[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-020":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-020","fire-112-1-water-chemical-020",112,1,20,"下列何種海龍替代品滅火劑，其熱分解物不至於產生氟化氫（HF）？",{"A":16,"B":17,"C":18,"D":19},"Inergen（IG-541）","HFC-227ea（FM-200）","HFC-23（FE-13）","FK5-1-12（Novec1230）","A",null,[],false,"本題考點：海龍替代滅火藥劑的化學組成，以及分子中有無氟原子決定熱分解物會不會出現氟化氫。\n【正解理由】依滅火藥劑組成判斷，Inergen（IG-541）是氮氣、氬氣與二氧化碳混合而成的惰性氣體藥劑，分子中完全不含氟原子，受熱也不會分解出氟化氫；其餘三者都是含氟化合物，故選 A。\n【逐項排除】\n(A) IG-541 屬惰性氣體混合藥劑，成分為氮、氬與二氧化碳，靠稀釋氧濃度滅火，無氟原子可供分解，熱分解物不含氟化氫。\n(B) HFC-227ea（FM-200）分子式為 C3HF7，屬氫氟碳化物，每個分子帶七個氟原子，高溫下與火場水氣作用會生成氟化氫。\n(C) HFC-23（FE-13）分子式為 CHF3，同屬氫氟碳化物，熱分解同樣產生氟化氫。\n(D) FK-5-1-12（Novec1230）為全氟酮類，分子式 C6F12O，含氟比例更高，受熱亦分解出氟化氫。\n【記憶點】藥劑代號帶 IG 者是惰性氣體、分子無氟；HFC 與 FK 系列分子含氟，熱分解產物必有氟化氫。","海龍（鹵化烷）滅火藥劑靠溴、氯自由基捕捉燃燒連鎖反應中的氫氧自由基，滅火效率極高，但同樣的溴、氯在平流層會破壞臭氧層，蒙特婁議定書因而將其列為管制物質並逐步淘汰。替代藥劑循兩條路線發展，這也是本題四個選項的分類依據。\n第一條路線是惰性氣體，代號一律以 IG 開頭：IG-01 為氬氣、IG-100 為氮氣、IG-55 為氮氣與氬氣、IG-541 為氮氣、氬氣與二氧化碳。這類藥劑本身就是空氣中原有的氣體，靠把防護區域的氧濃度稀釋到燃燒下限以下滅火，分子裡沒有鹵素，受熱不會生成任何酸性分解物，臭氧破壞潛勢為零。代價是滅火需要的體積濃度高，鋼瓶數量多、儲存壓力高。\n第二條路線是鹵化烴，包含氫氟碳化物與全氟酮。HFC-227ea 分子式 C3HF7、HFC-23 分子式 CHF3、FK-5-1-12 分子式 C6F12O，滅火機制以吸熱冷卻搭配部分化學抑制為主，所需濃度低、鋼瓶數量少，但分子中的碳氟鍵在火焰高溫下會斷裂，與水氣結合生成氟化氫。氟化氫具強腐蝕性與毒性，因此這類藥劑的設計特別重視放射時間與火災早期偵測，越早放射、火場溫度越低，分解量越少。\n易混淆對照：惰性氣體看的是「稀釋氧氣」，鹵化烴看的是「吸熱與抑制」；前者無氟、後者有氟，這一組對照幾乎每年都以不同包裝出題。延伸考點連結：《各類場所消防安全設備設置標準》第一百九十二條之一把乾粉、惰性氣體及鹵化烴等滅火設備列為防災監控系統綜合操作裝置應監控或操作的對象之一，同條並要求該裝置之緊急電源供電容量應供其有效動作二小時以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-019","依各類場所消防安全設備設置標準規定，樓地板面積在 X 平方公尺以上之餐廳或供失智照顧型之長期照顧機構使用之場所且樓地板面積合計在 Y 平方公尺以上者，其廚房排油煙管及煙罩應設簡易自動滅火設備。則 X、Y 為何？",19,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-021","某一場所設置有滅火藥劑為 IG-01 之惰性氣體滅火設備，依據消防安全設備測試報告書測試方法及判定要領，針對儲存容器進行外觀試驗，則在室溫 35℃時，充填壓力應在多少 kgf\u002Fcm2 以下？",21,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-018","乾粉滅火設備使用蓄壓用氣體容器，若氣體使用氮氣時，在溫度 35℃，大氣壓力（表壓力） 0 kg\u002Fcm2 狀態下，除加算清洗配管所需要量外，每一公斤乾粉藥劑需氮氣之量為何？",18,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-022","依各類場所消防安全設備設置標準規定，一般場所設置滅火器，下列敘述何者錯誤？",22,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-017","有關室內消防栓之水平距離、瞄子放水壓力、消防栓及位置之規定，下列敘述何者正確？",17,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-023","依各類場所消防安全設備設置標準規定，下列何種場所不需設置室內消防栓設備？",23,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-020",113,"有關水道連結型自動撒水設備，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-020",111,"電子工業廠房潔淨室設置消防安全設備，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-020",110,"飛機修理廠、飛機庫樓地板面積在 200 平方公尺以上者，可就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇下列何者設置之？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-020",109,"用於防護電氣設施之水霧滅火設備進行放水試驗時，最末端放射區域全部水霧噴頭之放水壓力均應能達到多少壓力以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-020",108,"公共危險物品等場所之滅火設備分類，下列敘述何者錯誤？",1785129971907]