[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-water-chemical-039":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-039","fire-112-1-water-chemical-039",112,1,39,"依各類場所消防安全設備設置標準規定，消防專用蓄水池之採水設置，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"有效水量計算，蓄水池深度得超過在基地地面下 4.5 公尺範圍內之水量","水量 40 立方公尺以上 120 立方公尺未滿，加壓送水裝置出水量 2,200(l\u002Fmin)及採水口數 3 個","加壓送水裝置應於採水口附近設啟動裝置及紅色啟動表示燈。但設有能由防災中心遙控啟動，且採水口與防災中心間設有通話連絡裝置者，不在此限","採水口接裝 63 毫米陽式快接頭，距離基地地面之高度在 1 公尺以下 0.5 公尺以上","B",null,[],false,"本題考點：消防專用蓄水池採機械方式引水時，加壓送水裝置出水量、採水口數與採水口規格之規定。\n【正解理由】依《各類場所消防安全設備設置標準》第一百八十六條第一款之表，水量在四十立方公尺以上一百二十立方公尺未滿者，出水量為二千二百公升／分，採水口數為二個；本選項寫成三個，與表列不符，故選 B。\n【逐項排除】\n(A) 正確。第一百八十五條第二項本文以蓄水池深度在基地地面下四點五公尺範圍內之水量為有效水量，但書明定採機械方式引水時不在此限，故採機械引水之採水設置得超過該深度範圍。\n(B) 錯誤。四十以上一百二十未滿之級距，表列採水口數為二個；三個係一百二十立方公尺以上之級距所對應之數量。\n(C) 正確。第一百八十六條第三款明定加壓送水裝置應於採水口附近設啟動裝置及紅色啟動表示燈，但設有能由防災中心遙控啟動，且採水口與防災中心間設有通話連絡裝置者，不在此限。\n(D) 正確。第一百八十六條第四款明定採水口接裝六十三毫米陽式快接頭，距離基地地面之高度在一公尺以下零點五公尺以上。\n【記憶點】採水表記「四十未滿→一千一百、一個；四十至一百二十未滿→二千二百、二個；一百二十以上→三千三百、三個」。","第一百八十六條專講「採機械方式引水」的情形，前提條件是除依第一百八十五條第一項第一款及第二款後段規定外，任一採水口至建築物各部分之水平距離在一百公尺以下。條文只有四款，全部都是考點：第一款是出水量與採水口數之對照表；第二款是幫浦全揚程，計算式為全揚程等於落差加配管摩擦損失水頭加 15m；第三款是採水口附近之啟動裝置及紅色啟動表示燈與其但書；第四款是採水口接頭規格與高度。\n採水口的規格在兩條之間最容易互換，要用「有沒有機械引水」來分：不採機械引水時走第一百八十五條第五款第二目，採水口為口徑一百毫米並接裝陽式螺牙；採機械方式引水時走第一百八十六條第四款，採水口接裝六十三毫米陽式快接頭。兩者的高度規定則一致，都是距基地地面一公尺以下零點五公尺以上。再往外一層可對照第一百八十條第五款的連結送水管送水口，接裝的是口徑六十三毫米陰式快速接頭，距基地地面之高度在一公尺以下零點五公尺以上，陽式與陰式的差別是命題常設的陷阱。\n第二款的全揚程計算式與第一百八十三條連結送水管中繼幫浦之全揚程計算式體例相同，都是把落差與配管摩擦損失水頭相加後再加一個固定水頭，但固定值與加項不同：第一百八十六條第二款為落差加配管摩擦損失水頭加 15m，第一百八十三條第一款則為消防水帶摩擦損失水頭加配管摩擦損失水頭加落差加 60m，同條第二款並定中繼幫浦出水量在每分鐘二千四百公升以上。\n檢修面可對照《消防安全設備及必要檢修項目檢修基準》第二十一章消防專用蓄水池一、外觀檢查採水口，其判定方法要求標示應清晰易於辨識，且每一採水口附近應設有紅色啟動表示燈，但設由防災中心遙控啟動且採水口與防災中心間設有通話聯絡裝置者不在此限，與設置條文的但書完全對應。標示文字則依第一百八十七條，進水管投入孔標明消防專用蓄水池字樣，採水口標明採水口或消防專用蓄水池採水口字樣。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-038","依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",38,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-040","有關公共危險物品場所設置自動撒水設備規定，下列敘述何者正確？",40,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-037","固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，下列敘述何者錯誤？",37,{"webId":41,"stem":42,"number":12,"year":43,"session":12},"fire-113-1-water-chemical-001","有關消防安全設備水源容量之放水時間，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",113,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-036","乾粉滅火設備採全區或局部之噴頭，下列設置規定何者錯誤？",36,{"webId":49,"stem":50,"number":51,"year":43,"session":12},"fire-113-1-water-chemical-002","室內停車空間設置水霧滅火設備，依據各類場所消防安全設備設置標準規定，下列敘述何者錯誤？",2,[53,56,60,64,68],{"webId":54,"year":43,"stem":55,"number":13},"fire-113-1-water-chemical-039","某一工廠儲存鹼金屬過氧化物，滅火藥劑適用下列何者？",{"webId":57,"year":58,"stem":59,"number":13},"fire-111-1-water-chemical-039",111,"可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",{"webId":61,"year":62,"stem":63,"number":13},"fire-110-1-water-chemical-039",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之遠隔啟動裝置，限用於儲存閃火點多少℃以下公共危險物品之室外儲槽？",{"webId":65,"year":66,"stem":67,"number":13},"fire-109-1-water-chemical-039",109,"公共危險品等場所中，所設置之室外消防栓設備，其緊急電源之供電容量應供其有效動作多久以上？",{"webId":69,"year":70,"stem":71,"number":13},"fire-108-1-water-chemical-039",108,"依各類場所消防安全設備設置標準之規定，公共危險物品室外儲槽場所之冷卻撒水設備如以幫浦方式進行加壓時，實際測得之放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在多少以上？",1785129972023]