[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-113-1-fire-law-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-113-1-消防法規概要-001","fire-113-1-fire-law-001",113,1,"依各類場所消防安全設備設置標準規定，防災中心樓地板面積應在多少平方公尺以上？",{"A":15,"B":16,"C":17,"D":18},"10","20","30","40","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 238 條所定防災中心之樓地板面積下限。\n【正解理由】第 238 條開宗明義規定「防災中心樓地板面積應在四十平方公尺以上」，並接續定其位置（設於消防人員自外面容易進出之位置、設於便於通達緊急昇降機間及特別安全梯處、出入口至屋外任一出入口之步行距離在三十公尺以下）與構造（冷暖、換氣等空調系統為專用；防災監控系統相關設備以地腳螺栓或其他堅固方法予以固定；內設供操作人員睡眠、休息區域者，該部分以防火區劃間隔）。四個選項中僅四十平方公尺與條文相符，故選 D。\n【逐項排除】\n(A) 十平方公尺遠低於第 238 條所定之四十平方公尺，不足以容納防災監控系統相關設備與值勤空間。\n(B) 二十平方公尺同樣低於條文所定之四十平方公尺下限。\n(C) 三十平方公尺並非面積門檻；第 238 條裡的「三十公尺」是防災中心出入口至屋外任一出入口之步行距離上限，單位與規範對象都不同，最常被移花接木成面積。\n(D) 四十平方公尺即第 238 條明定之樓地板面積下限，為正確者。\n【記憶點】防災中心記兩個數字：樓地板面積四十平方公尺以上、出入口至屋外步行距離三十公尺以下。","防災中心之所以要有面積下限，是因為它是全棟消防安全設備的操作匯集點。依同標準第 192-1 條，防災監控系統綜合操作裝置應設置於防災中心、中央管理室或值日室等經常有人之處所，並監控或操作下列設備：火警自動警報設備之受信總機、瓦斯漏氣火警自動警報設備之受信總機、緊急廣播設備之擴大機及操作裝置、連結送水管之加壓送水裝置及與其送水口處之通話連絡、緊急發電機、常開式防火門之偵煙型探測器、室內消防栓與自動撒水及泡沫與水霧等滅火設備之加壓送水裝置、乾粉與惰性氣體及鹵化烴等滅火設備、排煙設備；同條第二項並定其緊急電源準用第 38 條規定，且供電容量應供其有效動作二小時以上。這麼多盤面加上值勤人員的作業空間，四十平方公尺就是最低需求。\n其他設備也把防災中心當成優先設置位置：第 126 條規定火警受信總機裝置於值日室等經常有人之處所，但設有防災中心時，設於該中心；第 145-1 條就一一九火災通報裝置也作相同安排。應設防災監控系統綜合操作裝置的場所則見第 30-1 條：高層建築物、總樓地板面積在五萬平方公尺以上之建築物、總樓地板面積在一千平方公尺以上之地下建築物，以及其他經中央主管機關公告之供公眾使用之場所。\n人的面向由《消防法》第 13-1 條處理：高層建築物之防災中心或地下建築物之中央管理室，應置服勤人員，並經主管機關或經中央主管機關登錄之專業機構施予一定時數之訓練，領有合格證書，始得充任，任職期間並應定期接受複訓；管理權人應於服勤人員遴用之次日起十五日內，報請建築物所在地主管機關備查，異動時亦同。該條的訓練時數只寫「一定時數」，實際數字另定於其辦法，條文本身並未載明。未置領有合格證書之服勤人員或未依期限備查者，第 40 條定有罰鍰。",true,[27,32,36,40,44,48],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-112-1-fire-law-040","下列何者非屬行政院公共工程委員會編印之工程倫理手冊（第二版）所列，工程人員應瞭解、堅守及篤行之八大倫理基本守則之一？",40,112,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-fire-law-002","有關「防災監控系統綜合操作裝置」，下列敘述何者正確？",2,{"webId":37,"stem":38,"number":39,"year":31,"session":12},"fire-112-1-fire-law-039","依建築技術規則建築設計施工編及各類場所消防安全設備設置標準對無窗戶居室之定義及規定，下列敘述何者錯誤？",39,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-fire-law-003","依各類場所消防安全設備設置標準規定，下列何種場所於火災發生時，火警受信總機應連動停止相關娛樂用影音設備？",3,{"webId":45,"stem":46,"number":47,"year":31,"session":12},"fire-112-1-fire-law-038","依建築技術規則建築設計施工編之規定，下列何者屬耐燃二級裝修材料？",38,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-fire-law-004","有關二氧化碳滅火設備各種標示規格，下列何者錯誤？",4,[53,57,61,64,68],{"webId":54,"year":55,"stem":56,"number":12},"fire-115-1-fire-law-001",115,"依消防法規定，下列何者應委託中央主管機關許可之消防安全設備檢修專業機構辦理檢修申報？ ①複合用途建築物 ②地下建築物 ③高層建築物 ④大型集合住宅",{"webId":58,"year":59,"stem":60,"number":12},"fire-114-1-fire-law-001",114,"依消防法規定，下列何種建築物之服勤人員依法不用訓練，就可以充任？",{"webId":62,"year":31,"stem":63,"number":12},"fire-112-1-fire-law-001","針對法規、命令之敘述，下列何者錯誤？",{"webId":65,"year":66,"stem":67,"number":12},"fire-111-1-fire-law-001",111,"依消防法及消防法施行細則之規定，下列那一個場所應由管理權人，遴用防火管理人並責其製定消防防護計畫報請消防機關核備？",{"webId":69,"year":70,"stem":71,"number":12},"fire-110-1-fire-law-001",110,"工廠發生火災時，工廠之管理權人雖指派專人至現場協助救災，但未能提供廠區化學品種類、數量、位置平面配置圖及搶救必要資訊供消防人員參考。依消防法規定，該處管理權人多少罰鍰？",1785129968764]