[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-034","fire-112-1-water-chemical-034",112,1,34,"有關自動撒水設備免設撒水頭處所得設置補助撒水栓之規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"免設撒水頭處所任一點至水帶接頭之水平距離在 15 公尺以下","瞄子放水壓力在每平方公分 2.5 公斤以上，放水量在每分鐘 60 公升以上","補助撒水栓箱表面標示補助撒水栓字樣，箱體上方設置紅色啟動表示燈","開關閥設在距地板面 1.8 公尺以下","D",null,[],false,"本題考點：自動撒水設備免設撒水頭處所得設置補助撒水栓時的四項規定，關鍵在開關閥的設置高度。\n【正解理由】依《各類場所消防安全設備設置標準》關於免設撒水頭處所得設置補助撒水栓之規定，開關閥設在距地板面一點五公尺以下，(D) 寫成一點八公尺以下與該規定不符；本題問錯誤者，故選 D。\n【逐項排除】\n(A) 敘述正確。免設撒水頭處所任一點至水帶接頭之水平距離在十五公尺以下；《消防安全設備測試報告書測試方法及判定要領》自動撒水設備之外觀試驗對補助撒水栓的判定要領亦為「應設置在撒水頭未警戒部分至水帶接續口水平距離為 15m 以下的範圍內」。\n(B) 敘述正確。瞄子放水壓力在每平方公分二點五公斤以上、放水量在每分鐘六十公升以上，是補助撒水栓的放水性能要求。\n(C) 敘述正確。補助撒水栓箱表面標示補助撒水栓字樣，箱體上方設置紅色啟動表示燈，供人員辨識箱體位置與確認加壓送水裝置已啟動。\n(D) 敘述錯誤，開關閥的設置高度上限並非距地板面一點八公尺。\n【記憶點】水平距離十五公尺、二點五公斤與六十公升、紅色啟動表示燈、開關閥一點五公尺以下。","補助撒水栓是免設撒水頭處所的補償措施：那些處所因用途或構造不宜裝設撒水頭，改以人員操作的小型放水設備維持初期滅火能力，所以它的規定同時帶有撒水設備與消防栓的影子。它的放水性能為每平方公分二點五公斤以上、每分鐘六十公升以上；與之並列的是第 34 條第一項第二款第二目第二種消防栓的每平方公分一點七公斤以上或 0.17MPa 以上、放水量每分鐘八十公升以上，兩組數值分屬不同設備，不可互換。第 34 條第二項第一款另定室內消防栓開關距離樓地板之高度在零點三公尺以上一點五公尺以下，並要求設在走廊或防火構造樓梯間附近便於取用處。\n驗收面，《消防安全設備測試報告書測試方法及判定要領》自動撒水設備之外觀試驗把補助撒水栓與減壓裝置列在同一段，減壓措施的判定要領是「應採取防止撒水頭及補助撒水栓之放水壓力超過 10kgf\u002Fcm2 的措施」，補助撒水栓的設置場所則以至水帶接續口水平距離十五公尺以下為判定；同章對制水閥設置高度、流水檢知裝置、末端查驗閥、送水口口徑與設置高度的判定要領，也都與《設置標準》的設置數值對齊，是把設置條文與驗收要領一起背的好機會。\n須說明的是，補助撒水栓之專條全文本文未逐字引錄，上述依據僅引至該設備規定的層級而不寫條號，複習時請以《各類場所消防安全設備設置標準》公告條文核對。另一個同屬人員操作型的設備是移動式泡沫滅火設備，第 80 條定同一樓層各泡沫瞄子放射量在每分鐘一百公升以上、放射壓力在每平方公分三點五公斤以上，並在水帶接頭三公尺範圍內設置泡沫消防栓箱，箱內配置長二十公尺以上水帶及泡沫瞄子乙具，箱面表面積在零點八平方公尺以上，且在箱上方設置紅色幫浦啟動表示燈——紅色啟動表示燈是這一類箱體的共同標記。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-033","二氧化碳滅火設備滅火藥劑量，下列設置規定何者錯誤？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-035","二氧化碳滅火設備之滅火藥劑儲存容器，其設置規定下列何者錯誤？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-032","依各類場所消防安全設備設置標準規定，下列何者應設置消防專用蓄水池？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-036","乾粉滅火設備採全區或局部之噴頭，下列設置規定何者錯誤？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-031","消防幫浦之性能規定，下列敘述何者錯誤？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-037","固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，下列敘述何者錯誤？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-034",113,"蓄壓式鹵化烴滅火藥劑儲存容器使用水平液面計之方法進行滅火藥劑量性能檢查，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-034",111,"第五種滅火設備除滅火器外之其他設備，有關滅火效能值核算之規定，下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-034",110,"依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-034",109,"乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-034",108,"依各類場所消防安全設備設置標準之規定，水霧滅火設備之加壓送水裝置使用消防幫浦時，用於防護電氣設備者，每一個水霧噴頭壓力依規定均應達到多少以上？",1785129971993]