[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-112-1-water-chemical-012":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-水與化學系統消防安全設備概要-012","fire-112-1-water-chemical-012",112,1,12,"依據滅火器認可基準規定，由滅火器所充填之滅火藥劑量判別，下列何者屬大型滅火器？",{"A":16,"B":17,"C":18,"D":19},"強化液滅火器：60 公升以上","水滅火器：70 公升以上","二氧化碳滅火器：40 公斤以上","乾粉滅火器：16 公斤以上","A",null,[],false,"本題考點：《滅火器認可基準》就各類滅火器所定之「大型滅火器」滅火藥劑充填量門檻。\n【正解理由】依《滅火器認可基準》關於大型滅火器之規定，須以各類滅火器所充填之滅火藥劑量達該基準對該類滅火器所定之量以上者，始屬大型滅火器；其中強化液滅火器之判別量為六十公升以上，A 項所列六十公升與之相符，故選 A。大型滅火器並依《各類場所消防安全設備設置標準》第 197 條第一項第四款，於公共危險物品等場所之滅火設備分類中被列為第四種滅火設備。\n【逐項排除】\n(A) 強化液滅火器六十公升以上：與該基準所定強化液之大型判別量相符，為本題正解。\n(B) 水滅火器七十公升：水滅火器之大型判別量為八十公升以上，七十公升尚未達該量，仍非大型。\n(C) 二氧化碳滅火器四十公斤：二氧化碳滅火器之大型判別量為五十公斤以上，四十公斤未達該量。\n(D) 乾粉滅火器十六公斤：乾粉滅火器之大型判別量為二十公斤以上，十六公斤未達該量。\n【記憶點】大型判別量：機械泡沫二十公升、強化液六十公升、水八十公升；乾粉二十公斤、鹵化物三十公斤、二氧化碳五十公斤。","大型滅火器在《各類場所消防安全設備設置標準》第 197 條第一項第四款被列為公共危險物品等場所之第四種滅火設備，與第五種滅火設備之滅火器、水桶、水槽、乾燥砂、膨脹蛭石或膨脹珍珠岩分屬不同種類；判別是否為大型，靠的不是外型而是《滅火器認可基準》所定之滅火藥劑充填量，各類滅火器各有一組門檻：機械泡沫二十公升、強化液六十公升、水八十公升、乾粉二十公斤、鹵化物三十公斤、二氧化碳五十公斤。本題四個選項都是把其中一類的門檻改動一格，逐項比對量值即可。《滅火器認可基準》屬認可基準體例、本身無「第 N 條」結構，故本題依據引至基準名稱層級，其逐字門檻以中央主管機關公告之現行版本為準。\n大型滅火器在檢修上也留下痕跡：《消防安全設備及必要檢修項目檢修基準》滅火器之外觀檢查，把「車輪」與「氣體導入管」列為限大型滅火器之檢查項目，「壓力調整器」則限大型加壓式滅火器，看到這三項就知道談的是大型滅火器。同一部基準的滅火器性能檢查另定檢查頻率：化學泡沫滅火器每年實施一次性能檢查，其餘類型滅火器每三年實施一次；二氧化碳滅火器及海龍滅火器進行重量檢查時，失重超過百分之十以上或壓力表示值在綠色範圍外者應予更新；製造日期超過十年或無法辨識製造日期之水滅火器、機械泡沫滅火器或乾粉滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢。\n設置面的常考數值在第 31 條：滅火效能值以第十二條第一款及第五款場所每一百平方公尺、第二款至第四款場所每二百平方公尺、鍋爐房廚房等大量使用火源之處所每二十五平方公尺各有一滅火效能值；自樓面居室任一點至滅火器之步行距離在二十公尺以下；懸掛於牆上或放置於滅火器箱中者，其上端與樓地板面之距離，十八公斤以上者在一公尺以下、未滿十八公斤者在一點五公尺以下。這個十八公斤是懸掛高度的分界，與大型判別量是兩件事，讀題要分清楚。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-112-1-water-chemical-011","建築物高度在 X 公尺以下時，其連結送水管得與室內消防栓共用立管，其管徑在 Y 毫米以上，支管管徑在 Z 毫米以上。其中 X、Y 與 Z 分別為多少？",11,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-112-1-water-chemical-013","依據各類場所消防安全設備設置標準規定，加氣站之滅火器設置，下列敘述何者正確？",13,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-112-1-water-chemical-010","水霧滅火設備係利用特殊水霧噴頭，使水呈微粒霧狀及特定角度、形狀噴出，並均勻地覆蓋燃燒表面，達到滅火效果。下列何者非水霧滅火設備針對油類火災之滅火作用與原理？",10,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-112-1-water-chemical-014","有關二氧化碳滅火設備相關規定，下列敘述何者正確？",14,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-112-1-water-chemical-009","室外儲槽儲存閃火點在 70℃以下之第四類公共危險物品之顯著滅火困難場所，應依規定檢討設置下列何種設備？①補助泡沫消防栓 ②泡沫射水槍滅火設備 ③連結送液口 ④冷卻撒水設備 ⑤固定式泡沫滅火設備",9,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-112-1-water-chemical-015","有關滅火設備之緊急電源供電容量規定，下列敘述何者錯誤？",15,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-113-1-water-chemical-012",113,"自動撒水設備進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-111-1-water-chemical-012",111,"有關水霧滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-110-1-water-chemical-012",110,"進行乾粉滅火設備性能檢查時，對於滅火藥劑檢查注意事項，溫度及濕度超過多少以上時，應暫停檢查？",{"webId":66,"year":67,"stem":68,"number":13},"fire-109-1-water-chemical-012",109,"消防水系統設置呼水裝置時，其溢水用排水管口徑應在多少尺寸以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-108-1-water-chemical-012",108,"主成分為碳酸氫鉀及尿素化合物之乾粉滅火藥劑，採全區放射方式時，每立方公尺防護區域所需滅火藥劑量為多少公斤？",1785129971853]