備、射水設備與補助撒水栓之綜合檢查，都是瞄子口徑的二分之一。\n【逐項排除】\n(A) 正確。檢查方法明定於裝置消防栓最多之最高樓層做放水試驗，以該樓層全部消防栓放水為準，但消防栓超過二支時，以二支同時放水。\n(B) 錯誤。應為瞄子口徑的二分之一距離處，即本題所指之錯誤敘述。\n(C) 正確。同款後段明定公共危險物品等場所達顯著滅火困難者設置消防栓之數量超過五支時，以五支同時放水。\n(D) 正確。判定方法明定該場所第一種滅火設備之消防栓，其放水壓力應在 3.5kgf\u002Fcm2 以上 7kgf\u002Fcm2 以下。\n【記憶點】壓力表擺在瞄子口徑二分之一的位置，放水量再由瞄子壓力換算。","綜合檢查的放水量不是直接量出來的，而是由瞄子壓力換算：Ｑ＝0.653Ｄ平方乘以根號Ｐ，其中Ｑ為瞄子放水量（l\u002Fmin）、Ｄ為瞄子口徑（mm）、Ｐ為瞄子壓力（kgf\u002Fcm2）。式子的骨幹是孔口流出公式，理論流速為根號二倍重力加速度乘水頭，把水頭換成以每平方公分公斤表示的壓力、把面積換成以毫米表示的口徑並乘上流出係數後，各項常數收斂成 0.653。壓力表之所以放在瞄子口徑二分之一處，是因為射流離開瞄子後會先收縮再擴散，在該位置量到的才是穩定值，太近或太遠都會失真。\n一般場所與公共危險物品場所的數值分屬兩套。一般場所依《各類場所消防安全設備設置標準》第三十四條：第一種消防栓瞄子放水壓力在每平方公分一點七公斤以上、放水量在每分鐘一百三十公升以上；第二種放水壓力相同、放水量在每分鐘八十公升以上；全部消防栓超過二支時以二支計算，水源容量依第三十六條為繼續放水二十分鐘之水量。公共危險物品等場所達顯著滅火困難者依第二百零九條設置第一種消防栓，放水壓力在每平方公分三點五公斤以上、放水量在每分鐘二百六十公升以上，超過五支時以五支計算，水源容量為繼續放水三十分鐘之水量，緊急電源供電容量應供有效動作四十五分鐘以上。\n檢修基準的綜合檢查判定值就照這兩套分流：一般場所放水壓力 1.7kgf\u002Fcm2 以上 7kgf\u002Fcm2 以下，放水量第一種 130 l\u002Fmin 以上、第二種 80 l\u002Fmin 以上；公共危險物品等場所達顯著滅火困難者放水壓力 3.5kgf\u002Fcm2 以上 7kgf\u002Fcm2 以下，放水量 260 l\u002Fmin 以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-010","有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-012","自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-009","高度危險工作場所設置室外消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-013","水道連結型自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-008","有關幫浦之形狀、構造部分，依據消防幫浦認可基準規定，下列敘述何者錯誤？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-014","依據消防安全設備及必要檢修項目檢修基準，於檢查類似醫院之場所時，因切換成緊急電源可能會造成困擾時，得使用常用電源檢查，下列消防安全設備何者不適用此一規定？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-011",112,"建築物高度在 X 公尺以下時，其連結送水管得與室內消防栓共用立管，其管徑在 Y 毫米以上，支管管徑在 Z 毫米以上。其中 X、Y 與 Z 分別為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-011",111,"依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-011",110,"室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-011",109,"乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-011",108,"二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",1785129971593]