[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-fire-law-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-消防法規概要-011","fire-113-1-fire-law-011",113,1,11,"依防火牆及防火水幕設置基準規定，防火水幕之防護高度為 20 公尺時，其每公尺水幕長度放水量應在每分鐘多少公升以上？",{"A":16,"B":17,"C":18,"D":19},"50","100","150","200","D",null,[],false,"本題考點：《防火牆及防火水幕設置基準》第 5 點防火水幕放水量之基準值與逐公尺增量計算。\n【正解理由】依該基準第 5 點，防火水幕之防護高度在十公尺以下時，其每公尺水幕長度放水量應在每分鐘一百公升以上；其防護高度超過十公尺者，高度每增加一公尺，放水量每分鐘應增加十公升。本題防護高度二十公尺，超過十公尺的部分為十公尺，應在基準值上加計每分鐘一百公升，得每分鐘二百公升以上，故選 D。\n【逐項排除】\n(A) 每分鐘五十公升不符，該值既非第 5 點所定之基準值，也無法由基準值加計增量得出。\n(B) 每分鐘一百公升是防護高度在十公尺以下時之放水量，本題防護高度二十公尺，尚未計入超過十公尺部分之增量。\n(C) 每分鐘一百五十公升係以防護高度十五公尺代入所得，與本題所給之二十公尺不合。\n(D) 正確，即基準值一百公升加計十公尺增量後之數值。\n【演算步驟】公式：每公尺水幕長度放水量 Q ＝ 100 L\u002Fmin ＋（防護高度 H － 10 m）× 10 L\u002Fmin 每公尺。代入 H ＝ 20 m：Q ＝ 100 L\u002Fmin ＋（20 m － 10 m）× 10 L\u002Fmin ＝ 100 L\u002Fmin ＋ 100 L\u002Fmin ＝ 200 L\u002Fmin。\n【記憶點】十公尺以下一百公升起跳，每多一公尺加十公升。","防火水幕是用水膜取代實體防火牆，多用於室外儲槽與廠區境界線之間，所以本基準的數值全部圍繞「防護高度」展開，讀懂高度的定義才算真的會算。第 4 點規定，防火牆及防火水幕之防護高度，為儲槽側板外壁假想火面與距離邊緣線所成連線，和地面廠區境界線所延伸垂線交點之垂直高度；距離邊緣線位於海洋、湖泊、河川等時，則以岸邊所成連線計算；但防護高度未滿二公尺者，以二公尺計算。這個下限常被忽略，命題者若給一點五公尺，仍應以二公尺代入。\n上限則在第 6 點：沿防火水幕設有能以仰角八十五度以上放水之固定式放水槍，且放水槍與防護位置平行、左右角度範圍在四十五度以上、放水高度高於防護高度、放水槍出水量每分鐘一千五百公升以上並能有效防護防火水幕設置位置者，其防護高度超過二十五公尺者以二十五公尺計算；放水高度超過四十公尺者以四十公尺計算。\n算完放水量之後接著算水源與電源。第 10 點規定，儲槽容量未達一萬公秉者，水源容量不得小於防護該儲槽連續放水一百二十分鐘之水量；儲槽容量達一萬公秉以上者，不得小於連續放水二百四十分鐘之水量。第 9 點規定緊急電源之供電容量時間，儲槽容量未達一萬公秉者為一百八十分鐘，達一萬公秉以上者為三百六十分鐘。第 8 點規定加壓送水裝置應採用消防幫浦；應為專用，但與其他消防設備並用，無妨礙其他設備之性能時，不在此限；應連接緊急電源，但加壓送水裝置之驅動系統為引擎或渦輪機者，免設緊急電源；啟動後六分鐘內應能形成水幕，幫浦全揚程 H＝h1＋h2＋h3，即噴頭設計壓力換算水頭、配管摩擦損失水頭與落差之和。第 7 點第五款則規定配管管系竣工時應做加壓試驗，試驗壓力為加壓送水裝置全閉揚程一點五倍以上之水壓，須持續兩小時無漏水現象。第 11 點並規定本基準未規定者，準用緊急電源容量計算基準及消防幫浦加壓送水裝置等及配管摩擦損失計算基準。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-fire-law-010","依各類場所消防安全設備設置標準規定，有關設置於公共危險物品等場所之自動撒水設備，下列敘述何者錯誤？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-fire-law-012","依各類場所消防安全設備設置標準規定，防災監控系統綜合操作裝置應設置於防災中心、中央管理室或值日室等經常有人之處所，其緊急電源供電容量應有效動作多少小時以上？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-fire-law-009","有關消防幫浦性能應符合之規定，下列敘述何者錯誤？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-fire-law-013","依據消防法第 13 條第 1 項規定，一定規模以上之建築物，應由管理權人遴用防火管理人，責其訂定消防防護計畫，下列何者不屬於一定規模以上之建築物？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-fire-law-008","依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，有關液化石油氣販賣場所經營者相關規範，下列敘述何者正確？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-fire-law-014","依消防法規定，高層建築物之防災中心或地下建築物之中央管理室，應置服勤人員，並經主管機關或經中央主管機關登錄之專業機構施予一定時數之訓練，領有合格證書，始得充任；任職期間，並應定期接受複訓。試問初訓合格者，應多久時間複訓 1 次？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-011",114,"下列何者非屬開業建築師、電機技師得執行之消防安全設備設計、監造或測試、檢修？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-011",112,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，針對瓦斯行設置容器保管室相關安全規範，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-011",111,"有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-011",110,"可燃性高壓氣體儲存場所之構造、設備及安全管理相關規定，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-011",109,"依各類場所消防安全設備設置標準之規定，下列那一種火警探測器不適合裝設在麵粉廠灰塵會大量滯留的場所？",1785129968836]