[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-018":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-018","fire-112-1-water-chemical-018",112,1,18,"乾粉滅火設備使用蓄壓用氣體容器，若氣體使用氮氣時，在溫度 35℃，大氣壓力（表壓力） 0 kg\u002Fcm2 狀態下，除加算清洗配管所需要量外，每一公斤乾粉藥劑需氮氣之量為何？",{"A":16,"B":17,"C":18,"D":19},"10 公升","15 公升","20 公升","40 公升","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第一百零四條，乾粉滅火設備加壓或蓄壓用氣體容器所需的氣體量。\n【正解理由】依第一百零四條第三款，蓄壓用氣體使用氮氣時，在溫度攝氏三十五度、大氣壓力（表壓力）每平方公分零公斤或 0MPa 狀態下，每一公斤乾粉藥劑需氮氣十公升並加算清洗配管所需要量以上；題幹已言明除加算清洗配管所需要量外，所問即為十公升，故選 A。\n【逐項排除】\n(A) 十公升即第三款蓄壓用氮氣的基本量，題幹的溫度與表壓力條件與條文完全相同。\n(B) 十五公升未出現於本條任何一款，屬憑印象的中間值。\n(C) 二十公升與本條無涉；本條出現的「二十」是使用二氧化碳時每一公斤乾粉藥劑需二氧化碳二十公克，單位是公克而非公升。\n(D) 四十公升是同條第二款加壓用氣體使用氮氣的量，把加壓式與蓄壓式看混即會誤選。\n【記憶點】蓄壓氮氣十公升、加壓氮氣四十公升、二氧化碳一律二十公克，同一條第二款與第三款只差在加壓或蓄壓。","乾粉滅火設備必須靠氣體把藥劑推出噴頭，依加壓時機分成加壓式與蓄壓式。加壓式平時藥劑桶內不帶壓，動作時才由加壓用氣體容器灌入，因此每公斤藥劑需要的氮氣量較多；蓄壓式平時就把氮氣封在藥劑桶內，動作時直接洩放，所需氮氣量以維持壓力為主。第一百零四條把兩者的量並列在同一條：第二款加壓用氮氣每一公斤乾粉藥劑四十公升以上、使用二氧化碳者每一公斤乾粉藥劑二十公克並加算清洗配管所需要量以上；第三款蓄壓用氮氣每一公斤乾粉藥劑十公升並加算清洗配管所需要量以上、使用二氧化碳者同為二十公克。同條第一款限定加壓或蓄壓用氣體只能使用氮氣或二氧化碳，第四款要求清洗配管用氣體另以容器儲存，第五款要求採取有效之防震措施。\n所有數值都掛在同一組基準狀態：溫度攝氏三十五度、大氣壓力（表壓力）每平方公分零公斤或 0MPa。氣體體積隨溫度壓力變動，若不指定狀態就無法比較，這也是題幹一定會把三十五度與表壓力零寫進去的原因。\n延伸考點連結：蓄壓式另有第一百零九條，規定應設置以綠色表示使用壓力範圍之指示壓力表，這是外觀就能辨識蓄壓式的特徵。配管規定在第一百零五條，應為專用並依噴頭流量計算管徑，使用符合 CNS 六四四五並施予鍍鋅等防蝕處理之鋼管；但蓄壓式中壓力在每平方公分二十五公斤以上或 2.5MPa 以上、每平方公分四十二公斤以下或 4.2MPa 以下時，應使用符合 CNS 四六二六之無縫鋼管管號 Sch40 以上厚度，最低配管與最高配管間落差在五十公尺以下，配管採均分為原則使噴頭放射壓力均等。第一百零六條並規定自儲存容器起，配管任一部分與彎曲部分之距離應為管徑二十倍以上，目的正是避免乾粉藥劑與加壓或蓄壓用氣體在彎頭處分離，導致噴出的只有氣體而無藥劑。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-017","有關室內消防栓之水平距離、瞄子放水壓力、消防栓及位置之規定，下列敘述何者正確？",17,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-019","依各類場所消防安全設備設置標準規定，樓地板面積在 X 平方公尺以上之餐廳或供失智照顧型之長期照顧機構使用之場所且樓地板面積合計在 Y 平方公尺以上者，其廚房排油煙管及煙罩應設簡易自動滅火設備。則 X、Y 為何？",19,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-016","有關二氧化碳滅火設備構件之安全措施規定，下列敘述何者正確？",16,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-020","下列何種海龍替代品滅火劑，其熱分解物不至於產生氟化氫（HF）？",20,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-015","有關滅火設備之緊急電源供電容量規定，下列敘述何者錯誤？",15,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-021","某一場所設置有滅火藥劑為 IG-01 之惰性氣體滅火設備，依據消防安全設備測試報告書測試方法及判定要領，針對儲存容器進行外觀試驗，則在室溫 35℃時，充填壓力應在多少 kgf\u002Fcm2 以下？",21,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-018",113,"有關泡沫滅火設備泡沫放射試驗判定要領，下列何者與消防安全設備測試報告書規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-018",111,"依各類場所消防安全設備設置標準規定，總樓地板面積 100 平方公尺之何種場所應設置滅火器？ ①咖啡廳 ②幼兒園 ③陳列館 ④商場",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-018",110,"有關滅火器設置規定，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-018",109,"移動式泡沫滅火設備進行綜合檢查作業時，發泡倍率應在幾倍以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-018",108,"依各類場所消防安全設備檢修及申報作業基準，固定式泡沫滅火設備（低發泡）綜合檢查，設置泡沫頭者，每次選擇全部放射區域數之若干%以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力？",1785129971899]