[{"data":1,"prerenderedAt":74},["ShallowReactive",2],{"q-fire-113-1-alarm-evacuation-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":53,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-警報與避難系統消防安全設備概要-038","fire-113-1-alarm-evacuation-038",113,1,38,"針對差動式分布型空氣管式探測器進行接點水高試驗，其試驗之目的為何？",{"A":16,"B":17,"C":18,"D":19},"測試空氣管有無阻塞或洩漏","測試空氣管長度是否正確","測試檢出器之排氣孔有無阻塞","測試檢出器之靈敏度是否恰當","D",null,[],false,"本題考點：差動式分布型（空氣管式）探測器數項性能試驗的分工，接點水高試驗量的是檢出部接點閉合時的水位。\n【正解理由】依《消防安全設備測試報告書測試方法及判定要領》火警自動警報設備之性能試驗，差動式分布型（空氣管式）之「接點水高試驗」，係將流體壓力表及測試幫浦接在檢出部之試驗孔或空氣管之一端，再將試驗旋塞對合接點水高試驗位置，緩緩注入空氣，測定接點閉合時之水位；其判定要領為「接點閉合時之水位應在各檢出部所標示之值的範圍內」。所測得的水位即為使檢出部接點閉合所需之空氣壓力，落在標示值範圍內即代表該檢出部接點的動作靈敏度恰當，故選 D。\n【逐項排除】\n(A) 空氣管有無阻塞或洩漏是「流通試驗」的事；該試驗以測試幫浦注入空氣使流體壓力表水位上升至約 100mm 後停止，測定上昇水位降至 1\u002F2 為止之時間，並載明水位不停止者，空氣管有外漏之虞，應中止試驗。\n(B) 空氣管長度是否恰當同樣看流通試驗，其判定係依空氣管長度對照表所定之數值範圍，不是接點水高試驗的判定項目。\n(C) 接點水高試驗的判定項目只有接點閉合時之水位，檢出部排氣孔之狀況並不在其判定範圍內。\n(D) 判定要領要求接點閉合時之水位在各檢出部所標示之值的範圍內，量的正是檢出部接點的動作靈敏度，敘述正確。\n【記憶點】空氣管本身通不通看流通試驗，檢出部接點靈不靈敏看接點水高試驗。","差動式分布型（空氣管式）在《消防安全設備測試報告書測試方法及判定要領》火警自動警報設備性能試驗裡有四項試驗，四項各管一件事，把它們分清楚就能一次答對整組題。其一是火災動作試驗：把測試幫浦接在檢出部之試驗孔上，將試驗旋塞對合動作試驗位置，注入相當於探測器動作空氣壓（空氣膨脹壓力）之空氣量，測定自該時點至接點閉合為止之時間，判定為應在該檢出部所標示之範圍內。其二是動作持續試驗：在動作試驗中，測定探測器開始動作之後至接點開放為止之時間，同樣應在該檢出部所標示之範圍內。其三是流通試驗：把流體壓力表接在檢出部之試驗孔或空氣管之一端，將試驗旋塞對合流通試驗位置，由另端測試幫浦注入空氣使水位上升至約 100mm 後停止，再以試驗旋塞打開送氣口，測定上昇水位降至 1\u002F2 為止之時間，依空氣管內徑與空氣管長度之對照表判定。其四即本題的接點水高試驗，判定值是接點閉合時之水位。\n同屬差動式分布型，熱電偶式與熱半導體式走的是另一組試驗：動作試驗（把試驗器插頭插進檢出部，附加電壓，測定動作時之電壓）與回路合成阻抗試驗，判定值也都掛在各檢出部所標示之值。熱半導體式若安裝位置之高度未滿 8m，得依差動式局限型動作試驗之測試方法辦理。\n設置面的規定則在《各類場所消防安全設備設置標準》第 121 條第一款：空氣管式每一探測區域內之空氣管長度，露出部分在二十公尺以上；裝接於一個檢出器之空氣管長度在一百公尺以下；空氣管裝置在裝置面下方三十公分範圍內；裝置在自裝置面任一邊起一點五公尺以內之位置，其間距在防火構造建築物為九公尺以下、其他建築物為六公尺以下。判定要領的外觀試驗還補了施工細節：檢出部不得前後傾斜 5 度以上、不同檢出部之空氣管平行鄰接時相互間隔應在 1.5m 以內、直線部分以 0.35m 以內之間隔固定、接續或彎曲部分以 5cm 以內之間隔固定、彎曲半徑應在 5mm 以上、空氣管應使用接續管接續並予焊接。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-alarm-evacuation-037","有關第三種偵煙局限型探測器之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不符？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-alarm-evacuation-039","某捷運高架車站，因地形環境因素致車站早晚霧氣瀰漫，為防止霧氣結露產生探測器誤動作，選設之探測器除考量防水性能外，試問下列何者探測器不適用？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-alarm-evacuation-036","依住宅用火災警報器設置辦法規定，住宅用火災警報器應安裝於寢室、廚房、樓梯。若非屬前三類處所且任一樓層有超過 X 平方公尺之居室達 Y 間以上者，則設於走廊。則 X、Y 分別為何？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-alarm-evacuation-040","依據火警探測器認可基準，對於差動式探測器直線上升的動作試驗，自室溫狀態下以平均每分鐘 T℃直線升溫速度之水平氣流吹向時，應在 M 分鐘以內動作，下列敘述何者正確？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-alarm-evacuation-035","某揚聲器額定輸出功率 10 W，量測其額定功率之音響功率位準為 98 dB，試問依緊急廣播設備用揚聲器認可基準規定，採性能設計之緊急廣播設備揚聲器，於該揚聲器上所標示之音響功率位準（1 W）應為多少 dB？",35,{"webId":49,"stem":50,"number":51,"year":52,"session":12},"fire-114-1-alarm-evacuation-004","某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",4,114,[54,58,62,66,70],{"webId":55,"year":56,"stem":57,"number":13},"fire-112-1-alarm-evacuation-038",112,"有關通報試驗蓄積語音訊息之性能試驗，依據一一九火災通報裝置測試報告書判定要領，下列敘述何者錯誤？",{"webId":59,"year":60,"stem":61,"number":13},"fire-111-1-alarm-evacuation-038",111,"依消防安全設備及必要檢修項目檢修基準，針對緩降機之下降空間進行外觀檢查時，確認有無妨礙下降之物品，及有無確保下降必要之空間，下列何者錯誤？",{"webId":63,"year":64,"stem":65,"number":13},"fire-110-1-alarm-evacuation-038",110,"特別安全梯排煙室設置直接面向戶外之窗戶時，窗戶之有效開口面積應在多少平方公尺以上？",{"webId":67,"year":68,"stem":69,"number":13},"fire-109-1-alarm-evacuation-038",109,"有關應設置緊急照明設備之場所，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":71,"year":72,"stem":73,"number":13},"fire-108-1-alarm-evacuation-038",108,"依各類場所消防安全設備設置標準規定，特別安全梯及緊急昇降機間兼用排煙室時排煙閘門面積為 4 m2，忽略溫度的影響，測試點量得的平均風速 V(m\u002Fsec)應為多少以上為合格？",1785129962881]