[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-027","fire-112-1-water-chemical-027",112,1,27,"有關自動撒水設備設置流水檢知裝置規定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"樓地板面積在 3,000 平方公尺以下者，裝設一套，超過 3,000 平方公尺者，裝設二套","無隔間之樓層內，每套有效範圍得增為 9,000 平方公尺","附設制水閥，其高度距離樓地板面在 1.5 公尺以下 0.6 公尺以上","撒水頭或一齊開放閥開啟放水時，即發出信號","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 51 條自動撒水設備流水檢知裝置的四款規定。\n【正解理由】第 51 條第一款明定「各樓層之樓地板面積在三千平方公尺以下者，裝設一套，超過三千平方公尺者，裝設二套」，(A) 與條文相符，故選 A。同款但書另放寬：上下二層各層撒水頭數量在十個以下，且設有火警自動警報設備者，得二層共用。\n【逐項排除】\n(A) 正確，三千平方公尺是一套流水檢知裝置的有效範圍分界。\n(B) 錯誤。第二款規定無隔間之樓層內，前款三千平方公尺得增為一萬平方公尺，不是九千平方公尺。\n(C) 錯誤。第四款制水閥高度為距樓地板面一點五公尺以下、零點八公尺以上，下限是零點八公尺，且應於制水閥附近明顯易見處設置標明制水閥字樣之標識。\n(D) 錯誤。第三款的條文用語是「撒水頭或一齊開放閥開啟放水時，即發出警報」，發出的是警報而非信號。\n【記憶點】一套管三千平方公尺、無隔間放寬到一萬、制水閥零點八至一點五公尺、放水即發出警報。","流水檢知裝置即一般所稱的自動警報逆止閥，功能是偵知二次側水流並發出警報，所以第 51 條把「一套管多大面積」與「閥怎麼裝」寫在同一條。第一款以三千平方公尺為套數分界，第二款的無隔間樓層放寬到一萬平方公尺，理由是無隔間空間水流路徑單純、警報區域辨識不受影響；第一款但書允許上下二層共用，前提是各層撒水頭在十個以下且設有火警自動警報設備，等於用另一套警報系統補足辨識能力。\n制水閥的零點八公尺以上、一點五公尺以下，是站立操作的高度帶。《消防安全設備測試報告書測試方法及判定要領》自動撒水設備之外觀試驗對制水閥同樣列出「應設置於距離樓地板面高度在 0.8m 以上 1.5m 以下處所」，並要求採取無法任意關閉的措施，於附近明顯易見處標示其為控制閥及經常開放狀態，設置端與驗收端數值一致。\n易混淆對照：第 43 條把自動撒水設備分為密閉濕式、密閉乾式、開放式、預動式四種，另有其他經中央主管機關認可者；密閉乾式與預動式的流水檢知裝置二次側配管，依第 44 條須施予鍍鋅等防腐蝕處理，並為有效排水而使支管每十公尺傾斜四公分、主管每十公尺傾斜二公分。第 56 條的末端查驗閥則規定管徑二十五毫米以上、接裝在各層放水壓力最低之最遠支管末端、一次側設壓力表、二次側設與撒水頭同等放水性能之限流孔、距地板面高度二點一公尺以下並標明末端查驗閥字樣，與流水檢知裝置常在同一年度互相搭配命題。第 54 條則規定開放式自動撒水設備之放水區域，每一舞臺之放水區域在四個以下，放水區域在二個以上時，每一放水區域樓地板面積在一百平方公尺以上，且鄰接之放水區域相互重疊，使有效滅火。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-026","依據各類場所消防安全設備設置標準，有關撒水頭裝置之規定，下列敘述何者正確？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-028","有關水霧滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-025","有關公共危險物品場所設置室外消防栓之規定，下列敘述何者錯誤？",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-029","有關泡沫滅火設備，依各類場所消防安全設備設置標準規定，下列敘述何者正確？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-024","依各類場所消防安全設備設置標準規定，下列何種場所需設置室外消防栓設備？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-030","消防幫浦之防止水溫上升用排放裝置，下列敘述何者正確？",30,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-027",113,"公共危險物品等場所設置之室內消防栓設備，應符合下列何者規定？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-027",111,"自動撒水採用密閉乾式或預動式自動撒水設備，撒水頭動作後，流水檢知裝置應在幾分鐘內，使撒水頭放水？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-027",110,"二氧化碳滅火設備之全區放射或局部放射方式防護區域，對放射之滅火藥劑之排放規定，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-027",109,"中央消防主管機關認定儲存大量可燃物之場所天花板高度超過 6 公尺，或其他場所天花板高度超過 10 公尺者，應採用何種撒水頭？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-027",108,"依各類場所消防安全設備設置標準之規定，室外消防栓於其 I 公尺範圍內附設水帶箱，在 J 公尺以內，保持空曠，不得堆放物品或種植花木。下列 I，J 何者正確？",1785129971950]