[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-113-1-fire-science-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-火災學概要-002","fire-113-1-fire-science-002",113,1,2,"建築物為防止火焰透過大樓窗口向上層延燒，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"加大窗戶面積以提升對流","在不改變窗戶面積下，採用寬大於高的橫型窗戶","採用定溫型火警探測器","增加上下層窗戶間的側壁長度","D",null,[],false,"本題考點：火焰自外牆窗口噴出後向上層延燒的機制，以及可以切斷此路徑的建築手段。\n【正解理由】室內火災進入最盛期後多屬通風控制型燃燒，未燃可燃氣體隨熱煙自窗口湧出，在窗外遇新鮮空氣續燃，形成沿外牆上升的噴出火焰，再捲入上層窗口造成垂直延燒。加大上下層窗戶之間的側壁長度，等於拉長噴出火焰必須跨越的不燃區段，使火焰在抵達上層開口前已脫離牆面或衰減，是直接切斷此延燒路徑的做法，故選 D。\n【逐項排除】\n(A) 加大窗戶面積會增加通風控制型火災的空氣供給量與可燃氣體排出量，噴出火焰隨之增長，向上延燒的風險提高。\n(B) 在開口面積不變下，寬大於高的橫型窗噴出的火流較薄，容易貼附外牆面上升而捲入上層開口；高大於寬的縱型窗噴出火焰的水平動量較大，火舌中心線離牆較遠。\n(C) 定溫式探測器是火警自動警報設備的感知元件，作用是偵知火災並發出警報，本身不具備阻隔火焰跨越樓層的能力。\n(D) 加大上下開口之間的側壁長度即加大垂直方向的不燃隔距，可有效抑制噴出火焰捲入上層開口，為應選項。\n【記憶點】阻斷上下層延燒靠拉開開口之間的垂直距離，不是靠加大開口，也不是靠加裝偵知元件。","窗口噴出火焰是室內火災由燃料控制型轉為通風控制型之後的典型現象。室內進氣量大致由開口因子 A√H 支配，A 為開口面積、H 為開口高度；當燃料熱裂解產生的可燃氣體多於室內空氣所能消耗時，未燃氣體便隨高溫煙氣自開口湧出，在窗外與空氣混合後燃燒，於外牆面形成向上延伸的火舌。\n\n噴出火焰的貼牆程度受開口形狀支配。橫長型開口（寬大於高）噴出的火流截面薄、垂直動量占優，火焰緊貼外牆面爬升，牆面又反過來限制了空氣自背側捲入，這種貼壁流的行為與康達效應（Coanda effect）同源；縱長型開口（高大於寬）噴出的火焰帶有較大的水平動量，火舌中心線離牆較遠，向上捲入上層開口的機會相對減少。因此在開口面積無法縮小時，開口的長寬比本身就是設計參數。\n\n抑制上下層延燒的手段可分三類。垂直向的手段是拉開上下開口的距離，包括加長腰壁（上下窗之間的實心外牆）與設置陽台、水平遮陽板等突出物，使火焰路徑被迫外偏。材料面的手段是外牆與開口周邊採用不燃或耐燃材料，並避免可燃外牆裝修材成為火焰的連續燃料床。室內側的手段則是在火勢成長階段即以自動撒水設備壓制，使室內根本達不到大量噴出未燃氣體的狀態。\n\n易混淆之處在於設備功能的層次：探測器與受信總機負責偵知與通報，撒水頭負責抑制，防火區劃與外牆構造負責阻隔，三者不能互相取代，題目把偵知元件放進「防止延燒」的選項中即屬此種陷阱。延伸考點包括開口因子與燃燒速率的關係、通風控制型與燃料控制型的分界，以及外牆延燒與飛火延燒兩種擴大路徑的差異。",true,[28,31,35,40,44,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-113-1-fire-science-001","有一倉庫長寬高分別為 8 公尺，5 公尺及 4 公尺，內置可燃物之總重量為 600 公斤，試計算該倉庫之火載量若干（kg\u002Fm2）？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-113-1-fire-science-003","當起火區域產生閃燃時，人在其中是無法存活的，對於閃燃現象之敘述，下列何者錯誤？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-112-1-fire-science-040","已知距離光源 2 公尺處的減光率為 20%，則當與光源的距離加倍時，其減光率約為多少%？（提示：log(80)≒ 1.903，log(64)≒ 1.806）",40,112,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-fire-science-004","下列四種相等質量之物質：甲烷（CH4）、乙醇（C2H5OH）、乙炔（C2H2）及丙烯（C3H6），何者燃燒時具有最高之理論空氣量？",4,{"webId":45,"stem":46,"number":47,"year":39,"session":12},"fire-112-1-fire-science-039","假設定量乙醇(C2H5OH)與理論空氣量混合後產生完全燃燒，其後將燃燒廢氣冷卻至常溫，則其中二氧化碳的濃度約為多少%？",39,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-fire-science-005","大樓火災常伴隨煙囪效應。所謂煙囪效應是指建築物內部受熱後熱氣流上升，冷空氣由下方填補，使得火災產生的煙霧會快速瀰漫整個建築物的現象。針對以上敘述，下列何者錯誤？",5,[53,57,60,64,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-science-002",114,"建築物火災成長過程中有關衰退期的敘述何者錯誤？",{"webId":58,"year":39,"stem":59,"number":13},"fire-112-1-fire-science-002","下列何者屬於準自然發火性物質？",{"webId":61,"year":62,"stem":63,"number":13},"fire-111-1-fire-science-002",111,"有關爆燃與爆轟，下列敘述何者錯誤？",{"webId":65,"year":66,"stem":67,"number":13},"fire-110-1-fire-science-002",110,"依據建築物火災 t2 成長理論，當釋熱率（Q）達到 4 MW 時，需要 300 秒的時間，表示火災成長之速度為下列何者？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-fire-science-002",109,"三個面積分別為 0.20 m ，0.40 m ，0.60 m 之開口相互串聯時，其等效流動面積為何？",1785129966179]