[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-113-1-alarm-evacuation-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-113-1-警報與避難系統消防安全設備概要-001","fire-113-1-alarm-evacuation-001",113,1,"為能有效排除火場中的濃煙，必須定期確保排煙設備之有效性，依據排煙設備檢修基準之要求，進行排煙設備的相關檢查時，下列敘述何者錯誤？",{"A":15,"B":16,"C":17,"D":18},"排煙機啟動後，能連動吸煙口及排煙閘門開啟","綜合檢查時，醫院等切換成緊急電源進行檢查有困難之場所，應使用常用電源進行檢查","進行自動啟動裝置之性能檢查時，檢查方法為偵煙式探測器性能檢查，依照火警自動警報設備之檢查要領進行，確認探測器動作後，能否連動排煙機啟動","外觀檢查時，應注意有無室內裝修、增建改建及用途變更，並檢查排煙區劃之狀態","A",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》排煙設備的檢查內容，四個選項分散在外觀檢查、性能檢查與綜合檢查三段。\n【正解理由】依該基準排煙設備之綜合檢查，判定方法第一項為「吸煙口及排煙閘門打開後，能連動自動排煙機啟動」，動作順序是先開啟吸煙口與排煙閘門，再由其連動排煙機。選項所述為排煙機先啟動、再連動吸煙口及排煙閘門開啟，方向與該判定方法相反，故選 A。\n【逐項排除】\n(A) 把連動關係的先後倒置，與綜合檢查判定方法第一項所載相反，為本題答案。\n(B) 綜合檢查之注意事項明載「醫院等切換成緊急電源進行檢查有困難之場所，應使用常用電源進行檢查」，敘述與原文相符。\n(C) 性能檢查啟動裝置之自動啟動裝置，檢查方法為「偵煙式探測器性能檢查，依照火警自動警報設備之檢查要領進行，確認探測器動作後，能否連動排煙機啟動」，敘述正確。\n(D) 外觀檢查排煙區劃之注意事項為「確認有無室內裝修、增建改建及用途變更，並檢查排煙區劃之狀態」，敘述正確。\n【記憶點】排煙設備綜合檢查的連動順序是先開吸煙口與排煙閘門，再連動排煙機啟動。","《消防安全設備及必要檢修項目檢修基準》排煙設備分外觀檢查、性能檢查、綜合檢查三段，本題四個選項剛好散落三段，是典型的跨段命題。綜合檢查的檢查方法是切換成緊急電源的狀態，使偵煙式探測器動作及操作手動啟動裝置以確認各部分之性能；判定方法共四項：吸煙口及排煙閘門打開後能連動自動排煙機啟動、運轉電流在所規定的範圍內、排煙機運轉中應無異常聲音及振動且風道應無異常振動、排煙機回轉葉片的回轉方向應正常。注意事項則為醫院等切換成緊急電源進行檢查有困難之場所應使用常用電源進行檢查。\n性能檢查涵蓋三大塊。電動機之控制裝置查各開關、保險絲、繼電器、表示燈、結線接續與接地六項，判定上端子應無鬆動發熱、保險絲依回路圖所定種類及容量設置、繼電器應無脫落端子鬆動接點燒損灰塵附著。啟動裝置分自動與手動：自動啟動裝置依火警自動警報設備之檢查要領對偵煙式探測器進行，並確認排煙機應能確實啟動；手動啟動方式則確認手動啟動操作箱之把手及操作桿轉動與打開動作，判定為用手應能容易轉動把手、操作桿應無破損且鋼索應無斷落或生鏽。排煙機再分電動機（回轉軸、軸承部、動力傳達裝置、本體）與回轉葉片。外觀檢查的排煙區劃則分固定式垂壁與移動式垂壁，判定包含垂壁應無拆除、無顯著變形損傷龜裂，以及防火鐵捲門導槽應無損傷。\n設置面的數值可與《各類場所消防安全設備設置標準》第 188 條對讀：每層樓地板面積每五百平方公尺內以防煙壁區劃，地下建築物之地下通道每三百平方公尺區劃；防煙區劃範圍內任一位置至排煙口之水平距離在三十公尺以下，排煙口設於天花板或其下方八十公分範圍內；排煙口開口面積在防煙區劃面積百分之二以上；排煙機之排煙量在每分鐘一百二十立方公尺以上，一防煙區劃時每平方公尺每分鐘一立方公尺以上，二區以上時以最大防煙區劃面積每平方公尺每分鐘二立方公尺以上，地下通道總排煙量則在每分鐘六百立方公尺以上；緊急電源供電容量三十分鐘以上。防煙壁為自天花板下垂五十公分以上，地下通道之防煙壁則自天花板下垂八十公分以上。",true,[27,32,36,40,44,48],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-112-1-alarm-evacuation-040","依各類場所消防安全設備設置標準，醫院熱水室之場所適用選擇設置下列何種探測器？",40,112,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-113-1-alarm-evacuation-002","對於緊急電源插座距離樓地板的裝設高度範圍，下列何者正確？",2,{"webId":37,"stem":38,"number":39,"year":31,"session":12},"fire-112-1-alarm-evacuation-039","依消防安全設備及必要檢修項目檢修基準，檢查一一九火災通報裝置性能時，有關通報裝置本體檢查，下列敘述何者錯誤？",39,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-113-1-alarm-evacuation-003","下列場所不得免設排煙設備？",3,{"webId":45,"stem":46,"number":47,"year":31,"session":12},"fire-112-1-alarm-evacuation-038","有關通報試驗蓄積語音訊息之性能試驗，依據一一九火災通報裝置測試報告書判定要領，下列敘述何者錯誤？",38,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-113-1-alarm-evacuation-004","工業廠房設置機械排煙設備，其中特別安全梯與緊急升降機間兼用排煙室，該區域排煙閘門大小為 6 m2，並連接排煙管道時，不考慮溫度影響之因素，請問排煙風速（m\u002Fs）應達多少才能符合其法令規定？",4,[53,56,60,64,68],{"webId":54,"year":31,"stem":55,"number":12},"fire-112-1-alarm-evacuation-001","依據配線檢修基準性能檢查之檢查方法，有關高壓回路電源回路間及電源回路與大地間之絕緣電阻值測定，下列敘述何者錯誤？",{"webId":57,"year":58,"stem":59,"number":12},"fire-111-1-alarm-evacuation-001",111,"依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"webId":61,"year":62,"stem":63,"number":12},"fire-110-1-alarm-evacuation-001",110,"下列有關建築物火警分區之劃定，何者符合各類場所消防安全設備設置標準的規定？",{"webId":65,"year":66,"stem":67,"number":12},"fire-109-1-alarm-evacuation-001",109,"常開式之火警探測器信號回路，加設終端電阻之目的為何？",{"webId":69,"year":70,"stem":71,"number":12},"fire-108-1-alarm-evacuation-001",108,"某一新建建築物地面六層、地下二層，用途為辦公室，每層樓地板面積為 400 平方公尺，設置火警自動警報系統，假設 1 樓發生火警時，依各類場所消防安全設備設置標準規定，其鳴動方式為何？",1785129962482]