[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-113-1-alarm-evacuation-006":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-警報與避難系統消防安全設備概要-006","fire-113-1-alarm-evacuation-006",113,1,6,"依據各類場所消防安全設備設置標準之規定，避難器具於開口部應保有必要開口面積，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"緩降機開口部高與寬的加總最小值為 130 公分","救助袋開口部高與寬的加總最小值為 130 公分","滑臺開口部高度為 80 公分以上，寬為滑臺最大寬度以上","避難繩索開口部高與寬的加總最小值為 130 公分","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 162 條，避難器具於開口部應保有之必要開口面積表。\n【正解理由】第 162 條的表把避難器具分成四列：緩降機、避難梯、避難繩索及滑杆為「高八十公分以上，寬五十公分以上或高一百公分以上，寬四十五公分以上」；救助袋為「高六十公分以上，寬六十公分以上」；滑臺為「高八十公分以上，寬為滑臺最大寬度以上」；避難橋為「高一百八十公分以上，寬為避難橋最大寬度以上」。救助袋高與寬加總的最小值是六十加六十等於一百二十公分，並非一百三十公分，故選 B。\n【逐項排除】\n(A) 緩降機在第一列，八十加五十為一百三十、一百加四十五為一百四十五，最小加總一百三十公分，敘述正確。\n(B) 救助袋為高六十公分以上、寬六十公分以上，最小加總一百二十公分，與選項所寫一百三十公分不符，為本題答案。\n(C) 滑臺為高八十公分以上、寬為滑臺最大寬度以上，與表列逐字相符。\n(D) 避難繩索與緩降機、避難梯、滑杆同列，最小加總同為一百三十公分，敘述正確。\n【記憶點】救助袋開口是高寬各六十公分、加總一百二十；緩降機、避難梯、避難繩索及滑杆同列，最小加總一百三十公分。","避難器具的規格條文是《各類場所消防安全設備設置標準》第 161 條至第 165 條一組，順序依次為裝設、開口面積、操作面積、下降空間、下降空地，四張表的分列方式一致，救助袋每一張都自成一列。第 161 條列裝設五款：設在避難時易於接近處；與安全梯等避難逃生設施保持適當距離；供避難器具使用之開口部具有安全之構造；避難器具平時裝設於開口部或必要時能迅即裝設於該開口部；設置避難器具（滑杆、避難繩索及避難橋除外）之開口部，上下層應交錯配置不得在同一垂直線上，但在避難上無障礙者不在此限。\n第 163 條的操作面積：緩降機、避難梯、避難繩索及滑杆為零點五平方公尺以上（不含避難器具所佔面積），但邊長應為六十公分以上；救助袋為寬一百五十公分以上、長一百五十公分以上（含器具所佔面積），但無操作障礙且操作面積在二點二五平方公尺以上時不在此限；滑臺、避難橋則依避難器具大小及形狀留置。第 164 條的下降空間：緩降機以器具中心半徑零點五公尺圓柱形範圍內；避難梯自二側豎桿中心線向外二十公分以上及其前方六十五公分以上之範圍內；避難繩索及滑杆為無避難障礙之空間；救助袋斜降式在下方及側面上端二十五度、下端三十五度方向所圍範圍內，直降式與牆壁之間隔為三十公分以上並以救助袋中心半徑一公尺圓柱形範圍內；滑臺為滑面上方一公尺以上及滑臺兩端向外二十公分以上；避難橋為避難橋之寬度以上及橋面上方二公尺以上。第 165 條的下降空地：緩降機、避難梯與救助袋直降式為下降空間之投影面積；避難繩索及滑杆為無避難障礙之空地；救助袋斜降式為最下端起二點五公尺及其中心線左右一公尺以上所圍範圍；滑臺為前端起一點五公尺及其中心線左右零點五公尺所圍範圍；避難橋為無避難障礙之空地。\n往前追，避難器具的種類定義在第 10 條第二款：滑臺、避難梯、避難橋、救助袋、緩降機、避難繩索、滑杆及其他避難器具；第 25 條則規定建築物除十一層以上樓層及避難層外，各樓層應選設上述器具或經中央主管機關認可具同等性能者。減設與免設另見第 158 條、第 159 條。整組條文裡救助袋的數值與緩降機那一列全不相同，是最容易記混的地方。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-alarm-evacuation-005","依據現行出口標示燈及避難方向指示燈認可基準，對於內置型引導燈具相關試驗等標準，何者錯誤？",5,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-alarm-evacuation-007","醫療機構中的 3 樓，經容納病床數量、從業員工與相關區域之樓地板面積等相關條件評估後，其收容人數為 550 人，該樓層在無減設、免設考量下，至少應設多少具避難器具？",7,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-alarm-evacuation-004","工業廠房設置機械排煙設備，其中特別安全梯與緊急升降機間兼用排煙室，該區域排煙閘門大小為 6 m2，並連接排煙管道時，不考慮溫度影響之因素，請問排煙風速（m\u002Fs）應達多少才能符合其法令規定？",4,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-alarm-evacuation-008","某醫學中心的 7 樓在考量避難器具選設的種類中，下列避難器具不適合？",8,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-113-1-alarm-evacuation-003","下列場所不得免設排煙設備？",3,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-alarm-evacuation-009","出口標示燈及避難方向指示燈之緊急電源應使用蓄電池設備，其容量應能使其有效動作 20 分鐘以上。但設於下列場所之主要避難路徑，該容量應在 60 分鐘以上，並得採蓄電池設備及緊急發電機併設方式，以下場所何者錯誤？",9,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-112-1-alarm-evacuation-006",112,"有關室內排煙綜合試驗之排煙風量測試，依據排煙設備測試報告書判定要領，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-alarm-evacuation-006",111,"探測器依其工作原理，下列探測器何者具有搜集環境變異之功能，並採數位通訊方式傳回總機，再由總機根據歷史紀錄來決定是否作動？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-alarm-evacuation-006",110,"緊急廣播設備在樓梯或斜坡通道以外之場所，其設置之揚聲器採性能設計時，在揚聲器標示上如加註下列那二種項目者，該廣播區域內任一點至揚聲器之水平距離方可不受到 10 公尺以下的限制？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-alarm-evacuation-006",109,"差動式局限型探測器進行性能檢查時，使用加熱式試驗器加熱確認動作時間，加熱後到探測器動作應在多少時間以內？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-alarm-evacuation-006",108,"探測器應依裝置場所高度選擇探測器種類裝設，下列何者錯誤？",1785129962550]