[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-water-chemical-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-040","fire-112-1-water-chemical-040",112,1,40,"有關公共危險物品場所設置自動撒水設備規定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"防護對象任一點至撒水頭之水平距離在 2.1 公尺以下","開放式撒水設備，每一放水區域樓地板面積在 100 平方公尺以上","存放易燃性物質處所，撒水頭迴水板下方 90 公分及水平方向 30 公分以內，應保持淨空間","使用開放式撒水頭時，應在最大放水區域全部撒水頭，繼續放水 45 分鐘之水量","C",null,[],false,"本題考點：公共危險物品場所（第四編）自動撒水設備之水平距離、放水區域面積、淨空間與水源容量。\n【正解理由】依《各類場所消防安全設備設置標準》第二百十一條第五款但書，公共危險物品場所存放易燃性物質處所，撒水頭迴水板下方九十公分及水平方向三十公分以內，應保持淨空間，不得有障礙物；本選項與該但書逐字相符，故選 C。\n【逐項排除】\n(A) 錯誤。第二百十一條第二款明定防護對象任一點至撒水頭之水平距離在一點七公尺以下；二點一公尺是一般場所第四十六條第二款第一目一般反應型撒水頭之水平距離。\n(B) 錯誤。第二百十一條第三款明定開放式撒水設備每一放水區域樓地板面積在一百五十平方公尺以上，防護對象樓地板面積未滿一百五十平方公尺時以實際樓地板面積計算，並非一百平方公尺。\n(C) 正確。該但書就存放易燃性物質處所另定淨空間，數值為迴水板下方九十公分及水平方向三十公分以內。\n(D) 錯誤。第二百十一條第四款第二目明定使用開放式撒水頭時，應在最大放水區域全部撒水頭繼續放水三十分鐘之水量以上；四十五分鐘是同條第二項緊急電源之有效動作時間。\n【記憶點】公危場所自動撒水記「一點七公尺、一百五十平方公尺、三十分鐘、易燃性物質淨空間九十與三十公分」。","《各類場所消防安全設備設置標準》分編適用，第二百十一條屬第四編公共危險物品等場所，只適用於公共危險物品或可燃性高壓氣體場所；辦公室、停車空間、百貨等一般場所一律走第二編、第三編，兩編的同名規定數值不同，互套就是失分主因。《公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法》第九條也明定，該類場所之消防安全設備設置依設置標準及其他有關法令規定辦理，兩部法規因此是接續關係。\n把第二百十一條與一般場所條文並列最能看出差異。水平距離方面，第二百十一條第二款為一點七公尺以下；第四十六條第一款就戲院舞臺及道具室、電影院放映室或儲存易燃物品之倉庫同為一點七公尺以下，第二款則就一般反應型撒水頭定二點一公尺以下（防火構造建築物得增加為二點三公尺以下）、快速反應型撒水頭定二點三公尺以下（防火構造建築物得增加為二點六公尺以下）。淨空間方面，第四十七條第一項第二款為迴水板下方四十五公分內及水平方向三十公分內；第二百十一條第五款但書就存放易燃性物質處所另定為下方九十公分及水平方向三十公分以內。\n水源容量也要分開記。第二百十一條第四款：使用密閉式撒水頭者，應在設置三十個撒水頭繼續放水三十分鐘之水量以上，設置撒水頭數在三十個以下者以實際撒水頭數計算；使用開放式撒水頭者，應在最大放水區域全部撒水頭繼續放水三十分鐘之水量以上；使用密閉乾式或預動式流水檢知裝置時，前二目撒水頭數量應追加十個。緊急電源除準用第三十八條規定外，供電容量應供有效動作四十五分鐘以上，這個四十五分鐘常被移花接木寫成放水時間。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-039","依各類場所消防安全設備設置標準規定，消防專用蓄水池之採水設置，下列敘述何者錯誤？",39,{"webId":33,"stem":34,"number":12,"year":35,"session":12},"fire-113-1-water-chemical-001","有關消防安全設備水源容量之放水時間，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",113,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-038","依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",38,{"webId":41,"stem":42,"number":43,"year":35,"session":12},"fire-113-1-water-chemical-002","室內停車空間設置水霧滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",2,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-037","固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，下列敘述何者錯誤？",37,{"webId":49,"stem":50,"number":51,"year":35,"session":12},"fire-113-1-water-chemical-003","公共危險物品場所設置泡沫滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",3,[53,56,60,64,68],{"webId":54,"year":35,"stem":55,"number":13},"fire-113-1-water-chemical-040","有關射水設備測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":57,"year":58,"stem":59,"number":13},"fire-111-1-water-chemical-040",111,"二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",{"webId":61,"year":62,"stem":63,"number":13},"fire-110-1-water-chemical-040",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之供第四類公共危險物品之顯著滅火困難場所之加壓送水裝置，啟動後 X 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 Y 公尺以下，但設有保壓措施者不在此限。X、Y 分別為何？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-water-chemical-040",109,"儲槽規定設置補助泡沫消防栓時，下列敘述何者錯誤？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-water-chemical-040",108,"電動機之使用應符合之相關規定，下列何者錯誤？",1785129972027]