[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-water-chemical-008":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-水與化學系統消防安全設備概要-008","fire-113-1-water-chemical-008",113,1,8,"有關幫浦之形狀、構造部分，依據消防幫浦認可基準規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"動葉輪之均衡性需良好，且流體之通路要順暢","有發生銹蝕之虞的部分，應施予有效之防蝕處理","傳動部分因外側易被接觸，應裝設防觸電措施","在軸封部位不得有吸入空氣或嚴重漏水現象","C",null,[],false,"本題考點：消防幫浦本體之形狀與構造要件，四個選項有三項取自幫浦構造規定，只有一項把防護方式換掉。\n【正解理由】依《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》第三點所定幫浦構造，第五款明定「傳動部分由外側易被接觸位置應裝設安全保護蓋」，要防的是聯軸器、皮帶等旋轉件把人員或衣物捲入的機械危害，屬實體遮蔽措施；題敘改成應裝設防觸電措施，把規範方向換成電氣危害，與該款所定不符，故選 C。\n【逐項排除】\n(A) 正確。同點第二款明定「動葉輪之均衡性需良好，且流體之通路要順暢」，均衡性不良會產生振動與異常聲響。\n(B) 正確。同點第六款明定在易生銹部位應做防銹處理，裝設在地面上之幫浦及其固定底架並應粉刷油漆。\n(C) 錯誤。傳動部分所需者為安全保護蓋，並非防觸電措施，即本題所指之錯誤敘述。\n(D) 正確。同點第三款明定「在軸封部位不得有吸入空氣或嚴重漏水現象」，軸封吸入空氣會使幫浦揚程與出水量下降。\n【記憶點】傳動部分加的是蓋子不是電：安全保護蓋防捲入，與防觸電無關。","幫浦構造之規定共八款，除本題四個選項所涉者外，尚包括：翻砂鑄件內外面均需光滑，不得有砂孔、龜裂或厚度不均；對軸承部添加潤滑油之方式，應可從外部檢視潤滑油油面高度，且必須設有補給用之加油嘴或加油孔；固定腳架所使用之螺栓及基礎螺栓，對地應有充分之耐震強度；與幫浦相連接之配管系中所使用之凸緣，須使用國家標準七九○、七九一及七九二等鐵金屬製管凸緣基準尺度。八款可分三組記：鑄件與葉輪講本體品質、軸封與軸承講運轉可靠、保護蓋與防銹及耐震螺栓講使用安全。\n同一基準第十五點另定附屬裝置之控制盤規定，是同一命題脈絡的高頻考點：控制盤應使用鋼板或其他非可燃性材料製造，易腐蝕之材料應施予有效防銹蝕處理；表示燈應易於辨認，並區分為電源表示燈白色、啟動表示燈紅色、呼水槽減水表示燈橘黃色、電動機電流超過負載表示燈橘黃色；儀表應包括電流表、電壓表，但在該控制盤以外地方可以辨認電壓者得免裝設；警報裝置之停鳴、復原需由人直接操作，且不得有因警報鳴動而連帶使馬達自動停止之構造；控制盤並應配備備用保險絲、線路圖及操作說明書。\n易混淆對照：構造規定管幫浦這台機器本身，控制盤規定管它的電氣操作介面，《消防安全設備測試報告書測試方法及判定要領》室內消防栓設備外觀試驗管的則是裝上去之後的呼水裝置尺寸——呼水槽水量應確保在 100 公升以上、溢水用排水管口徑應為 50A 以上、呼水管 25A 以上、補給水管 15A 以上，減水警報裝置之發信部應為浮筒開關或電極棒。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-water-chemical-007","消防水帶用快速接頭之構造，依據消防水帶用快速接頭認可基準規定，下列敘述何者錯誤？",7,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-water-chemical-009","高度危險工作場所設置室外消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",9,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-water-chemical-006","建築物樓設置消防專用蓄水池，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",6,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-water-chemical-010","有關室內消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",10,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-water-chemical-005","廚房設置簡易自動滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",5,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-water-chemical-011","室內消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",11,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-water-chemical-008",112,"某引擎試驗室設置有泡沫滅火設備，採高發泡放出口局部放射方式，依規定高發泡放出口之泡沫水溶液放射量，防護面積每 1 平方公尺應在每分鐘 X 公升以上。又防護面積係指防護對象外周線以高出防護對象物高度 Y 倍數值（該數值小於 1 公尺時，以 1 公尺計）所包圍之面積。其中 X+Y=？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-008",111,"固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，發泡倍率應在幾倍以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-008",110,"消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-008",109,"預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-008",108,"移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",1785129971573]