[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-036","fire-112-1-water-chemical-036",112,1,36,"乾粉滅火設備採全區或局部之噴頭，下列設置規定何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"全區放射方式所設之噴頭能使放射藥劑迅速均勻地擴散至整個防護區域","乾粉噴頭之放射壓力在每平方公分 1 公斤以上","核算之滅火藥劑量須於 60 秒內全部放射完畢","局部放射方式所設噴頭之有效射程內，應涵蓋防護對象所有表面，且所設位置不得因藥劑之放射使可燃物有飛散之虞","C",null,[],false,"本題考點：乾粉滅火設備全區及局部放射方式噴頭之設置規定，關鍵在放射壓力與藥劑放射完畢之時限。\n【正解理由】依《各類場所消防安全設備設置標準》第一百條第三款，依前條第一款或第二款所核算之滅火藥劑量須於三十秒內全部放射完畢；本選項寫成六十秒，與該款明定之三十秒不符，故選 C。\n【逐項排除】\n(A) 正確。第一百條第一款明定全區放射方式所設之噴頭能使放射藥劑迅速均勻地擴散至整個防護區域。\n(B) 正確。第一百條第二款明定乾粉噴頭之放射壓力在每平方公分一公斤以上或 0.1MPa 以上。\n(C) 錯誤。第一百條第三款所定之放射時限為三十秒，全區與局部放射均適用此一時限，並無六十秒之規定，是本題應選之錯誤敘述。\n(D) 正確。第一百條第四款明定局部放射方式所設噴頭之有效射程內，應涵蓋防護對象所有表面，且所設位置不得因藥劑之放射使可燃物有飛散之虞。\n【記憶點】乾粉噴頭記「一公斤壓力、三十秒放完」，四款只有時間最容易被改成六十秒。","第一百條共四款，是乾粉滅火設備噴頭的完整規定：第一款要求全區放射之噴頭能使藥劑迅速均勻擴散至整個防護區域；第二款定放射壓力在每平方公分一公斤以上或 0.1MPa 以上；第三款定核算之藥劑量須於三十秒內全部放射完畢；第四款定局部放射噴頭之有效射程應涵蓋防護對象所有表面，且位置不得使可燃物有飛散之虞。四款要整組記，命題者通常只動其中一個數字。\n藥劑量的出處在第九十九條第一款之表：全區放射每立方公尺防護區域所需滅火藥劑量，第一種乾粉（主成份碳酸氫鈉）為 0.6、第二種乾粉（主成份碳酸氫鉀）為 0.36、第三種乾粉（主成份磷酸二氫銨）為 0.36、第四種乾粉（主成份碳酸氫鉀及尿素化合物）為 0.24 公斤／立方公尺；每平方公尺開口部所需追加量依序為 4.5、2.7、2.7、1.8 公斤／平方公尺。局部放射方式中，可燃性固體或易燃性液體存放於上方開放式容器且燃燒限於一面者，防護對象每平方公尺表面積所需藥劑量第一種乾粉為 8.8、第二種或第三種乾粉為 5.2、第四種乾粉為 3.6 公斤，追加倍數均為 1.1。\n易混淆對照：二氧化碳滅火設備第八十四條第二款之放射壓力，常溫儲存之高壓式為每平方公分十四公斤以上或 1.4MPa 以上，儲存於攝氏零下十八度以下之低壓式為每平方公分九公斤以上或 0.9MPa 以上；同條第三款之全區放射時間表列電信機械室、總機室為 3.5 分、其他為 1 分；同條第五款局部放射則為三十秒內放射完畢。兩種設備的壓力與時間各有出處，抄錯條就會抄錯數字。\n延伸考點：第八十五條規定全區或局部放射方式防護區域內之通風換氣裝置，應在滅火藥劑放射前停止運轉；第九十四條規定放射後之藥劑應於一小時內排出，採機械排放時排風機為專用且具每小時五次之換氣量，採自然排放時開口面向外氣部分應占防護區域樓地板面積百分之十以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-035","二氧化碳滅火設備之滅火藥劑儲存容器，其設置規定下列何者錯誤？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-037","固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，下列敘述何者錯誤？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-034","有關自動撒水設備免設撒水頭處所得設置補助撒水栓之規定，下列敘述何者錯誤？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-038","依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-033","二氧化碳滅火設備滅火藥劑量，下列設置規定何者錯誤？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-039","依各類場所消防安全設備設置標準規定，消防專用蓄水池之採水設置，下列敘述何者錯誤？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-036",113,"有關室外消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-036",111,"二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-036",110,"依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-036",109,"任一消防專用蓄水池至建築物各部分之水平距離不得超過多少公尺？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-036",108,"依各類場所消防安全設備設置標準之規定，高發泡放出口在全區放射防護區域內，樓地板面積每多少平方公尺應至少設置 1 個，且能有效放射至該區域，並附設泡沫放出停止裝置？",1785129972011]