[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-fire-law-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-消防法規概要-032","fire-113-1-fire-law-032",113,1,32,"依建築技術規則建築設計施工編規定，有關耐燃合板、耐燃纖維板、耐燃塑膠板及石膏板等耐燃材料，係指耐燃幾級之材料？",{"A":16,"B":17,"C":18,"D":19},"一級","二級","三級","四級","C",null,[],false,"本題考點：《建築技術規則建築設計施工編》第 1 條建築技術用語定義中，不燃材料、耐火板與耐燃材料分別對應耐燃一、二、三級的關係。\n【正解理由】依《建築技術規則建築設計施工編》第 1 條建築技術用語定義，耐燃材料指耐燃合板、耐燃纖維板、耐燃塑膠板、石膏板及其他經中央主管建築機關認定符合耐燃三級之材料。題幹所列四種板材即該定義逐字列名之例示，對應等級為耐燃三級，故選 C。\n【逐項排除】\n(A) 耐燃一級對應的是不燃材料，例示為混凝土、磚或空心磚、瓦、石料、鋼鐵、鋁、玻璃、礦棉、陶瓷品等無機材料，與題幹所列板材不同。\n(B) 耐燃二級對應的是耐火板，例示為木絲水泥板、耐燃石膏板等，與耐燃合板、耐燃纖維板、耐燃塑膠板分屬不同等級。\n(C) 耐燃三級即耐燃材料，其例示涵蓋耐燃合板、耐燃纖維板、耐燃塑膠板及石膏板，與題幹完全相符，為正確答案。\n(D) 建築技術規則之耐燃分級體系止於耐燃三級，並無耐燃四級之分類，本項所指等級不存在。\n【記憶點】一級不燃材料、二級耐火板、三級耐燃材料；名稱本身叫「耐燃材料」的那一組正好落在第三級。","耐燃等級之所以要三分，是因為建築內部裝修與消防設備的規定都以它為門檻，等級不同、可用的場所就不同。《各類場所消防安全設備設置標準》裡最常見的是耐燃一級：第 159 條第五款規定榮譽國民之家、長期照顧服務機構、老人福利機構、兒童及少年福利機構、護理機構、身心障礙福利機構等場所使用之樓層，須各樓層以具一小時以上防火時效之牆壁及防火設備分隔為二個以上之區劃、裝修材料以耐燃一級材料裝修、並設有火警自動警報設備及自動撒水設備，才得免設避難器具；第 188 條第一款但書規定戲院、電影院、歌廳、集會堂等場所觀眾席及工廠等類似建築物，天花板高度在五公尺以上且天花板及室內牆面以耐燃一級材料裝修者，不受每五百平方公尺以防煙壁區劃之限制；第 190 條所列得免設排煙設備之處所，多款也都以天花板及室內牆面以耐燃一級材料裝修為要件。\n建築端同樣如此。《建築技術規則建築設計施工編》第 86 條第四款規定使用類組為 B-3 組之廚房，應以具有一小時以上防火時效之牆壁及防火門窗等防火設備與該樓層之樓地板形成區劃，其天花板及牆面之裝修材料以耐燃一級材料為限；同條第五款對其他經中央主管建築機關指定使用用途之建築物或居室亦同。\n易混淆對照：防火時效與耐燃等級是兩套獨立的指標。防火時效講的是構造在標準火害下維持一定時間不失效（如一小時、三十分鐘），耐燃等級講的是材料本身在受熱時的發煙與燃燒表現；同一道牆可能同時被要求「具一小時以上防火時效」與「以耐燃一級材料裝修」，兩者不能互相取代。第 86 條第一款的分戶牆要求防火時效、第二款的分間牆要求以不燃材料建造，正是這兩套指標並用的實例。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-fire-law-031","依建築技術規則建築設計施工編規定，所謂「無窗戶居室」係指有效採光面積未達該居室樓地板面積多少者？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-fire-law-033","依建築技術規則建築設計施工編規定，下列何者不視為居室？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-fire-law-030","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準規定，對於電動機之構造與機能，下列敘述何者錯誤？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-fire-law-034","有關防火牆及防火水幕設置基準規定，下列敘述何者錯誤？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-fire-law-029","有關消防安全設備檢修申報之相關規定，下列敘述何者正確？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-fire-law-035","液化石油氣販賣場所經營者應每 6 個月向販賣場所及供應設備所在地之消防機關申報資料，下列敘述何者錯誤？",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-032",114,"依可燃性高壓氣體場所標示板規格及設置要點規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-032",112,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-032",111,"供某住宿式長期照顧機構使用之五層樓建築物，各樓層若符合下列何者之規定，得免設避難器具？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-032",110,"裝置避難器具之固定部（係指裝設避難器具之樑、柱、樓板等堅固構造或經補強之部分）直接裝置在建築物主要構造部之施工方法，若以金屬膨脹錨定螺栓之施工方法，金屬膨脹錨定螺栓間之間隔，應為埋入深度之幾倍以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-032",109,"依各類場所消防安全設備檢修及申報作業基準，有關滅火器外觀檢查之規定，滅火器本體上端與樓地板面之距離，18 公斤以上者不得超過 a 公尺，未滿 18 公斤者不得超過 b 公尺。a、b 值各為下列何者？",1785129968985]