[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-031","fire-112-1-water-chemical-031",112,1,31,"消防幫浦之性能規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"在額定出水量之 150%時，其揚程達到性能曲線上全揚程之 65%以上","在額定出水量（1\u002Fmin）900 以上 2,700 以下，最大吸水全揚程 5.5 公尺以上，且不得有異常現象","在額定出水量 150%時，其軸動力不得超過馬達額定輸出馬力之 120%","幫浦在啟動時其軸承不得發生過熱，噪音或異常振動現象","C",null,[],false,"本題考點：《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》第 5 點幫浦性能的四組規定，含性能曲線、吸水性能、消耗動力與啟動狀態。\n【正解理由】第 5 點第三款第二目規定，在額定出水量一百五十％時，其軸動力不得超過馬達額定輸出馬力之一百一十％，(C) 寫成一百二十％與該目不符；本題問錯誤者，故選 C。\n【逐項排除】\n(A) 敘述正確。第一款第二目，幫浦之出水量在額定出水量一百五十％時，其全揚程應達到性能曲線上全揚程之六十五％以上。\n(B) 敘述正確。第二款吸水性能表列額定出水量九百以上二千七百以下者，最大吸水全揚程五點五公尺，且不得有異常現象。\n(C) 敘述錯誤，一百五十％出水量時的軸動力上限是馬達額定輸出馬力之一百一十％。\n(D) 敘述正確。第五款規定幫浦在啟動時其軸承不得發生過熱、噪音或異常振動現象。\n【記憶點】性能曲線一百五十％對六十五％、全閉一百四十％以下、額定一百至一百一十％；軸動力在一百五十％出水量時只放寬到一百一十％。","第 5 點是消防幫浦的驗收核心。第一款把性能曲線釘出三個點：額定出水量時，全揚程必須達到所標示揚程之一百％至一百一十％之間；出水量為額定之一百五十％時，全揚程應達到性能曲線上全揚程之六十五％以上；全閉揚程應為性能曲線上全揚程之一百四十％以下。三點合起來，保證幫浦在超量出水時仍供得起壓力，在全閉時又不會把配管撐爆。\n第二款的吸水性能依額定出水量分四段：九百未滿為最大吸水全揚程六點零公尺、九百以上二千七百以下為五點五公尺、超過二千七百至五千以下為四點五公尺、超過五千至八千五百以下為四點零公尺。出水量愈大、允許的吸水高度愈小，因為吸水管流速提高後摩擦損失與汽蝕風險同步上升。第三款的消耗動力分兩段：在額定出水量時，軸動力不得超過馬達之額定輸出馬力；在額定出水量一百五十％時，不得超過馬達額定輸出馬力之一百一十％。第 10 點另規定電動機在額定負荷狀態下應能順利啟動，額定輸出連續運轉八小時後不得發生異狀，且在超過額定輸出百分之十輸出力運轉一小時仍不致過熱。\n驗收面可對照《消防安全設備測試報告書測試方法及判定要領》連結送水管設備之性能試驗：全閉運轉時，全閉揚程應在額定負荷運轉時測得揚程的一百四十％以下；額定負荷運轉時，測得揚程應在該幫浦所標示揚程的一百％以上一百一十％以下，與本基準的數值完全對應。第 5 點第四款並要求幫浦之效率應依額定出水量在規定曲線求其規定值以上；同一基準第 19 點的啟動用水壓開關裝置，則規定啟動用壓力槽容量應有一百公升以上，並使用口徑 25mm 以上配管與幫浦出水側逆止閥之二次側配管連接，中途裝置止水閥。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-030","消防幫浦之防止水溫上升用排放裝置，下列敘述何者正確？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-032","依各類場所消防安全設備設置標準規定，下列何者應設置消防專用蓄水池？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-029","有關泡沫滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-033","二氧化碳滅火設備滅火藥劑量，下列設置規定何者錯誤？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-028","有關水霧滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-034","有關自動撒水設備免設撒水頭處所得設置補助撒水栓之規定，下列敘述何者錯誤？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-031",113,"依各類場所消防安全設備設置標準規定，二氧化碳滅火設備使用氣體啟動者，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-031",111,"應設置消防專用蓄水池之場所規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-031",110,"公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-031",109,"使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-031",108,"第四種乾粉滅火藥劑儲存容器，有關充填比之規定，下列何者正確？",1785129971968]