[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-fire-science-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-火災學概要-019","fire-113-1-fire-science-019",113,1,19,"所謂通風控制燃燒，其燃燒速度受下列何因素決定？",{"A":16,"B":17,"C":18,"D":19},"室內燃燒溫度","室內表面積","可燃物表面積","對外開口面積","D",null,[],false,"本題考點：通風控制燃燒的定義，其燃燒速度受限於外氣供應量，而非可燃物本身的裂解能力。\n【正解理由】室內火災在閃燃之後進入最盛期，可燃物大量裂解出可燃氣體，氧氣供應成為瓶頸，此時質量燃燒速率約等於每秒 0.09A√H 公斤，其中 A 為對外開口面積、H 為開口高度，完全由開口所能導入的空氣量決定。開口愈大則進氣愈多、燃燒愈猛烈；開口受限則燃燒受抑，未燃氣體流出開口後在室外燃燒。故選 D。\n【逐項排除】\n(A) 室內燃燒溫度是燃燒速率與熱平衡所造成的結果，屬被動變數，不是決定進氣量的原因。\n(B) 室內表面積影響的是牆體吸熱與熱回饋量，會改變室溫高低與升溫速度，但不控制空氣進入量。\n(C) 可燃物表面積是燃料控制階段的決定因素，火災成長期供氧充足時才由它主導燃燒速率。\n(D) 對外開口面積連同開口高度構成通風因子，直接決定進氣量，是通風控制階段的控制因子，為正解。\n【記憶點】成長期看可燃物表面積，最盛期看對外開口，燃料控制看燃料、通風控制看窗口。","區劃空間內的火災依序經歷起火、成長、閃燃、最盛與衰退。成長期空氣充足，燃燒速度取決於可燃物的表面積、排列方式與裂解速率，稱為燃料控制型；閃燃之後室內幾乎全面燃燒，氧氣消耗速度超過開口補充速度，控制權移轉到開口條件，稱為通風控制型。量化判定工具是當量比，即實際的燃料與空氣供應比除以化學計量比，當量比小於一為燃料控制，大於一為通風控制。\n空氣比是另一個常考且容易寫錯的定義：空氣比 m 等於實際供給空氣量除以理論空氣量，完全燃燒時其值大於一，超出一的那一部分才是過剩空氣率，也就是過剩空氣率等於 m 減一。通風控制狀態相當於空氣比小於一的缺氧燃燒，燃燒不完全，一氧化碳與煤煙的產生量急遽上升，這正是火場致死與能見度驟降的主因。\n通風控制也是回燃現象的前提。回燃指開口極小或近乎密閉的空間內，火勢因缺氧而轉為悶燒，室內蓄積高溫且富含未燃可燃氣體，一旦門窗突然開啟，空氣湧入使混合氣濃度回落到燃燒範圍內，瞬間產生激烈燃燒並自開口噴出火球。回燃與爆燃是不同層次的名詞，不可混稱：爆燃指火焰以次音速向未燃混合氣傳播的燃燒波，用以與傳播速度超過音速的爆轟相對，描述的是火焰傳播型態而非火場現象。\n延伸考點：以火載量除以每秒 0.09A√H 公斤可概估最盛期持續時間，開口大則燒得快而短、開口小則燒得慢而久。敘述型選項的判別線索也在此：成長期的燃燒速率與可燃物的種類、堆積方式高度相關，最盛期的燃燒速率則幾乎與可燃物種類無關而只隨開口條件變化，只要抓住這條分野，通風控制與燃料控制的正誤判斷幾乎都能定案。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-fire-science-018","空氣中氧氣的體積含量約為 X%，當氧濃度下降至 Y%時，一般燃燒難以持續，則 X，Y 分別為多少？",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-fire-science-020","依據「滅火器認可基準」對於火災分類之內容，下列物質燃燒時，何者屬於 A 類火災？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-fire-science-017","建築火災中會被通風口的大小設計所影響，通風因子為下列何者？（A：通風口面積、W：通風口寬度、H：通風口高度）",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-fire-science-021","依建築物火災 t2 成長理論，若釋熱率達 1 MW 需時間 100 秒，則釋熱率達 4 MW 所需時間為多少秒？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-fire-science-016","依國家標準 CNS15030「化學品分類及標示」規定混合物中含致癌物質超過 0.1%即屬致癌混合物。目前內政部消防署決議限制滅火器藥劑以下那一類物質含量不得超過 0.1%？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-fire-science-022","一物體在 27℃時輻射出的能量為 E，則當溫度升高到 627℃時輻射出的能量變為多少？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-fire-science-019",112,"建築物火災中，在所謂通風控制燃燒（Ventilation Controlled）情形下，可燃物燃燒速度主要受何因素決定？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-fire-science-019",111,"有關火羽流及天花板噴射流的敘述，下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-fire-science-019",110,"當發生危害物質災害時，為降低對民眾及搶救人員的危害，應迅速劃定管制區域，下列區域何者一般以黃色標示？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-fire-science-019",109,"若一物體的溫度為 327℃，輻射率（ Emissivity）為 0.1，已知史蒂芬–波茲曼常數為 5.67×10-8 W\u002Fm2k4，則其輻射強度（Emissive Power）約為多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-fire-science-019",108,"下列何種滅火劑使用於金屬火災時，沒有「與金屬產生化學反應而衍生危害物質」的可能？",1785129966288]