[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-113-1-alarm-evacuation-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-113-1-警報與避難系統消防安全設備概要-004","fire-113-1-alarm-evacuation-004",113,1,4,"工業廠房設置機械排煙設備，其中特別安全梯與緊急升降機間兼用排煙室，該區域排煙閘門大小為 6 m2，並連接排煙管道時，不考慮溫度影響之因素，請問排煙風速（m\u002Fs）應達多少才能符合其法令規定？",{"A":16,"B":17,"C":18,"D":19},"1","0.5","0.25","0.1","A",null,[],false,"本題考點：特別安全梯與緊急昇降機間兼用之排煙室，採排煙、進風風管方式時的排煙量下限，再由閘門面積換算風速。\n【正解理由】依《各類場所消防安全設備設置標準》第 189 條第二款第四目，排煙機、進風機之排煙量、進風量在每秒四立方公尺（兼用時，每秒六立方公尺）以上。題示為特別安全梯與緊急昇降機間兼用之排煙室並連接排煙管道，排煙量下限為每秒六立方公尺；以排煙閘門面積六平方公尺除之，風速下限為每秒一公尺，故選 A。\n【逐項排除】\n(A) 每秒一公尺，即每秒六立方公尺除以六平方公尺，正好等於兼用時的下限。\n(B) 每秒零點五公尺換回排煙量僅每秒三立方公尺，未達兼用時之每秒六立方公尺。\n(C) 每秒零點二五公尺換回排煙量僅每秒一點五立方公尺，同樣未達下限。\n(D) 每秒零點一公尺換回排煙量僅每秒零點六立方公尺，與條文所定相差一個數量級。\n【演算步驟】排煙量 Ｑ＝風速 v × 閘門面積 A；兼用時 Ｑ ≥ 6 m³／s，A ＝ 6 m²；v ＝ Ｑ ÷ A ＝ 6 m³／s ÷ 6 m² ＝ 1 m／s。\n【記憶點】特別安全梯排煙室每秒四立方公尺，與緊急昇降機間兼用時每秒六立方公尺。","《各類場所消防安全設備設置標準》第 189 條專門處理特別安全梯或緊急昇降機間排煙室的排煙設備，體例是「依下列規定選擇設置」，兩款各是一條完整路徑。第一款走直接面向戶外之窗戶：排煙時窗戶與煙接觸部分使用不燃材料；窗戶有效開口面積位於天花板高度二分之一以上之範圍內；有效開口面積在二平方公尺以上，但兼用時應在三平方公尺以上；平時關閉之窗戶設手動開關裝置，操作部分設於距離樓地板面八十公分以上一百五十公分以下之牆面並標示簡易之操作方式。\n第二款走排煙、進風風管：排煙口、排煙風管、進風口、進風風管及其他與煙接觸部分應使用不燃材料；風管貫穿防火區劃時應在貫穿處設防火閘門，跨樓層設置時立管應置於防火區劃之管道間；排煙口位於天花板高度二分之一以上之範圍內，與直接連通戶外之排煙風管連接，該風管並連接排煙機；進風口位於天花板高度二分之一以下之範圍內，其直接面向戶外者開口面積在一平方公尺（兼用時，為一點五平方公尺）以上，或與直接連通戶外之進風風管連接而該風管連接進風機。第四目就是本題的計算依據：排煙機、進風機之排煙量、進風量在每秒四立方公尺（兼用時，每秒六立方公尺）以上，且可隨排煙口、進風口開啟而自動啟動。第六目另定排煙口、進風口、排煙機及進風機連接緊急電源，其供電容量應供其有效動作三十分鐘以上。\n計算上用的是體積流率等於截面積乘流速這條關係，單位上立方公尺每秒除以平方公尺正好得到公尺每秒，所以題目只要給定閘門面積就能反推風速下限。命題者把閘門面積設成六平方公尺，讓兼用時的每秒六立方公尺除下來剛好是整數一。若同題改成非兼用，下限即為每秒四立方公尺，同樣面積算出的風速下限為每秒約零點六七公尺。與本條相關的還有第 28 條第一項第五款把依建築技術規則應設置之特別安全梯或緊急昇降機間列為應設排煙設備之場所，以及建築技術規則建築設計施工編第 107 條第一款第四目要求緊急用昇降機之機間應設置排煙設備。",true,[28,32,36,40,44,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-113-1-alarm-evacuation-003","下列場所不得免設排煙設備？",3,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-alarm-evacuation-005","依據現行出口標示燈及避難方向指示燈認可基準，對於內置型引導燈具相關試驗等標準，何者錯誤？",5,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-113-1-alarm-evacuation-002","對於緊急電源插座距離樓地板的裝設高度範圍，下列何者正確？",2,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-alarm-evacuation-006","依據各類場所消防安全設備設置標準之規定，避難器具於開口部應保有必要開口面積，下列敘述何者錯誤？",6,{"webId":45,"stem":46,"number":12,"year":11,"session":12},"fire-113-1-alarm-evacuation-001","為能有效排除火場中的濃煙，必須定期確保排煙設備之有效性，依據排煙設備檢修基準之要求，進行排煙設備的相關檢查時，下列敘述何者錯誤？",{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-113-1-alarm-evacuation-007","醫療機構中的 3 樓，經容納病床數量、從業員工與相關區域之樓地板面積等相關條件評估後，其收容人數為 550 人，該樓層在無減設、免設考量下，至少應設多少具避難器具？",7,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-alarm-evacuation-004",114,"某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",{"webId":57,"year":58,"stem":59,"number":13},"fire-112-1-alarm-evacuation-004",112,"依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",{"webId":61,"year":62,"stem":63,"number":13},"fire-111-1-alarm-evacuation-004",111,"某建築物火警自動警報設備之鳴動方式依規定採分區鳴動，在分區鳴動經多少分鐘內或受信總機再接受火災信號時，應立即全區鳴動？",{"webId":65,"year":66,"stem":67,"number":13},"fire-110-1-alarm-evacuation-004",110,"有一棟總樓地板面積 4,000 平方公尺的七層辦公建築物，當起火層為地上第二層時，下列有關其火警自動警報設備分區鳴動方式的敘述，何者正確？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-alarm-evacuation-004",109,"某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",1785129962514]