[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-fire-law-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-消防法規概要-009","fire-113-1-fire-law-009",113,1,9,"有關消防幫浦性能應符合之規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"幫浦之額定出水量，在其性能曲線上之全揚程必須達到額定揚程 100%至 110%之間","幫浦之出水量在額定出水量之 150%時，其全揚程應達到額定出水量；性能曲線上全揚程之 65%以上","全閉揚程應為性能曲線上全揚程之 150%以下","幫浦所消耗之動力，在額定出水量 150%時，其軸動力不得超過馬達額定輸出馬力之 110%","C",null,[],false,"本題考點：《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》第 5 點所定幫浦性能曲線上的三個判定值與軸動力限制。\n【正解理由】依該基準第 5 點第一款，幫浦所標示之額定出水量，在其性能曲線上之全揚程必須達到額定揚程之百分之一百至百分之一百十之間；幫浦之出水量在額定出水量之百分之一百五十時，全揚程應達到性能曲線上全揚程之百分之六十五以上；全閉揚程應為性能曲線上全揚程之百分之一百四十以下。選項 C 把全閉揚程上限寫成百分之一百五十以下，與該點所定之百分之一百四十不同，題目問錯誤者，故選 C。\n【逐項排除】\n(A) 敘述正確，即第 5 點第一款第一目之額定點規定，全揚程須在額定揚程之百分之一百至百分之一百十之間。\n(B) 敘述正確，即第 5 點第一款第二目，出水量在額定出水量之百分之一百五十時，全揚程應達性能曲線上全揚程之百分之六十五以上。\n(C) 錯誤所在。全閉揚程之上限為性能曲線上全揚程之百分之一百四十以下，不是百分之一百五十以下。\n(D) 敘述正確，即第 5 點第三款第二目，在額定出水量百分之一百五十時，軸動力不得超過馬達額定輸出馬力之百分之一百十。\n【記憶點】幫浦性能三個數字：額定點一百至一百十、一百五十出水量點六十五以上、全閉一百四十以下。","本題四個選項全部改寫自同一部技術基準，只動一個數字，屬於典型的「數值辨識題」。《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》是依《各類場所消防安全設備設置標準》授權訂定的技術基準，體例是「點」而非「條」，引用時應寫第幾點。\n第 5 點除性能曲線外，第二款另以表列方式規定吸水性能，各列為：額定出水量九百公升每分鐘未滿者，最大吸水全揚程六點零公尺；九百以上二千七百以下者為五點五公尺；超過二千七百至五千以下者為四點五公尺；超過五千至八千五百以下者為四點零公尺。第三款第一目並規定在額定出水量時，軸動力不得超過馬達之額定輸出馬力，第二目才是百分之一百五十出水量時的百分之一百十上限，兩目是不同工況，不可混用。第五款規定幫浦在啟動時其軸承不得發生過熱、噪音或異常振動現象。第 10 點則規範電動機機能：幫浦在額定負荷狀態下應能順利啟動，電動機在額定輸出連續運轉八小時後不得發生異狀，且在超過額定輸出百分之十輸出力運轉一小時仍不致發生障礙、引起過熱現象。\n同樣的數值在驗收端也會出現。《消防安全設備測試報告書測試方法及判定要領》連結送水管設備之性能試驗即載明：全閉揚程應在額定負荷運轉時之測得揚程的 140% 以下，測得揚程應在該幫浦所標示揚程的 100% 以上 110% 以下；呼水裝置之減水警報應在呼水槽之水量減至 1\u002F2 前確實動作；防止水溫上升排放裝置之排放水量應在 q＝LsC／（60Δt）求出之量以上，其中 C 為 860kcal、Δt 為 30℃；幫浦性能試驗裝置求出之出水量與流量計表示值之差，應在該流量計使用範圍最大刻度的 ±3% 以內。設置基準與驗收判定在此處數值一致，是少數可以互相印證的考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-fire-law-008","依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，有關液化石油氣販賣場所經營者相關規範，下列敘述何者正確？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-fire-law-010","依各類場所消防安全設備設置標準規定，有關設置於公共危險物品等場所之自動撒水設備，下列敘述何者錯誤？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-fire-law-007","依各類場所消防安全設備設置標準規定，所謂有效開口係指開口下端距樓地板面多少公分以內？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-fire-law-011","依防火牆及防火水幕設置基準規定，防火水幕之防護高度為 20 公尺時，其每公尺水幕長度放水量應在每分鐘多少公升以上？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-fire-law-006","依各類場所消防安全設備設置標準規定，平時有特定或不特定人員使用之中央管理室、防災中心等類似處所，不得設置下列那一種滅火設備？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-fire-law-012","依各類場所消防安全設備設置標準規定，防災監控系統綜合操作裝置應設置於防災中心、中央管理室或值日室等經常有人之處所，其緊急電源供電容量應有效動作多少小時以上？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-114-1-fire-law-009",114,"依消防法、消防安全設備檢修及申報辦法規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-112-1-fire-law-009",112,"依消防安全設備檢修專業機構管理辦法之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-111-1-fire-law-009",111,"有關室內儲槽場所幫浦設備之設置規定，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-110-1-fire-law-009",110,"依消防設備師及消防設備士管理辦法規定，各級消防機關得檢查消防設備師及消防設備士之業務或令其報告、提出證明文件、表冊及有關資料。若某消防設備士拒絕提供前述資料，違反規定時，主管機關應如何處理？",{"webId":70,"year":71,"stem":72,"number":13},"fire-109-1-fire-law-009",109,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法，有關地下儲槽場所位置、構造及設備之規定，下列敘述何者正確？",1785129968827]