[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-035":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-035","fire-112-1-water-chemical-035",112,1,35,"二氧化碳滅火設備之滅火藥劑儲存容器，其設置規定下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"充填比在高壓式為 1.5 以上 1.9 以下；低壓式為 1.1 以上 1.4 以下","低壓式儲存容器，應設有液面計、壓力表及壓力警報裝置，壓力在每平方公分 23 公斤以上或每平方公分 19 公斤以下時發出警報","容器閥使用電磁閥直接開啟時，同時開啟之儲存容器數在 6 支以上者，該儲存容器應設 2 個以上之電磁閥","充填比，指容器內容積（公升）與液化氣體重量（公斤）之比值","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 87 條二氧化碳滅火藥劑儲存容器的充填比、低壓式附屬裝置與容器閥開放裝置。\n【正解理由】第 87 條第一項第七款第二目規定，容器閥使用電磁閥直接開啟時，同時開啟之儲存容器數在七支以上者，該儲存容器應設二個以上之電磁閥；(C) 寫成六支以上與該目不符，本題問錯誤者，故選 C。\n【逐項排除】\n(A) 敘述正確。第一款充填比在高壓式為一點五以上一點九以下，低壓式為一點一以上一點四以下。\n(B) 敘述正確。第五款低壓式儲存容器應設有液面計、壓力表及壓力警報裝置，壓力在每平方公分二十三公斤以上或每平方公分十九公斤以下時發出警報。\n(C) 敘述錯誤，設二個以上電磁閥的門檻是同時開啟之儲存容器數在七支以上。\n(D) 敘述正確。同條第二項明定前項第一款充填比，指容器內容積（公升）與液化氣體重量（公斤）之比值。\n【記憶點】高壓式一點五至一點九、低壓式一點一至一點四；低壓式警報二十三與十九公斤；電磁閥直接開啟七支以上要設二個以上。","充填比是容器內容積除以液化氣體重量，比值愈小代表裝得愈滿、容器內壓愈高，因此第 87 條第一款對高壓式與低壓式分別給上下限：高壓式一點五以上一點九以下，低壓式一點一以上一點四以下。低壓式靠冷凍維持低溫，同條第六款要求設置使容器內部溫度維持於攝氏零下二十度以上、攝氏零下十八度以下之自動冷凍機，第五款的液面計、壓力表與壓力警報裝置則負責監看二十三公斤與十九公斤兩個界線。儲存場所依第二款須置於防護區域外、置於溫度攝氏四十度以下且溫度變化較少處，不得置於有日光曝曬或雨水淋濕之處，第八款並要求採取有效防震措施。\n《消防安全設備及必要檢修項目檢修基準》惰性氣體滅火設備之性能檢查，把低壓式的動作壓力帶整理成一串：破壞板動作壓力三十七、安全閥起噴壓力二十五、壓力上升警報二十三、冷凍機啟動二十二、冷凍機停止二十一、壓力下降警報十九，單位為 kgf\u002Fcm2，常用壓力範圍即落在十九至二十三之間；同章並記明藥劑量之測定結果與重量表或圖面明細表核對，差值應在充填值百分之十以下，二氧化碳滅火設備之充填比應在一點五以上。\n延伸考點是第 88 條的啟動用氣體容器：能耐每平方公分二百五十公斤之壓力、內容積應有一公升以上、所儲存之二氧化碳重量在零點六公斤以上、充填比在一點五以上，且不得兼供防護區域之自動關閉裝置使用。第 89 條的配管另定高壓式使用無縫鋼管為管號 Sch 80 以上、低壓式為 Sch 40 以上厚度，配管接頭及閥類之耐壓，高壓式為每平方公分一百六十五公斤以上、低壓式為每平方公分三十七點五公斤以上，最低配管與最高配管間之落差在五十公尺以下。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-034","有關自動撒水設備免設撒水頭處所得設置補助撒水栓之規定，下列敘述何者錯誤？",34,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-036","乾粉滅火設備採全區或局部之噴頭，下列設置規定何者錯誤？",36,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-033","二氧化碳滅火設備滅火藥劑量，下列設置規定何者錯誤？",33,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-037","固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，下列敘述何者錯誤？",37,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-032","依各類場所消防安全設備設置標準規定，下列何者應設置消防專用蓄水池？",32,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-038","依各類場所消防安全設備設置標準規定，消防專用蓄水池之設置，下列敘述何者錯誤？",38,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-035",113,"惰性氣體進行高壓式全區放射綜合檢查，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-035",111,"二氧化碳滅火設備採全區放射，其噴頭設置規定下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-035",110,"依消防安全設備及必要檢修項目檢修基準，製造日期超過 10 年或無法辨識製造日期之何種滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-035",109,"廚房等大量使用火源之處所，多少樓地板面積需有一滅火效能值？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-035",108,"依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備呼水裝置之減水警報裝置，當水量減少至多少前應發出警報？",1785129972000]