[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-alarm-evacuation-012":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-警報與避難系統消防安全設備概要-012","fire-113-1-alarm-evacuation-012",113,1,12,"當火警發信機兼作其他消防安全設備之啟動裝置者，有關火警自動警報設備之配線保護規定，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"火警發信機與受信總機間之配線應採耐熱保護","火警發信機與受信總機間之配線得採一般配線","標示燈回路與受信總機間之配線應採耐熱保護","定址式火警發信機與受信總機間之配線應採耐熱保護","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第二百三十六條附表就火警自動警報設備配線耐燃、耐熱保護範圍所加之附註一。\n【正解理由】依第二百三十六條，消防安全設備緊急供電系統之配線，依該條附表之區分施予耐燃保護或耐熱保護；該表就火警自動警報設備所附之註一明定「火警發信機兼作其他消防安全設備之啟動裝置者：標示燈回路應採耐熱保護」。可知在此情形下被拉高為耐熱保護者是「標示燈回路」，火警發信機與受信總機間之回路並未因此改採耐熱保護，A 之敘述與該註不符，即為錯誤者，故選 A。\n【逐項排除】\n(A) 註一所指應採耐熱保護之對象為標示燈回路，而非火警發信機與受信總機間之配線，敘述錯誤。\n(B) 火警發信機與受信總機間之配線，於該表列為得採一般配線者，敘述正確。\n(C) 與註一所定「標示燈回路應採耐熱保護」相符，敘述正確。\n(D) 定址式火警發信機與受信總機間之回路，於該表列為應施耐熱保護者，敘述正確。\n【記憶點】火警發信機兼作其他設備啟動裝置時，被拉高到耐熱保護的是標示燈回路，不是火警發信機本身那條回路。","第二百三十五條與第二百三十六條是一組。第二百三十五條先定通則：電氣配線應設專用回路，不得與一般電路相接，且開關有消防安全設備別之明顯標示；緊急用電源回路及操作回路使用六百伏特耐熱絕緣電線，或同等耐熱效果以上之電線；電源回路之配線施予耐燃保護，作法為電線裝於金屬導線管槽內並埋設於防火構造物之混凝土內，混凝土保護厚度為二十毫米以上，但在使用不燃材料建造且符合建築技術規則防火區劃規定之管道間得免埋設，使用 MI 電纜或耐燃電纜時得按電纜裝設法直接敷設；標示燈回路及控制回路之配線則施予耐熱保護，作法為電線於金屬導線管槽內裝置，使用 MI 電纜、耐燃電纜或耐熱電線電纜時得按電纜裝設法直接敷設。第二百三十六條再以附表逐設備標出耐燃、耐熱保護之範圍，火警自動警報設備列於該表第 4 項。\n該表附有三個註，三者都是把表格本文的原則再往下切一層，考點常出在這裡。註一即本題所考：火警發信機兼作其他消防安全設備之啟動裝置者，標示燈回路應採耐熱保護。註二：中繼器（亦稱模組）之緊急電源回路，中繼器內置蓄電池者，得採一般配線。註三：中繼器之控制回路，得採耐熱保護。\n《消防安全設備及必要檢修項目檢修基準》第二十七章配線之外觀檢查亦明定，耐燃、耐熱保護配線之區分應符合《各類場所消防安全設備設置標準》第二百三十六條之規定，並以表 27-1、表 27-2 分別列出耐燃配線與耐熱配線可用之電線種類及施工方法，其中六○○Ｖ耐熱聚氯乙烯絕緣電線（HIV）、聚四氟乙烯絕緣電線、鋼帶鎧裝電纜、矽橡膠絕緣電線、匯流排槽等兩表皆列，差別在施工方法：耐燃配線須埋設於混凝土內（保護厚度二十公厘以上），耐熱配線則裝於金屬導線管槽內即可。《消防安全設備測試報告書測試方法及判定要領》第二十二章配線之外觀試驗，同樣把判定要領指回第二百三十六條，三份文件的判準一致。\n延伸考點：電源回路走耐燃保護、標示燈回路與控制回路走耐熱保護，是本科反覆出現的骨幹；再加上三個註的例外，幾乎可以涵蓋歷年配線題的出題面。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-alarm-evacuation-011","某一場所設有一 A 級出口標示燈，其縱向尺度為 0.8 公尺，且未顯示避難方向符號者，請問其步行距離應為多少公尺？",11,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-alarm-evacuation-013","下列緊急廣播設備之配線規定，除依用戶用電設備裝置規則外，依下列規定設置，何者錯誤？",13,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-alarm-evacuation-010","下列場所設置的出口標示燈及非設於樓梯或坡道之避難方向指示燈，何者符合規定之要求？",10,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-alarm-evacuation-014","某社區活動中心位於建築物第 2 層（非避難層），經檢討該活動中心為有開口樓層，依規定自活動中心任一點易於觀察識別其主要出入口，且與主要出入口之步行距離分別在 X 公尺以下，得免設出口標示燈；步行距離在 Y 公尺以下，得免設避難方向指示燈，則 X+Y=？",14,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-alarm-evacuation-009","出口標示燈及避難方向指示燈之緊急電源應使用蓄電池設備，其容量應能使其有效動作 20 分鐘以上。但設於下列場所之主要避難路徑，該容量應在 60 分鐘以上，並得採蓄電池設備及緊急發電機併設方式，以下場所何者錯誤？",9,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-alarm-evacuation-015","瓦斯洩漏時檢知器設置位置將會影響其探測性能，依據消防安全設備及必要檢修項目檢修基準之規定，來判定瓦斯漏氣檢知器設置場所及設置位置，下列何者為適合的設置場所？",15,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-alarm-evacuation-012",112,"有關出口標示燈及避難方向指示燈，在沒有不易看清或識別該燈情形的條件，依據各類場所消防安全設備設置標準，下列有效範圍何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-012",111,"某餐廳廚房之瓦斯爐具使用天然氣作為燃料時，依法設有瓦斯漏氣火警自動警報設備，其瓦斯漏氣檢知器應設於距瓦斯爐具水平距離 X 公尺以內，且於該水平距離內之天花板無淨高 Y 公分以上之樑或類似構造體區隔之吸氣口 Z 公尺範圍內，試問Ｘ、Ｙ、Z 分別為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-012",110,"建築物某一樓層（A 區）通往直通樓梯（B 區）的出口標示燈（L）附有誘導音裝置，並設置有停止專用偵煙式探測器（D）及具有緊急廣播設備連動停止性能，在其性能試驗之連動停止試驗中，下列何者應判定不合格？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-012",109,"有關緊急電源插座之設置規定，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-012",108,"有關依各類場所消防安全設備設置標準規定設置之耐燃保護、耐熱保護措施，室內消防栓、室外消防栓、自動撒水、水霧、泡沫、乾粉、二氧化碳滅火設備、連結送水管設備等之配管，於實施施工、加壓試驗及配合建築物樓地板、樑、柱、牆施工須預埋消防管線時，消防專技人員何人應一併拍照建檔存證以供消防機關查核，消防機關並得視需要隨時派員前往查驗？",1785129962607]