[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-alarm-evacuation-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-警報與避難系統消防安全設備概要-034","fire-113-1-alarm-evacuation-034",113,1,34,"依據消防安全設備及必要檢修項目檢修基準，針對 119 火災通報裝置本體實施性能檢查，其中以火警自動警報設備連動啟動將一區段蓄積語音送出後，再操作手動啟動裝置，應能再送出蓄積語音，此為下列何種檢查項目？",{"A":16,"B":17,"C":18,"D":19},"優先通報機能","通報自始播放機能","手動啟動裝置優先機能","再撥號機能","C",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》一一九火災通報裝置本體性能檢查各機能項目的辨識。\n【正解理由】該章二、性能檢查（二）通報裝置本體第 5 項「手動啟動裝置優先機能（限與火警自動警報設備連動者）」，檢查方法為連動啟動使蓄積語音送出時操作手動啟動裝置後確認狀況，判定方法為「因連動啟動將一區段蓄積語音送出後，再操作手動啟動裝置，應能再送出蓄積語音」，與題幹敘述逐字相符，故選 C。\n【逐項排除】\n(A) 優先通報機能是把電話回路以試驗機等方式成為通話狀態後啟動，判定為應正常送出蓄積語音，該回路連接之電話機有使用中時應能強制切斷、優先送出蓄積語音，重點在對既有通話的優先。\n(B) 通報自始播放機能是以試驗機之消防機關側電話機應答，確認蓄積語音須為自始播放或一區段之蓄積語音須完整、明瞭及清晰，重點在語音的完整性。\n(C) 正確，即上述第 5 項所定之判定方法。\n(D) 再撥號機能是使試驗機之消防機關側電話機於通話狀態，操作手動啟動或連動啟動後確認應能自動再撥號，重點在撥號動作而非再送語音。\n【記憶點】連動送完一段語音後、手動再按能再送一次，考的就是手動啟動裝置優先機能。","一一九火災通報裝置在《設置標準》第 9 條被列為警報設備五種之一，設置規定在第 145-1 條，共六款：應具手動及自動啟動功能；應設於值日室等經常有人之處所，但設有防災中心時應設於該中心；設置遠端啟動裝置時應設有可與設置該裝置場所通話之設備；手動啟動裝置之操作開關距離樓地板面之高度在零點八公尺以上一點五公尺以下；裝置附近應設置送、收話器並與其他內線電話明確區分；應避免斜裝置並採取有效防震措施。\n\n檢修基準對通報裝置本體的性能檢查共列八項：保險絲類、啟動機能（再分手動啟動裝置與連動啟動）、優先通報機能、通報自始播放機能、手動啟動裝置優先機能、蓄積語音訊息、再撥號機能、通話機能。八項中有四項都會操作啟動裝置，差別在「觀察的是什麼」：優先通報機能觀察的是既有通話能否被強制切斷、蓄積語音能否優先送出；通報自始播放機能觀察的是語音是否自始播放且完整明瞭清晰；手動啟動裝置優先機能觀察的是連動送出一段語音後手動再啟動能否再送一次；再撥號機能觀察的是消防機關側忙線時能否自動再撥號。第 8 項通話機能又細分三小項：蓄積語音送出後之回撥應答狀況（自動開放二十秒時間的電話回路，由消防機關側送出回撥信號確認應答）、不應答時的繼續通報狀態（消防機關側保持不應答時應繼續送出蓄積語音）、切換狀況（蓄積語音通訊中以手動操作切換電話回路為送話機側，應能使語音通報停止並相互通話）。\n\n啟動機能兩小項的判定方法都是「通報裝置動作時，以中文字幕或國語音效顯示」，這也是常見的填空考點。延伸方面，第 236 條把一一九火災通報裝置列入消防安全設備緊急供電系統配線應施予耐燃或耐熱保護之設備種類表中；同一設備若與防災監控系統綜合操作裝置併設，其監控項目則回到第 192-1 條所列九款設備的架構去理解。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-alarm-evacuation-033","某餐廳使用瓦斯燃料，其成分為甲烷（CH4）占 10%、乙烷（C2H6）占 40%、丙烷（C3H8）占 50%，設置有瓦斯漏氣火警自動警報設備。今針對瓦斯漏氣檢知器實施外觀與性能檢查，下列何者正確？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-alarm-evacuation-035","某揚聲器額定輸出功率 10 W，量測其額定功率之音響功率位準為 98 dB，試問依緊急廣播設備用揚聲器認可基準規定，採性能設計之緊急廣播設備揚聲器，於該揚聲器上所標示之音響功率位準（1 W）應為多少 dB？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-alarm-evacuation-032","依據消防安全設備及必要檢修項目檢修基準，針對瓦斯漏氣火警自動警報設備實施綜合檢查，其中切換成預備電源之狀態，使任一檢知器動作，確認其性能是否正常。此為下列何種檢查項目？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-alarm-evacuation-036","依住宅用火災警報器設置辦法規定，住宅用火災警報器應安裝於寢室、廚房、樓梯。若非屬前三類處所且任一樓層有超過 X 平方公尺之居室達 Y 間以上者，則設於走廊。則 X、Y 分別為何？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-alarm-evacuation-031","避難器具於竣工查驗時，針對固定架或支固器具使用螺栓固定實施性能試驗，為確認螺栓對拉出之耐力，進行拉拔強度試驗。今使用直徑 10 毫米錨定螺栓，設計拉拔荷重（試驗荷重）為 960 公斤力（kgf），使用扭力扳手作為測定拉拔荷重之器具時，則鎖緊扭力應為多少公斤力-公分（kgf．cm）？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-alarm-evacuation-037","有關第三種偵煙局限型探測器之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不符？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-alarm-evacuation-034",112,"有關無線電通信輔助設備無線電接頭之外觀試驗，依據無線電通信輔助設備測試報告書判定要領，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-034",111,"二氧化碳滅火系統全區放射的空間，以往造成人員死傷之動作噴發，與防護空間下列因素何者無關？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-034",110,"依消防安全設備及必要檢修項目檢修基準，救助袋進行開口部外觀檢查時，開口部面積之限制，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-034",109,"有關排煙設備綜合檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-034",108,"依各類場所消防安全設備設置標準之規定，下列何種避難器具的開口面積應為高 60 公分以上，寬 60 公分以上？",1785129962829]