[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-alarm-evacuation-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-警報與避難系統消防安全設備概要-029","fire-113-1-alarm-evacuation-029",113,1,29,"有關特別安全梯與緊急昇降機間排煙室兼用時，其排煙設備採機械排煙、自然進風方式，則排煙機之排煙量應在 X m3\u002Fsec 以上；直接面向戶外之進風口開口面積應在 Y m2 以上則 X、Y 各為多少？",{"A":16,"B":17,"C":18,"D":19},"X=4；Y=2","X=6；Y=1","X=4；Y=3","X=6；Y=1.5","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 189 條第二款「設置排煙、進風風管」時，特別安全梯排煙室與緊急昇降機間兼用之排煙量與進風口開口面積。\n【正解理由】第 189 條第二款第四目明定「排煙機、進風機之排煙量、進風量在每秒四立方公尺（兼用時，每秒六立方公尺）以上」，本題為兼用，X＝6；同款第三目明定進風口「位於天花板高度二分之一以下之範圍內；其直接面向戶外，開口面積在一平方公尺（兼用時，為一點五平方公尺）以上」，本題採自然進風且直接面向戶外並為兼用，Y＝1.5，故選 D。\n【逐項排除】\n(A) X＝4 是非兼用時之排煙量；Y＝2 是同條第一款第三目「窗戶之有效開口面積在二平方公尺以上」，屬設置直接面向戶外窗戶之方式，與本題採風管方式不符。\n(B) X＝6 正確，但 Y＝1 是非兼用時直接面向戶外進風口之開口面積。\n(C) X＝4 為非兼用時之排煙量；Y＝3 是第一款第三目但書兼用時窗戶之有效開口面積三平方公尺。\n(D) 兩個數值均與第 189 條第二款第三目、第四目括號內之兼用值相符。\n【記憶點】第 189 條的兼用值全在括號裡：排煙量每秒四對六立方公尺，戶外進風口一對一點五平方公尺，窗戶二對三平方公尺。","第 189 條的體例是「二擇一」：第一款走自然方式，設置直接面向戶外之窗戶，要求排煙時窗戶與煙接觸部分使用不燃材料、有效開口面積位於天花板高度二分之一以上之範圍內、有效開口面積在二平方公尺以上（兼用三平方公尺以上），平時關閉之窗戶並設手動開關裝置，操作部分設於距離樓地板面八十公分以上一百五十公分以下之牆面並標示簡易操作方式。第二款走風管方式，六目依序規範不燃材料、貫穿防火區劃處設防火閘門、排煙口位於天花板高度二分之一以上而進風口位於二分之一以下、排煙量與進風量、手動開關裝置及探測器連動自動開關裝置、以及連接緊急電源且供電容量應供其有效動作三十分鐘以上。本題「機械排煙、自然進風」正落在第二款：排煙側用排煙機，進風側走「直接面向戶外」的開口而非進風風管，因此排煙量取第四目、開口面積取第三目前段。\n\n第三目的關鍵在於「或」：進風口有兩條互斥路徑，一是直接面向戶外並有一平方公尺（兼用一點五平方公尺）以上之開口面積，二是與直接連通戶外之進風風管連接並接進風機。走風管那條時，該目並未對開口面積另定數值，判讀時要先確認題目走的是哪一條。\n\n此設備的應設依據是第 28 條第一項第五款「依建築技術規則應設置之特別安全梯或緊急昇降機間」。與之對照的《建築技術規則建築設計施工編》第 102 條同樣採兼用加碼的體例：可開向戶外之窗戶不得小於二平方公尺、兼用不得小於三平方公尺；未設窗戶時排煙口面積四平方公尺以上、兼排煙室使用時六平方公尺以上；排煙管道內部斷面積不得小於六平方公尺、兼用不得小於九平方公尺；進風口開口面積不得小於一平方公尺、兼用不得小於一點五平方公尺，進風管道內部斷面積不得小於二平方公尺、兼用不得小於三平方公尺；設有每秒鐘可進、排四立方公尺以上並可隨進風口與排煙口開啟而自動操作之進風機、排煙機者，得不受第二款、第三款、第五款之限制。另一組容易混用的數值是第 188 條的室內排煙設備，排煙機之排煙量在每分鐘一百二十立方公尺以上，單位是每分鐘而非每秒，作答時先看單位再看數字。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-alarm-evacuation-028","依消防安全設備及必要檢修項目檢修基準，針對防災監控系統綜合操作裝置進行性能檢查，有關消防搶救支援性能項目，於 LCD 螢幕應能針對下列各樓層平面圖，以簡明易操作之方式切換其表示。所敘述之樓層平面圖下列何者錯誤？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-alarm-evacuation-030","某建築物於第五層開設健身休閒中心，依法應設置排煙設備。惟於該場所內之衣帽間規劃免設排煙設備，試問符合下列何種條件方得免設？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-alarm-evacuation-027","有關出口標示燈、避難方向指示燈與緊急照明燈之緊急電源規定，下列敘述何者正確？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-alarm-evacuation-031","避難器具於竣工查驗時，針對固定架或支固器具使用螺栓固定實施性能試驗，為確認螺栓對拉出之耐力，進行拉拔強度試驗。今使用直徑 10 毫米錨定螺栓，設計拉拔荷重（試驗荷重）為 960 公斤力（kgf），使用扭力扳手作為測定拉拔荷重之器具時，則鎖緊扭力應為多少公斤力-公分（kgf．cm）？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-alarm-evacuation-026","依規定出口標示燈及避難方向指示燈，應保持不熄滅。惟為配合政府機關推動節能減碳措施，除上述燈具採用省電產品外，出口標示燈及走廊通道避難方向指示燈，符合下列何者規定，得予減光或消燈？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-alarm-evacuation-032","依據消防安全設備及必要檢修項目檢修基準，針對瓦斯漏氣火警自動警報設備實施綜合檢查，其中切換成預備電源之狀態，使任一檢知器動作，確認其性能是否正常。此為下列何種檢查項目？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-alarm-evacuation-029",112,"某建築物總樓地板面積在 5 萬平方公尺以上其主要避難路徑的地方，該出口標示燈及避難方向指示燈之緊急電源容量應在 60 分鐘以上，下列場所何者不是主要避難路徑？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-029",111,"緩降機為顧及使用之安全，裝置時應考慮之位置下列何者為佳？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-029",110,"有關瓦斯漏氣檢知器之設置，當瓦斯對空氣之比重小於 1 時，應設於距瓦斯燃燒器具水平距離 A 公尺以內；當瓦斯對空氣之比重大於 1 時，應設於距瓦斯燃燒器具水平距離 B 公尺以內，其中 A 及 B 分別為：",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-029",109,"有關瓦斯漏氣火警自動警報設備檢知器外觀檢查選取之檢查數量，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-029",108,"消防安全設備測試報告書測試方法及判定要領中規定，火警自動警報設備外觀試驗，其定溫式感知線型探測器之判定要領中，下列何者正確？",1785129962784]