[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-022":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-022","fire-112-1-water-chemical-022",112,1,22,"依各類場所消防安全設備設置標準規定，一般場所設置滅火器，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"地下層或無開口樓層，且樓地板面積在 50 平方公尺以上之各類場所應設滅火器","超級市場各層樓地板面積每一百平方公尺（含未滿）有一滅火效能值","設滅火器字樣之標識，其每字應在 20 平方公分以上","美術館設滅火器字樣標識之顏色得為紅底白字、白底紅字、綠底白字、白底綠字等","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第十四條應設滅火器之場所，與第三十一條滅火器之效能值核算及標識規格。\n【正解理由】依第三十一條第四款，滅火器應固定放置於取用方便之明顯處所，並設有以紅底白字標明滅火器字樣之標識，僅在與室內消防栓箱等設備併設於箱體內並於箱面標明滅火器字樣時，標識顏色才不在此限；美術館屬第十二條第二款第四目之乙類場所，並無四種顏色任選之規定，故選 D。\n【逐項排除】\n(A) 第十四條第三款：設於地下層或無開口樓層，且樓地板面積在五十平方公尺以上之各類場所應設滅火器，敘述正確。\n(B) 超級市場屬第十二條第一款第四目，依第三十一條第一款第一目，各層樓地板面積每一百平方公尺（含未滿）有一滅火效能值，敘述正確。\n(C) 第三十一條第四款明定標識每字應在二十平方公分以上，敘述正確。\n(D) 標識顏色限紅底白字，選項列出白底紅字、綠底白字、白底綠字等，與條文不符，即為本題所問的錯誤敘述。\n【記憶點】紅底白字、每字二十平方公分以上；甲類與戊類每一百平方公尺一效能值，乙丙丁類每二百平方公尺一效能值。","滅火效能值是把不同藥劑、不同容量的滅火器換算成同一把尺的制度：一具滅火器能撲滅多少模型火就有多少效能值，法規再依場所火載量規定每多少樓地板面積要有一個效能值。第三十一條第一款把一般場所分成三檔：供第十二條第一款（甲類）及第五款（戊類）使用之場所，各層樓地板面積每一百平方公尺（含未滿）有一滅火效能值；供第二款至第四款（乙、丙、丁類）使用之場所，每二百平方公尺（含未滿）有一滅火效能值；鍋爐房、廚房等大量使用火源之處所，則加嚴為每二十五平方公尺（含未滿）有一滅火效能值。第二款另規定電影片映演場所放映室及電氣設備使用之處所，每一百平方公尺（含未滿）另設一滅火器。\n設置方式的三個數值也常被抽考：第三款步行距離，設有滅火器之樓層自樓面居室任一點至滅火器之步行距離在二十公尺以下；第四款標識，紅底白字且每字在二十平方公分以上；第五款高度，懸掛於牆上或放置滅火器箱中之滅火器，其上端與樓地板面之距離，十八公斤以上者在一公尺以下、未滿十八公斤者在一點五公尺以下。第十四條則管「哪些場所要設」，共五款：甲類場所、地下建築物、幼兒園；總樓地板面積在一百五十平方公尺以上之乙、丙、丁類場所；設於地下層或無開口樓層且樓地板面積在五十平方公尺以上之各類場所；設有放映室或變壓器、配電盤及其他類似電氣設備之各類場所；設有鍋爐房、廚房等大量使用火源之各類場所。\n易混淆對照：公共危險物品場所走第四編第一百九十九條，第五種滅火設備的效能值核算為製造或處理場所之建築物外牆防火構造者每一百平方公尺、非防火構造者每五十平方公尺有一滅火效能值，儲存場所之建築物外牆防火構造者每一百五十平方公尺、非防火構造者每七十五平方公尺有一滅火效能值，另每達管制量之十倍（含未滿）應有一滅火效能值。兩編各自適用，不可互套。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-021","某一場所設置有滅火藥劑為 IG-01 之惰性氣體滅火設備，依據消防安全設備測試報告書測試方法及判定要領，針對儲存容器進行外觀試驗，則在室溫 35℃時，充填壓力應在多少 kgf\u002Fcm2 以下？",21,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-023","依各類場所消防安全設備設置標準規定，下列何種場所不需設置室內消防栓設備？",23,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-020","下列何種海龍替代品滅火劑，其熱分解物不至於產生氟化氫（HF）？",20,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-024","依各類場所消防安全設備設置標準規定，下列何種場所需設置室外消防栓設備？",24,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-019","依各類場所消防安全設備設置標準規定，樓地板面積在 X 平方公尺以上之餐廳或供失智照顧型之長期照顧機構使用之場所且樓地板面積合計在 Y 平方公尺以上者，其廚房排油煙管及煙罩應設簡易自動滅火設備。則 X、Y 為何？",19,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-025","有關公共危險物品場所設置室外消防栓之規定，下列敘述何者錯誤？",25,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-022",113,"下列場所何者得設置水霧滅火設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-022",111,"有關水道連結型自動撒水設備進行綜合檢查時，其放水壓力應為多少？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-022",110,"同一建築基地內有二棟以上建築物時，建築物間外牆與中心線水平距離第一層在 X 公尺以下，第二層在 Y 公尺以下，且合計各棟該第一層及第二層樓地板面積在 Z 平方公尺以上者，應設置消防專用蓄水池。X、Y、Z 分別為何？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-022",109,"室內消防栓之箱面字樣，每字不得小於多少平方公分？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-022",108,"有關潔淨藥劑氣體滅火設備滅火藥劑主要成分之敘述，下列何者正確？",1785129971918]